Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

2904610 Phoenix Contact AC/DC Power Supplies

Phoenix Contact 2904610 Primary-switched QUINT POWER power supply for DIN rail mounting with free choice of output characteristic curve and SFB (Selective Fuse Breaking) technology, input: 1-phase, output: 48 V DC / 5 A
Phoenix Contact

Part#:2904610

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 178

Nov 19, 2024

Primary-switched QUINT POWER power supply for DIN rail mounting with free choice of output characteristic curve and SFB (Selective Fuse Breaking) technology, input: 1-phase, output: 48 V DC / 5 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2904610 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Depth with alternative assembly
    53 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Degree of pollution
    2
  • Input voltage range
    100 V AC ... 240 V AC -15 % ... +10 %
  • Current consumption
    3.4 A (100 V AC)
  • Mains buffering time
    typ. 43 ms (120 V AC)
  • Protective circuit/component
    Varistor, gas-filled surge arrester
  • Nominal output voltage
    48 V DC
  • Static Boost (IStat.Boost)
    6.25 A
  • Residual ripple
    < 70 mVPP (with nominal values)
  • Maximum power dissipation in no-load condition
    < 3 W (120 V AC)
  • Efficiency
    typ. 92.3 % (120 V AC)
  • Insulation voltage output / PE
    0.5 kV DC (type test)
  • Depth
    125 mm
  • Installation distance right/left
    5 mm / 5 mm
  • Ambient temperature (operation)
    -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Climatic class
    3K3 (in acc. with EN 60721)
  • Dielectric strength maximum
    300 V AC 60 s
  • Discharge current to PE
    < 3.5 mA
  • Type of protection
    Transient surge protection
  • Width with alternative assembly
    122 mm
  • Installation distance top/bottom
    50 mm / 50 mm
  • Degree of protection
    IP20
  • Installation height
    ≤ 5000 m (> 2000 m, observe derating)
  • AC frequency range
    50 Hz ... 60 Hz -10 % ... +10 %
  • Nominal power consumption
    271 VA
  • Recommended breaker for input protection
    10 A ... 16 A (Characteristic B, C, D, K or comparable)
  • Selective Fuse Breaking (ISFB)
    30 A (15 ms)
  • Derating
    > 60 °C ... 70 °C (2.5%/K)
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • Protection against overvoltage at the output (OVP)
    ≤ 60 V DC
  • Power loss nominal load max.
    < 19 W (120 V AC)
  • Environmental protection directive
    RoHS Directive 2011/65/EU
  • Protection class
    I
  • Mounting position
    horizontal DIN rail NS 35, EN 60715
  • Conductor cross section AWG min.
    24
  • Standard - Safety of transformers
    EN 61558-2-16
  • Standard - safety for equipment for measurement, control, and laboratory use
    IEC 61010-1
  • Standard - Safe isolation
    IEC 61558-2-16
  • UL approvals
    UL Listed UL 508
  • Conducted noise emission
    EN 55016
  • Frequency range
    50 Hz ... 60 Hz
  • Fast transients (burst)
    EN 61000-4-4
  • Signal
    4 kV (Test Level 4 - asymmetrical)
  • I/O/S
    asymmetrical
  • Voltage dips
    EN 61000-4-11
  • Damped oscillating magnetic field
    EN 61000-4-10
  • Asymmetrical conducted disturbance variables
    EN 61000-4-16
  • Input, output (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • Criterion A
    Normal operating behavior within the specified limits.
  • Width
    50 mm
  • Height with alternative assembly
    130 mm
  • Ambient temperature (start-up type tested)
    -40 °C
  • Max. permissible relative humidity (operation)
    ≤ 95 % (at 25 °C, non-condensing)
  • Nominal input voltage range
    100 V AC ... 240 V AC
  • Frequency range (fN)
    50 Hz ... 60 Hz -10 % ... +10 %
  • Inrush current
    typ. 16 A (at 25 °C)
  • Input fuse
    8 A (slow-blow, internal)
  • Nominal output current (IN)
    5 A
  • Connection in series
    yes
  • Output power
    240 W
  • Typical response time
    300 ms (from SLEEP MODE)
  • Insulation voltage input/output
    4 kV AC (type test)
  • Connection method
    Push-in connection
  • Conductor cross section flexible min.
    0.2 mm²
  • Height
    130 mm
  • Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
  • China RoHS
    Environmentally Friendly Use Period = 25;
  • ECLASS 5.1
    27049002
  • Setting range of the output voltage (USet)
    48 V DC ... 56 V DC (constant capacity)
  • Dynamic Boost (IDyn.Boost)
    10 A (5 s)
  • Feedback voltage resistance
    ≤ 60 V DC
  • Control deviation
    < 0.5 % (Static load change 10 % ... 90 %)
  • Net weight
    1 kg
  • MTBF (IEC 61709, SN 29500)
    > 1242000 h (25 °C)
  • Insulation voltage input / PE
    3.5 kV AC (type test)
  • Assembly instructions
    alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
  • EMC requirements for noise immunity
    EN 61000-6-1
  • Stripping length
    8 mm
  • Standard - Electrical safety
    IEC 61010-2-201 (SELV)
  • Rail applications
    EN 50121-3-2
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • Contact discharge
    8 kV (Test Level 4)
  • Flicker
    EN 61000-3-3
  • Test field strength
    110 A/m
  • Conducted interference
    EN 61000-4-6
  • Voltage
    2.5 kV
  • Voltage dip
    0 %
  • Test level 2
    150 Hz 1.5 kHz (Test Level 4)
  • Test level 3
    1.5 kHz 15 kHz (Test Level 4)
  • Test level 6
    16.7 Hz 50 Hz 60 Hz (Test Level 4)
  • Signals (test level 2)
    100 kHz 1 MHz (Test Level 3 - asymmetrical)
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • REACh SVHC
    Lead 7439-92-1
  • ETIM 6.0
    EC002540
  • Conductor cross section solid min.
    0.2 mm²
  • Conductor cross section flexible max.
    1.5 mm²
  • Conductor cross section solid max.
    1 mm²
  • EMC requirements for noise emission
    EN 61000-6-3
  • Standard – Safety extra-low voltage
    IEC 61010-1 (SELV)
  • Standard – Limitation of mains harmonic currents
    EN 61000-3-2
  • CSA
    CAN/CSA-C22.2 No. 60950-1-07
  • Harmonic currents
    EN 61000-3-2
  • Electrostatic discharge
    EN 61000-4-2
  • Input
    2 kV (Test Level 4 - symmetrical)
  • Output
    1 kV (Test Level 3 - symmetrical)
  • Power frequency magnetic field
    EN 61000-4-8
  • Frequency
    50 Hz
  • Number of periods
    0,5 / 1 / 5 / 50 / 250 periods
  • Attenuated sinusoidal oscillations (ring wave)
    EN 61000-4-12
  • Attenuated oscillating wave
    EN 61000-4-18
  • Input, output (test level 2)
    10 MHz
  • Signals (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • ECLASS 10.0.1
    27040701
  • ETIM 7.0
    EC002540
  • Conductor cross section AWG max.
    16
  • HART FSK Physical Layer Test Specification Compliance
    Output voltage UOut compliant
  • EMC requirements, power plant
    IEC 61850-3
  • Mains variation/undervoltage
    SEMI F47-0706, EN 61000-4-11
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Noise emission
    EN 55016
  • Discharge in air
    15 kV (Test Level 4)
  • Electromagnetic HF field
    EN 61000-4-3
  • Comments
    Criterion A
  • Additional text
    Test Level 2
  • Pulse-shape magnetic field
    EN 61000-4-9
  • Test level 1
    15 Hz 150 Hz (Test Level 4)
  • Test level 4
    15 kHz 150 kHz (Test Level 4)
  • Test level 5
    16.7 Hz 50 Hz 60 Hz (Test Level 4)
  • Input, output (test level 3)
    100 kHz 1 MHz (Test Level 3 - asymmetrical)
  • Criterion C
    Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
  • ECLASS 11.0
    27040701
  • ECLASS 9.0
    27040701

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


This item can ship within 24h!

1-year warranty

$398.35

Stock:

178

Select Qty:

$398.35

$398.35 each

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo