Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

KFU8-UFC-1.D.FA Pepperl + Fuchs Electronic Components

Pepperl + Fuchs KFU8-UFC-1.D.FA Frequency Converter with Trip Values, 1-channel signal conditioner, Universal usage at different power supplies, Input for 2- or 3-wire sensors, NAMUR sensors or dry contacts, Input frequency 1 mHz ... 10 kHz, Current output 0/4 mA ... 20 mA, Relay contac
Pepperl + Fuchs

Part#:KFU8-UFC-1.D.FA

Manufacturer:Pepperl + Fuchs

Product Lifecycle:Active

Get a quick Quote!

Frequency Converter with Trip Values, 1-channel signal conditioner, Universal usage at different power supplies, Input for 2- or 3-wire sensors, NAMUR sensors or dry contacts, Input frequency 1 mHz ... 10 kHz, Current output 0/4 mA ... 20 mA, Relay contac

Check out the KFU8-UFC-1.D.FA Pepperl + Fuchs price in the box on the right side or send a quick quote.

Product Details

  • Mounting
    on 35 mm DIN mounting rail acc. to EN 60715:2001
  • Dimensions
    40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
  • Supplementary information
    Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
  • Ambient temperature
    -20 ... 60 °C (-4 ... 140 °F)
  • Degree of protection
    IEC 60529:2001
  • Mass
    300 g
  • Electromagnetic compatibility
    NE 21:2006
  • Labeling
    space for labeling at the front
  • Directive 2014/35/EU
    EN 61010-1:2010
  • Configuration
    via operating buttons, via PACTware
  • Directive 2014/30/EU
    EN 61326-1:2006
  • Display elements
    LEDs , display
  • Output III/IV
    basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
  • Control elements
    Control panel
  • Output IV/power supply
    reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
  • Interface/output III
    basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
  • Output III/power supply
    reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
  • Interface/power supply
    reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
  • Start-up override/power supply
    reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
  • Mutual output I, II, III
    reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
  • Output I, II/other circuits
    reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
  • Input I/other circuits
    reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
  • Response delay
    ≤ 200 ms
  • Measuring time
    < 100 ms
  • Influence of ambient temperature
    0.003 %/K (30 ppm)
  • Accuracy
    0.1 % of the measurement value , > 0.001 Hz
  • Resolution
    0.1 % of the measurement value , ≥ 0.001 Hz
  • Measurement range
    0.001 ... 10000 Hz
  • Fault signal
    downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
  • Load
    max. 650 Ω
  • Open loop voltage
    max. 24 V DC
  • Current range
    0 ... 20 mA or 4 ... 20 mA
  • Output IV
    analog
  • Contact loading
    250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
  • Output III
    electronic output, passive
  • Signal level
    1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof), 0-signal: blocked output (off-state current ≤ 10 µA)
  • Output I, II
    signal, relay
  • Mechanical life
    5 x 107switching cycles
  • Energized/De-energized delay
    approx. 20 ms / approx. 20 ms
  • Active/Passive
    I > 4 mA (for min. 100 ms) / I < 1.5 mA
  • Input II
    startup override: 1 ... 1000 s, adjustable in steps of 1 s
  • Pulse duration
    > 50 µs
  • Line fault detection
    breakage I ≤ 0.15 mA; short-circuit I > 4 mA
  • Input frequency
    0.001 ... 10000 Hz
  • Switching point/switching hysteresis
    logic 1: > 2.5 mA ; logic 0: < 1.9 mA
  • Input resistance
    4.7 kΩ
  • Input I
    2- or 3-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
  • Open circuit voltage/short-circuit current
    22 V / 40 mA
  • Power dissipation/power consumption
    ≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA
  • Connection side
    field side
  • Programming interface
    programming socket
  • Rated voltage
    20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
  • Safety Integrity Level (SIL)
    SIL 2
  • Signal type
    Digital Input
  • Connection
    terminals 23, 24

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging



Related documents KFU8-UFC-1.D.FA Specs

1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Pepperl + Fuchs

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Pepperl + Fuchs Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Pepperl + Fuchs Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Pepperl + Fuchs, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo