Nikki Gonzales
Nick Goetz
Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

2904617 Phoenix Contact AC/DC Power Supplies

Phoenix Contact 2904617 Primary-switched QUINT POWER supply for DIN rail mounting, with selectable output characteristic curve and SFB Technology (selective fuse breaking), protective coating and integrated decoupling MOSFET, input: 1-phase, output: 24 V DC / 20 A
Phoenix Contact

Part#:2904617

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 1

Apr 26, 2024

About the product: Primary-switched QUINT POWER supply for DIN rail mounting, with selectable output characteristic curve and SFB Technology (selective fuse breaking), protective coating and integrated decoupling MOSFET, input: 1-phase, output: 24 V DC / 20 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2904617 Phoenix Contact price in the box on the right side or send a quick quote.

2904617 Product Details

  • Frequency range (fN)
    50 Hz ... 60 Hz -10 % ... +10 %
  • Selective Fuse Breaking (ISFB)
    120 A (15 ms)
  • Protection against overvoltage at the output (OVP)
    < 30 V DC (double protection incl. shutdown)
  • Dynamic Boost (IDyn.Boost)
    30 A (5 s)
  • Feedback voltage resistance
    ≤ 35 V DC
  • Efficiency
    typ. 92.7 % (120 V AC)
  • Conductor cross section solid min.
    0.2 mm²
  • Conductor cross section flexible max.
    1.5 mm²
  • EMC requirements for noise emission
    EN 61000-6-3
  • Standard - Safe isolation
    IEC 61558-2-16
  • Connection in series
    yes
  • Maximum power dissipation in no-load condition
    < 5 W (120 V AC)
  • MTBF (IEC 61709, SN 29500)
    > 868000 h (25 °C)
  • Connection method
    Push-in connection
  • Conductor cross section AWG max.
    16
  • Nominal power consumption
    520 VA
  • Type of protection
    Transient surge protection
  • Test level 7
    16.7 Hz 50 Hz 60 Hz (Test Level 4)
  • Height
    130 mm
  • Installation distance right/left
    5 mm / 5 mm
  • Max. permissible relative humidity (operation)
    ≤ 100 % (at 25 °C, non-condensing)
  • Input voltage range
    100 V AC ... 240 V AC -15 % ... +10 %
  • Static Boost (IStat.Boost)
    25 A
  • Derating
    > 60 °C ... 70 °C (2.5%/K)
  • Output power
    480 W
  • Typical response time
    300 ms (from SLEEP MODE)
  • Mounting position
    horizontal DIN rail NS 35, EN 60715
  • Conductor cross section AWG min.
    24
  • Standard - Safety of transformers
    EN 61558-2-16
  • Explosive atmosphere
    IEC 60079-0
  • CSA
    CAN/CSA-C22.2 No. 60950-1-07
  • Conducted noise emission
    EN 55016
  • ECLASS 6.0
    27049000
  • Recommended breaker for input protection
    10 A ... 16 A (Characteristic B, C, D, K or comparable)
  • Nominal output current (IN)
    20 A
  • Test level 5
    16.7 Hz 50 Hz 60 Hz (Test Level 4)
  • Depth
    125 mm
  • Ambient temperature (operation)
    -40 °C ... 75 °C (> 60 °C Derating: 2.5 %/K)
  • Degree of pollution
    2
  • AC frequency range
    50 Hz ... 60 Hz -10 % ... +10 %
  • Mains buffering time
    typ. 36 ms (120 V AC)
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • Control deviation
    < 0.5 % (Static load change 10 % ... 90 %)
  • Power loss nominal load max.
    < 38 W (120 V AC)
  • Protection class
    I
  • Conductor cross section solid max.
    1 mm²
  • Stripping length
    8 mm
  • Standard - Electrical safety
    IEC 61010-2-201 (SELV)
  • Standard – Safety extra-low voltage
    IEC 61010-1 (SELV)
  • UL approvals
    UL Listed UL 508
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • Residual ripple
    < 30 mVPP (with nominal values)
  • Net weight
    1.3 kg
  • Insulation voltage input/output
    4 kV AC (type test)
  • Assembly instructions
    Alignable: horizontally 0 mm at Pout <50% PN, 5 mm at Pout ≥50% PN, next to active components 15 mm, vertically 50 mm
  • Conductor cross section flexible min.
    0.2 mm²
  • EMC requirements for noise immunity
    EN 61000-6-1
  • Standard - safety for equipment for measurement, control, and laboratory use
    IEC 61010-1
  • Mains variation/undervoltage
    SEMI F47-0706, EN 61000-4-11
  • SIQ
    BG (type approved)
  • Noise emission
    EN 55016
  • Flicker
    EN 61000-3-3
  • Electromagnetic HF field
    EN 61000-4-3
  • Output
    1 kV (Test Level 3 - symmetrical)
  • Conducted interference
    EN 61000-4-6
  • Voltage dips
    EN 61000-4-11
  • Pulse-shape magnetic field
    EN 61000-4-9
  • Electrostatic discharge
    EN 61000-4-2
  • Contact discharge
    8 kV (Test Level 4)
  • Input
    2 kV (Test Level 4 - symmetrical)
  • Power frequency magnetic field
    EN 61000-4-8
  • Damped oscillating magnetic field
    EN 61000-4-10
  • Test level 3
    1.5 kHz 15 kHz (Test Level 4)
  • Input, output (test level 2)
    10 MHz
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • ECLASS 7.0
    27049002
  • Discharge in air
    15 kV (Test Level 4)
  • Comments
    Criterion A
  • Signal
    4 kV (Test Level 4 - asymmetrical)
  • Voltage
    2.5 kV
  • Number of periods
    0,5 / 1 / 5 / 50 / 250 periods
  • Attenuated oscillating wave
    EN 61000-4-18
  • Input, output (test level 3)
    100 kHz 1 MHz (Test Level 3 - asymmetrical)
  • Criterion A
    Normal operating behavior within the specified limits.
  • ETIM 6.0
    EC002540
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Discharge current to PE
    < 3.5 mA
  • Input fuse
    12 A (slow-blow, internal)
  • Nominal input voltage range
    100 V AC ... 240 V AC
  • Climatic class
    3K3 (in acc. with EN 60721)
  • Width with alternative assembly
    122 mm
  • Installation height
    ≤ 5000 m (> 2000 m, observe derating)
  • Dielectric strength maximum
    300 V AC 60 s
  • Current consumption
    6.8 A (100 V AC)
  • Shipbuilding approval
    DNV GL applied for
  • Harmonic currents
    EN 61000-3-2
  • Additional text
    Test Level 2
  • DNV GL noise radiation
    Class B
  • Fast transients (burst)
    EN 61000-4-4
  • Test level 1
    15 Hz 150 Hz (Test Level 4)
  • Test level 2
    150 Hz 1.5 kHz (Test Level 4)
  • Test level 6
    150 Hz 180 Hz (Test Level 4)
  • REACh SVHC
    Lead 7439-92-1
  • Height with alternative assembly
    130 mm
  • Installation distance top/bottom
    50 mm / 50 mm
  • Protective circuit/component
    Varistor, gas-filled surge arrester
  • EMC requirements, power plant
    IEC 61850-3
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Test field strength
    110 A/m
  • Attenuated sinusoidal oscillations (ring wave)
    EN 61000-4-12
  • Test level 4
    15 kHz 150 kHz (Test Level 4)
  • Asymmetrical conducted disturbance variables
    EN 61000-4-16
  • Input, output (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • Signals (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • Criterion C
    Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
  • ECLASS 10.0.1
    27040701
  • ECLASS 9.0
    27040701
  • Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
  • Inrush current
    typ. 10 A (at 25 °C)
  • Nominal output voltage
    24 V DC
  • Setting range of the output voltage (USet)
    24 V DC ... 28 V DC (constant capacity)
  • HART FSK Physical Layer Test Specification Compliance
    Output voltage UOut compliant
  • Degree of protection
    IP20
  • Width
    70 mm
  • Depth with alternative assembly
    73 mm
  • Standard – Limitation of mains harmonic currents
    EN 61000-3-2
  • Rail applications
    EN 50121-3-2
  • DNV GL conducted interference
    Class A
  • Frequency range
    50 Hz ... 60 Hz
  • Surge voltage load (surge)
    EN 61000-4-5
  • I/O/S
    asymmetrical
  • Frequency
    50 Hz
  • Voltage dip
    0 %
  • Signals (test level 2)
    100 kHz 1 MHz (Test Level 3 - asymmetrical)
  • ECLASS 11.0
    27040701
  • ETIM 7.0
    EC002540

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

This item can ship within 5 days!

1-year warranty

$606.14

2904617

Stock:

1

Select Qty:

$606.14

$606.14 each

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo