Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

3273048 Phoenix Contact Terminal Blocks

Phoenix Contact 3273048 Distribution block, Block with vertical alignment, The blocks can be bridged with one another via the conductor shaft. For corresponding plug-in bridges, see accessories, nom. voltage: 690 V, nominal current: 24 A, connection method: Push-in connection, n
Phoenix Contact

Part#:3273048

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 64

Nov 26, 2024

Distribution block, Block with vertical alignment, The blocks can be bridged with one another via the conductor shaft. For corresponding plug-in bridges, see accessories, nom. voltage: 690 V, nominal current: 24 A, connection method: Push-in connection, n

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 3273048 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Number of levels
    1
  • Nominal cross section
    2.5 mm²
  • Rated surge voltage
    8 kV
  • Insulating material group
    I
  • Maximum total current
    48 A
  • Shock protection test specification
    DIN EN 50274 (VDE 0660-514):2002-11
  • Finger protection
    guaranteed
  • Result of flexion and pull-out test
    Test passed
  • Tensile test result
    Test passed
  • Setpoint
    1 N
  • Result of temperature-rise test
    Test passed
  • Result of aging test
    Test passed
  • Test duration per axis
    5 h
  • ASD level
    6.12 (m/s2)2/Hz
  • Shock duration
    18 ms
  • Surface flammability NFPA 130 (ASTM E 162)
    passed
  • Smoke gas toxicity NFPA 130 (SMP 800C)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 3
  • Height NS 35/7,5
    32.4 mm
  • Conductor cross section solid min.
    0.34 mm²
  • Conductor cross section flexible min.
    0.14 mm²
  • Conductor cross section flexible, with ferrule with plastic sleeve max.
    2.5 mm²
  • Conductor cross section flexible, with ferrule without plastic sleeve min.
    0.34 mm²
  • Permissible humidity (storage/transport)
    30 % ... 70 %
  • ECLASS 10.0.1
    27141120
  • ECLASS 4.1
    27141121
  • ECLASS 5.1
    27141120
  • ETIM 6.0
    EC000897
  • UNSPSC 13.2
    39121410
  • UNSPSC 19.0
    39121410
  • Bending test turns
    135
  • Bending test rotation speed
    10 rpm
  • Tight fit on carrier
    NS 35
  • Short circuit stability result
    Test passed
  • Result of thermal test
    Test passed
  • Test frequency
    f1 = 5 Hz to f2 = 250 Hz
  • Number of shocks per direction
    3
  • Shock test result
    Test passed
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
    130 °C
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 3
  • Fire protection for rail vehicles (DIN EN 45545-2) R26
    HL 1 - HL 3
  • Connection method
    Push-in connection
  • Conductor cross section AWG min.
    26
  • Max. AWG conductor cross section, flexible
    14
  • Conductor cross section flexible max.
    2.5 mm²
  • Conductor cross section flexible, with ferrule with plastic sleeve min.
    0.34 mm²
  • China RoHS
    Environmentally friendly use period: unlimited = EFUP-e
  • Ambient temperature (assembly)
    -5 °C ... 70 °C
  • ECLASS 4.0
    27141121
  • ECLASS 9.0
    27141120
  • UNSPSC 12.01
    39121410
  • Number of connections
    18
  • Color
    red
  • Insulating material
    PA
  • Overvoltage category
    III
  • Maximum load current
    32 A
  • Open side panel
    No
  • Nominal voltage UN
    690 V
  • Result of surge voltage test
    Test passed
  • Power frequency withstand voltage setpoint
    1.89 kV
  • Result of power-frequency withstand voltage test
    Test passed
  • Result of tight fit on support
    Test passed
  • Conductor cross section short circuit testing
    4 mm²
  • Result of voltage-drop test
    Test passed
  • Proof of thermal characteristics (needle flame) effective duration
    30 s
  • Ageing test for screwless modular terminal block temperature cycles
    192
  • Test directions
    X-, Y- and Z-axis (pos. and neg.)
  • Shock form
    Half-sine
  • Relative insulation material temperature index (Elec., UL 746 B)
    130 °C
  • Calorimetric heat release NFPA 130 (ASTM E 1354)
    28 MJ/kg
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 3
  • Height NS 15
    30.4 mm
  • Connection in acc. with standard
    IEC 60947-7-1
  • Conductor cross section solid max.
    4 mm²
  • Conductor cross section flexible, with ferrule without plastic sleeve max.
    2.5 mm²
  • Ambient temperature (storage/transport)
    -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
  • Internal cylindrical gage
    A3
  • Ambient temperature (actuation)
    -5 °C ... 70 °C
  • ECLASS 5.0
    27141120
  • ETIM 3.0
    EC000897
  • UNSPSC 6.01
    30211811
  • UNSPSC 20.0
    39121410
  • ECLASS 7.0
    27141120
  • ETIM 7.0
    EC000897
  • UNSPSC 18.0
    39121410
  • UNSPSC 11
    39121410
  • Note
    The max. load current must not be exceeded by the total current of all connected conductors.
  • Potentials
    1
  • Flammability rating according to UL 94
    V0
  • Degree of pollution
    3
  • Nominal current IN
    24 A
  • Maximum power dissipation for nominal condition
    0.77 W (the value is based on one connection block and is multiplied according to the pin assignment)
  • Back of the hand protection
    guaranteed
  • Result of the test for mechanical stability of terminal points (5 x conductor connection)
    Test passed
  • Bending test conductor cross section/weight
    0.14 mm² / 0.2 kg
  • Requirement temperature-rise test
    Increase in temperature ≤ 45 K
  • Short-time current
    0.48 kA
  • Test spectrum
    Service life test category 2, bogie-mounted
  • Oscillation, broadband noise test result
    Test passed
  • Acceleration
    30g
  • Test specification, shock test
    DIN EN 50155 (VDE 0115-200):2008-03
  • Static insulating material application in cold
    -60 °C
  • Specific optical density of smoke NFPA 130 (ASTM E 662)
    passed
  • Length
    58.1 mm
  • Width
    28.6 mm
  • Stripping length
    8 mm ... 10 mm
  • Conductor cross section AWG max.
    12
  • Min. AWG conductor cross section, flexible
    26
  • Connection cross sections directly pluggable
    0.34 mm² 4 mm² 24 12
  • Operating temperature
    -60 °C ... 105 °C (max. short-term operating temperature 130°C)
  • ECLASS 11.0
    27141120
  • ECLASS 6.0
    27141100
  • ETIM 4.0
    EC000897
  • UNSPSC 7.0901
    39121410
  • UNSPSC 21.0
    39121410
  • Test specification, oscillation, broadband noise
    DIN EN 50155 (VDE 0115-200):2008-03

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


This item can ship within 24h!

1-year warranty

$8.10

Stock:

64

Select Qty:

$8.10

$8.10 each

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo