Nikki Gonzales
Nick Goetz
Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

2904625 Phoenix Contact AC/DC Power Supplies

Phoenix Contact 2904625 Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, NFC interface, and protective coating, input: 1-phase, output: 24 V DC / 10 A
Phoenix Contact

Part#:2904625

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

About the product: Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, NFC interface, and protective coating, input: 1-phase, output: 24 V DC / 10 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2904625 Phoenix Contact price in the box on the right side or send a quick quote.

2904625 Product Details

  • Ambient temperature (operation)
    -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Nominal input voltage range
    100 V AC ... 240 V AC
  • AC frequency range
    50 Hz ... 60 Hz -10 % ... +10 %
  • Nominal power consumption
    274 VA
  • Mains buffering time
    typ. 42 ms (120 V AC)
  • Dynamic Boost (IDyn.Boost)
    20 A (5 s)
  • Connection in series
    yes
  • Residual ripple
    < 80 mVPP (with nominal values)
  • Power loss nominal load max.
    < 20 W (120 V AC)
  • Insulation voltage output / PE
    0.5 kV DC (type test)
  • Connection method
    Push-in connection
  • Conductor cross section AWG max.
    16
  • Standard – Safety extra-low voltage
    IEC 61010-1 (SELV)
  • CSA
    CAN/CSA-C22.2 No. 60950-1-07
  • Additional text
    Test Level 2
  • Harmonic currents
    EN 61000-3-2
  • Signal
    4 kV (Test Level 4 - asymmetrical)
  • Surge voltage load (surge)
    EN 61000-4-5
  • Frequency
    50 Hz
  • Attenuated sinusoidal oscillations (ring wave)
    EN 61000-4-12
  • Test level 5
    16.7 Hz 50 Hz 60 Hz (Test Level 4)
  • Input, output (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • Criterion A
    Normal operating behavior within the specified limits.
  • ECLASS 10.0.1
    27040701
  • Installation distance top/bottom
    50 mm / 50 mm
  • Degree of pollution
    2
  • Discharge current to PE
    < 3.5 mA
  • Input fuse
    8 A (slow-blow, internal)
  • Protective circuit/component
    Varistor, gas-filled surge arrester
  • Static Boost (IStat.Boost)
    12.5 A
  • Derating
    > 60 °C (2.5%/K)
  • Protection against overvoltage at the output (OVP)
    ≤ 32 V DC
  • Environmental protection directive
    RoHS Directive 2011/65/EU
  • Mounting position
    horizontal DIN rail NS 35, EN 60715
  • Conductor cross section flexible min.
    0.2 mm²
  • EMC requirements for noise immunity
    EN 61000-6-1
  • Standard – Limitation of mains harmonic currents
    EN 61000-3-2
  • Standard - Safe isolation
    IEC 61010-2-201
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Contact discharge
    8 kV (Test Level 4)
  • Test field strength
    100 A/m
  • Input
    2 kV (Test Level 4 - symmetrical)
  • I/O/S
    asymmetrical
  • Voltage dip
    0 %
  • Test level 1
    15 Hz 150 Hz (Test Level 4)
  • Attenuated oscillating wave
    EN 61000-4-18
  • Input, output (test level 3)
    Test Level 3 - asymmetrical
  • Criterion C
    Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
  • ECLASS 11.0
    27040701
  • Depth
    125 mm
  • Depth with alternative assembly
    53 mm
  • Degree of protection
    IP20
  • Max. permissible relative humidity (operation)
    ≤ 100 % (at 25 °C, non-condensing)
  • Input voltage range
    100 V AC ... 240 V AC -15 % ... +10 %
  • Current consumption
    3.4 A (100 V AC)
  • Recommended breaker for input protection
    10 A ... 16 A (Characteristic B, C, D, K or comparable)
  • Power factor (cos phi)
    0.94
  • Setting range of the output voltage (USet)
    24 V DC ... 29.5 V DC (constant capacity)
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • Typical response time
    300 ms (from SLEEP MODE)
  • Efficiency
    typ. 92.5 % (120 V AC)
  • Insulation voltage input / PE
    3.5 kV AC (type test)
  • Conductor cross section solid max.
    1 mm²
  • Stripping length
    8 mm
  • HART FSK Physical Layer Test Specification Compliance
    Output voltage UOut compliant
  • Mains variation/undervoltage
    SEMI F47-0706, EN 61000-4-11
  • Shipbuilding approval
    DNV GL, PRS, BV, LR, ABS
  • DNV GL conducted interference
    Class A
  • Discharge in air
    15 kV (Test Level 4)
  • Comments
    Criterion A
  • Power frequency magnetic field
    EN 61000-4-8
  • Number of periods
    0,5 / 1 / 5 / 50 / 250 periods
  • Test level 3
    1.5 kHz 15 kHz (Test Level 4)
  • Test level 4
    15 kHz 150 kHz (Test Level 4)
  • REACh SVHC
    Lead 7439-92-1
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • Installation distance right/left
    5 mm / 5 mm
  • Ambient temperature (start-up type tested)
    -40 °C
  • Installation height
    ≤ 5000 m (> 2000 m, observe derating)
  • Frequency range (fN)
    50 Hz ... 60 Hz -10 % ... +10 %
  • Inrush current
    typ. 12 A (at 25 °C)
  • Type of protection
    Transient surge protection
  • Nominal output voltage
    24 V DC
  • Selective Fuse Breaking (ISFB)
    60 A (15 ms)
  • Feedback voltage resistance
    ≤ 35 V DC
  • Maximum power dissipation in no-load condition
    < 3 W (120 V AC)
  • Net weight
    0.9 kg
  • Insulation voltage input/output
    4 kV AC (type test)
  • Conductor cross section solid min.
    0.2 mm²
  • EMC requirements for noise emission
    EN 61000-6-3
  • Standard - Electrical safety
    IEC 61010-2-201 (SELV)
  • Rail applications
    EN 50121-3-2
  • SIQ
    BG (type approved)
  • Noise emission
    EN 55016
  • Electrostatic discharge
    EN 61000-4-2
  • Electromagnetic HF field
    EN 61000-4-3
  • Fast transients (burst)
    EN 61000-4-4
  • Conducted interference
    EN 61000-4-6
  • Voltage
    2.5 kV
  • Test level 2
    150 Hz 1.5 kHz (Test Level 4)
  • Input, output (test level 2)
    100 kHz 1 MHz (Test Level 3 - asymmetrical)
  • Test level 6
    16.7 Hz 50 Hz 60 Hz (Test Level 4)
  • ECLASS 9.0
    27040701
  • Control deviation
    < 0.5 % (Static load change 10 % ... 90 %)
  • Output power
    240 W
  • MTBF (IEC 61709, SN 29500)
    > 1251000 h (25 °C)
  • Protection class
    I
  • Assembly instructions
    alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
  • Conductor cross section AWG min.
    24
  • Standard - Safety of transformers
    IEC 61558-2-16 pending
  • EMC requirements, power plant
    IEC 61850-3
  • Standard - safety for equipment for measurement, control, and laboratory use
    IEC 61010-1
  • UL approvals
    UL Listed UL 508
  • Conducted noise emission
    EN 55016
  • DNV GL noise radiation
    Class B
  • Frequency range
    50 Hz ... 60 Hz
  • Output
    1 kV (Test Level 3 - symmetrical)
  • Voltage dips
    EN 61000-4-11
  • Pulse-shape magnetic field
    EN 61000-4-9
  • Damped oscillating magnetic field
    EN 61000-4-10
  • Asymmetrical conducted disturbance variables
    EN 61000-4-16
  • Signals (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • Signals (test level 2)
    100 kHz 1 MHz (Test Level 3 - asymmetrical)
  • Height
    130 mm
  • Height with alternative assembly
    130 mm
  • Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
  • Climatic class
    3K3 (in acc. with EN 60721)
  • Dielectric strength maximum
    300 V AC 60 s
  • Nominal output current (IN)
    10 A
  • Flicker
    EN 61000-3-3
  • Width
    50 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Width with alternative assembly
    122 mm
  • Conductor cross section flexible max.
    1.5 mm²

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

2904625

Select Qty:

Average response time: 11 minutes

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty