Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

2904603 Phoenix Contact AC/DC Power Supplies

Phoenix Contact 2904603 Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, and NFC interface, input: 1-phase, output: 24 V DC/40 A
Phoenix Contact

Part#:2904603

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 391

Nov 21, 2024

Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, and NFC interface, input: 1-phase, output: 24 V DC/40 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2904603 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Installation distance right/left
    5 mm / 5 mm
  • Ambient temperature (start-up type tested)
    -40 °C
  • Degree of pollution
    2
  • Frequency range (fN)
    50 Hz ... 60 Hz -10 % ... +10 %
  • Depth
    140 mm
  • Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
  • Climatic class
    3K3 (in acc. with EN 60721)
  • Nominal input voltage range
    100 V AC ... 240 V AC
  • Current consumption
    13.6 A (100 V AC)
  • Inrush current
    typ. 12 A (at 25 °C)
  • Nominal output current (IN)
    40 A
  • Selective Fuse Breaking (ISFB)
    215 A (15 ms)
  • Feedback voltage resistance
    ≤ 35 V DC
  • Output power
    960 W
  • Power loss nominal load max.
    < 50 W (120 V AC)
  • Environmental protection directive
    RoHS Directive 2011/65/EU
  • Protection class
    I
  • Conductor cross section AWG min.
    24
  • Height
    130 mm
  • Installation distance top/bottom
    50 mm / 50 mm
  • Max. permissible relative humidity (operation)
    ≤ 95 % (at 25 °C, non-condensing)
  • Installation height
    ≤ 5000 m (> 2000 m, observe derating)
  • Discharge current to PE
    < 3.5 mA
  • Nominal output voltage
    24 V DC
  • Static Boost (IStat.Boost)
    45 A
  • Width
    120 mm
  • Degree of protection
    IP20
  • Ambient temperature (operation)
    -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Input voltage range
    100 V AC ... 240 V AC -15 % ... +10 %
  • Recommended breaker for input protection
    16 A ... 20 A (Characteristic B, C, D, K or comparable)
  • Derating
    > 60 °C ... 70 °C (2.5%/K)
  • Control deviation
    < 0.5 % (Static load change 10 % ... 90 %)
  • Insulation voltage input/output
    4 kV AC (type test)
  • Conductor cross section solid min.
    0.2 mm²
  • Stripping length
    8 mm
  • EMC requirements, power plant
    IEC 61850-3
  • Standard - Safe isolation
    IEC 61558-2-16
  • Rail applications
    EN 50121-3-2
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Harmonic currents
    EN 61000-3-2
  • Contact discharge
    8 kV (Test Level 4)
  • Input
    2 kV (Test Level 4 - symmetrical)
  • Surge voltage load (surge)
    EN 61000-4-5
  • Damped oscillating magnetic field
    EN 61000-4-10
  • Attenuated sinusoidal oscillations (ring wave)
    EN 61000-4-12
  • Test level 4
    15 kHz 150 kHz (Test Level 4)
  • Input, output (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • Signals (test level 2)
    100 kHz 1 MHz (Test Level 3 - asymmetrical)
  • ECLASS 10.0.1
    27040701
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Dielectric strength maximum
    300 V AC 60 s
  • Input fuse
    16 A (slow-blow, internal)
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • Protection against overvoltage at the output (OVP)
    ≤ 32 V DC
  • Efficiency
    typ. 94.8 % (120 V AC)
  • Mounting position
    horizontal DIN rail NS 35, EN 60715
  • Conductor cross section flexible min.
    0.2 mm²
  • EMC requirements for noise immunity
    EN 61000-6-1
  • HART FSK Physical Layer Test Specification Compliance
    Output voltage UOut compliant
  • SIQ
    BG (type approved)
  • Conducted noise emission
    EN 55016
  • Flicker
    EN 61000-3-3
  • DNV GL conducted interference
    Class A
  • Electromagnetic HF field
    EN 61000-4-3
  • Signal
    4 kV (Test Level 4 - asymmetrical)
  • Frequency
    50 Hz
  • Pulse-shape magnetic field
    EN 61000-4-9
  • Test level 3
    1.5 kHz 15 kHz (Test Level 4)
  • Test level 7
    16.7 Hz 50 Hz 60 Hz (Test Level 4)
  • Signals (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • Criterion A
    Normal operating behavior within the specified limits.
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 9.0
    27040701
  • Mains buffering time
    typ. 29 ms (120 V AC)
  • Setting range of the output voltage (USet)
    24 V DC ... 29.5 V DC (constant capacity)
  • Dynamic Boost (IDyn.Boost)
    60 A (5 s)
  • Residual ripple
    < 50 mVPP (with nominal values)
  • Maximum power dissipation in no-load condition
    < 4 W (120 V AC)
  • MTBF (IEC 61709, SN 29500)
    > 934000 h (25 °C)
  • Connection method
    Push-in connection
  • Conductor cross section flexible max.
    1.5 mm²
  • Standard - Safety of transformers
    EN 61558-2-16
  • Standard - safety for equipment for measurement, control, and laboratory use
    IEC 61010-1
  • CSA
    CAN/CSA-C22.2 No. 60950-1-07
  • Shipbuilding approval
    DNV GL
  • Additional text
    Test Level 2
  • Frequency range
    50 Hz ... 60 Hz
  • Output
    1 kV (Test Level 3 - symmetrical)
  • Voltage
    2.5 kV
  • Number of periods
    0,5 / 1 / 5 / 50 / 250 periods
  • Test level 2
    150 Hz 1.5 kHz (Test Level 4)
  • Test level 5
    16.7 Hz 50 Hz 60 Hz (Test Level 4)
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • Connection in series
    yes
  • Net weight
    2.6 kg
  • Insulation voltage input / PE
    2.5 kV AC (type test)
  • Insulation voltage output / PE
    0.5 kV DC (type test)
  • Conductor cross section solid max.
    1 mm²
  • Conductor cross section AWG max.
    16
  • Standard - Electrical safety
    IEC 61010-2-201 (SELV)
  • Mains variation/undervoltage
    SEMI F47-0706, EN 61000-4-11
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • Noise emission
    EN 55016
  • Electrostatic discharge
    EN 61000-4-2
  • Comments
    Criterion A
  • Fast transients (burst)
    EN 61000-4-4
  • I/O/S
    asymmetrical
  • Power frequency magnetic field
    EN 61000-4-8
  • Test level 1
    15 Hz 150 Hz (Test Level 4)
  • Test level 6
    150 Hz 180 Hz (Test Level 4)
  • Attenuated oscillating wave
    EN 61000-4-18
  • Input, output (test level 3)
    100 kHz 1 MHz (Test Level 3 - asymmetrical)
  • China RoHS
    Environmentally Friendly Use Period = 25;
  • ECLASS 11.0
    27040701
  • EMC requirements for noise emission
    EN 61000-6-3
  • Standard – Safety extra-low voltage
    IEC 61010-1 (SELV)
  • Standard – Limitation of mains harmonic currents
    EN 61000-3-2
  • UL approvals
    UL Listed UL 508
  • DNV GL noise radiation
    Class B
  • Discharge in air
    15 kV (Test Level 4)
  • Test field strength
    110 A/m
  • Conducted interference
    EN 61000-4-6
  • Voltage dips
    EN 61000-4-11
  • Voltage dip
    0 %
  • Asymmetrical conducted disturbance variables
    EN 61000-4-16
  • Input, output (test level 2)
    10 MHz
  • Criterion C
    Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


This item can ship within 24h!

1-year warranty

$593.10

Stock:

391

Select Qty:

$593.10

$593.10 each

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

This item can ship within 5 days!

UBC10.241 Part Image. Manufactured by Puls.

UBC10.241

$596.31

Verified stock: 14

PULS UBC10.241 is an Uninterruptible Power Supply (UPS) control module within the U-series, featuring a built-in battery with a 50% power reserve and a green status LED. This module is housed in aluminium and utilizes spring-clamp connections for installation. It measures W123mm x H124mm x D119mm and operates on a supply voltage range of 22.5Vdc to 30Vdc, with a nominal 24Vdc. The rated current is 10A at 22.5Vdc and can reach up to 15A in buffer mode for less than 5 seconds at full output voltage. It supports DIN rail mounting and can operate in ambient air temperatures ranging from 0 to +40°C. The current consumption is 1.1A at a 24Vdc input, and it is designed for DC networks. Visual position indicators include Ready, Buffering, Inhibit, and Replace Battery. Protection functions include output overvoltage protection with a typical 32Vdc and a maximum of 35Vdc, and overload/short-circuit protection with a minimum of 17.9A and a maximum of 21A at load impedance. It is advised not to use the DC-UPS in parallel to increase output power, but paralleling two units for 1+1 redundancy is possible for higher system reliability. The output voltage is regulated at 22.5Vdc in buffer mode with a 23Vdc turn-ON. The efficiency is rated at 0.978 with a 24Vdc input, and the rated power is 360W at 24Vdc and 240W/360W in buffer mode. Power dissipation/losses are 2.9W with a 24Vdc input at 0A output current and 5.5W at 10A output current. Ripple is maintained at 20mVpp across a frequency range of 20Hz to 20MHz at 50Ω. The electrical durability is rated at 137400 hours at 40°C with a 10A output and 24Vdc input, equivalent to 15 years or 131400 hours at both 40°C with a 5A output and 25°C with a 10A output.

Puls

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo