Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

3273234 Phoenix Contact Terminal Blocks

Phoenix Contact 3273234 Distribution block, Block with horizontal alignment and integrated supply, The blocks can be bridged with one another via the conductor shaft. For corresponding plug-in bridges, see accessories, nom. voltage: 690 V, nominal current: 24 A, connection metho
Phoenix Contact

Part#:3273234

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 43

Nov 27, 2024

Distribution block, Block with horizontal alignment and integrated supply, The blocks can be bridged with one another via the conductor shaft. For corresponding plug-in bridges, see accessories, nom. voltage: 690 V, nominal current: 24 A, connection metho

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 3273234 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Conductor cross section short circuit testing
    10 mm²
  • Number of levels
    1
  • Flammability rating according to UL 94
    V0
  • Insulating material group
    I
  • Nominal voltage UN
    690 V
  • Back of the hand protection
    guaranteed
  • Result of flexion and pull-out test
    Test passed
  • Bending test conductor cross section/weight
    0.5 mm² / 0.3 kg
  • Setpoint
    5 N
  • Short circuit stability result
    Test passed
  • Result of aging test
    Test passed
  • Test spectrum
    Service life test category 2, bogie-mounted
  • Test duration per axis
    5 h
  • Shock form
    Half-sine
  • Relative insulation material temperature index (Elec., UL 746 B)
    130 °C
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
    130 °C
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 3
  • Height NS 35/7,5
    30.9 mm
  • Conductor cross section solid max.
    10 mm²
  • Max. AWG conductor cross section, flexible
    10
  • Connection cross sections directly pluggable
    1 mm² 10 mm²
  • Overvoltage category
    III
  • Maximum load current
    57 A (with 10 mm² conductor cross section)
  • Finger protection
    guaranteed
  • Power frequency withstand voltage setpoint
    1.89 kV
  • Result of tight fit on support
    Test passed
  • Result of temperature-rise test
    Test passed
  • Oscillation, broadband noise test result
    Test passed
  • UNSPSC 12.01
    39121410
  • Shock protection test specification
    DIN EN 50274 (VDE 0660-514):2002-11
  • Bending test turns
    135
  • Requirement temperature-rise test
    Increase in temperature ≤ 45 K
  • Result of thermal test
    Test passed
  • ASD level
    6.12 (m/s2)2/Hz
  • Shock test result
    Test passed
  • Value
    1 mm²
  • Insulating material
    PA
  • Nominal current IN
    41 A (with 6 mm² conductor cross section)
  • Result of power-frequency withstand voltage test
    Test passed
  • Bending test rotation speed
    10 rpm
  • Tight fit on carrier
    NS 35
  • Test frequency
    f1 = 5 Hz to f2 = 250 Hz
  • Connection method
    Push-in connection
  • Open side panel
    No
  • Result of surge voltage test
    Test passed
  • Result of the test for mechanical stability of terminal points (5 x conductor connection)
    Test passed
  • Tensile test result
    Test passed
  • Result of voltage-drop test
    Test passed
  • Short-time current
    1.2 kA
  • Ageing test for screwless modular terminal block temperature cycles
    192
  • Acceleration
    30g
  • Test directions
    X-, Y- and Z-axis (pos. and neg.)
  • UNSPSC 6.01
    30211811
  • Static insulating material application in cold
    -60 °C
  • Length
    45.7 mm
  • Conductor cross section solid min.
    1 mm²
  • Conductor cross section flexible max.
    10 mm²
  • Conductor cross section flexible, with ferrule with plastic sleeve max.
    6 mm²
  • Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
    1.5 mm²
  • Permissible humidity (storage/transport)
    30 % ... 70 %
  • China RoHS
    Environmentally friendly use period: unlimited = EFUP-e
  • ECLASS 5.1
    27141120
  • ETIM 3.0
    EC000897
  • ETIM 7.0
    EC000897
  • Number of connections
    13
  • Nominal cross section
    2.5 mm²
  • Test specification, shock test
    DIN EN 50155 (VDE 0115-200):2008-03
  • Shock duration
    18 ms
  • Smoke gas toxicity NFPA 130 (SMP 800C)
    passed
  • Conductor cross section flexible, with ferrule with plastic sleeve min.
    0.5 mm²
  • Connection
    Feed-in stage
  • Ambient temperature (actuation)
    -5 °C ... 70 °C
  • ECLASS 4.0
    27141121
  • ECLASS 6.0
    27141100
  • ECLASS 9.0
    27141120
  • Color
    black
  • Test specification, oscillation, broadband noise
    DIN EN 50155 (VDE 0115-200):2008-03
  • Number of shocks per direction
    3
  • Calorimetric heat release NFPA 130 (ASTM E 1354)
    28 MJ/kg
  • Stripping length
    10 mm ... 12 mm
  • Conductor cross section AWG max.
    8
  • Note
    The max. load current must not be exceeded by the total current of all connected conductors.
  • Nominal cross section feed-in
    6 mm²
  • Rated surge voltage
    8 kV
  • Maximum total current
    57 A (with 10 mm² conductor cross section)
  • Surface flammability NFPA 130 (ASTM E 162)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 3
  • Width
    41 mm
  • Connection in acc. with standard
    IEC 60947-7-1
  • Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
    0.5 mm²
  • Operating temperature
    -60 °C ... 105 °C (max. short-term operating temperature 130°C)
  • ECLASS 10.0.1
    27141120
  • ECLASS 7.0
    27141120
  • ETIM 6.0
    EC000897
  • UNSPSC 11
    39121410
  • UNSPSC 19.0
    39121410
  • Potentials
    1
  • Degree of pollution
    3
  • Maximum power dissipation for nominal condition
    1.31 W (the value is based on one connection block and is multiplied according to the pin assignment)
  • Proof of thermal characteristics (needle flame) effective duration
    30 s
  • Specific optical density of smoke NFPA 130 (ASTM E 662)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 3
  • Fire protection for rail vehicles (DIN EN 45545-2) R26
    HL 1 - HL 3
  • Conductor cross section AWG min.
    20
  • Conductor cross section flexible min.
    0.5 mm²
  • Conductor cross section flexible, with ferrule without plastic sleeve min.
    0.5 mm²
  • Ambient temperature (assembly)
    -5 °C ... 70 °C
  • ECLASS 4.1
    27141121
  • ETIM 4.0
    EC000897
  • UNSPSC 13.2
    39121410
  • UNSPSC 20.0
    39121410
  • Min. AWG conductor cross section, flexible
    20
  • Conductor cross section flexible, with ferrule without plastic sleeve max.
    6 mm²
  • Internal cylindrical gage
    A3
  • Ambient temperature (storage/transport)
    -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
  • ECLASS 11.0
    27141120
  • ECLASS 5.0
    27141120
  • UNSPSC 7.0901
    39121410
  • UNSPSC 18.0
    39121410
  • UNSPSC 21.0
    39121410

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


This item can ship within 24h!

1-year warranty

$6.15

Stock:

43

Select Qty:

$6.15

$6.15 each

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo