KFU8-UFC-EX1.D Pepperl + Fuchs Electronic Components
Part#:KFU8-UFC-EX1.D
Manufacturer:Pepperl + Fuchs
Product Lifecycle:Active
Get a quick Quote!
Frequency Converter with Trip Values, 1-channel isolated barrier, Universal usage at different power supplies, Input for NAMUR sensors or dry contacts, Input frequency 1 mHz ... 5 kHz, Current output 0/4 mA ... 20 mA, Relay contact and transistor output,
Check out the KFU8-UFC-EX1.D Pepperl + Fuchs price in the box on the right side or send a quick quote.
Product Details
- Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
- IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
- IECEx certificate IECEx TUN 04.0007
- Control drawing 16-538FM-12
- Power Po 34 mW (linear characteristic)
- Directive 2014/34/EU EN IEC 60079-0:2018 , EN 60079-11:2012
- Interface RS 232
- Current Io 13.5 mA
- Maximum safe voltage Um 40 V (Attention! The rated voltage can be lower.)
- Maximum safe voltage 253 V AC / 125 V DC (Attention! Umis no rated voltage.)
- Marking II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
- Voltage Uo 10.1 V
- Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
- Input EN 60947-5-6:2000
- EU-type examination certificate TÜV 99 ATEX 1471
- Degree of protection IEC 60529:2001
- Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
- Mass 300 g
- Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
- Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
- Electromagnetic compatibility NE 21:2006
- Directive 2014/35/EU EN 61010-1:2010
- Labeling space for labeling at the front
- Display elements LEDs , display
- Start-up override/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
- Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
- Configuration via operating buttons, via PACTware
- Control elements Control panel
- Interface/output III basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
- Output IV/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
- Output III/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
- Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
- Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
- Output III/IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
- Output III/start-up override basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
- Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
- Response delay ≤ 200 ms
- Influence of ambient temperature 0.003 %/K (30 ppm)
- Accuracy 0.1 % of the measurement value , > 0.001 Hz
- Measuring time < 100 ms
- Measurement range 0.001 ... 5000 Hz
- Resolution 0.1 % of the measurement value , ≥ 0.001 Hz
- Load max. 650 Ω
- Signal level 1-signal: (L+) - 2.5 V (50 mA, short-circuit/overload proof), 0-signal: switched off (off-state current ≤ 10 µA)
- Current range 0 ... 20 mA or 4 ... 20 mA
- Fault signal downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
- Open loop voltage max. 24 V DC
- Output IV analog
- Energized/De-energized delay approx. 20 ms / approx. 20 ms
- Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
- Output I, II signal, relay
- Output III electronic output, passive
- Mechanical life 5 x 107switching cycles
- Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
- Open circuit voltage/short-circuit current 18 V / 5 mA
- Input frequency 0.001 ... 5000 Hz
- Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
- Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
- Power dissipation/power consumption ≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA
- Input I sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
- Programming interface programming socket
- Rated voltage 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
- Safety Integrity Level (SIL) SIL 2
- Connection terminals 23, 24
- Signal type Digital Input
- Connection side field side
- Pulse duration > 50 µs
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
Related documents KFU8-UFC-EX1.D Specs
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Pepperl + Fuchs
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Pepperl + Fuchs Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Pepperl + Fuchs Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Pepperl + Fuchs, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.