Universal Temperature Converter, 1-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Current output 0/4 mA ... 20 mA, Sink or source mode, Configurable by PACTware, Line ult (LFD) and sensor burnout
Check out the KCD2-UT2-EX1 Pepperl + Fuchs price in the box on the right side or send a quick quote.
Product Details
- Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
- Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
- IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
- IECEx certificate IECEx BAS 13.0057X
- Certificate BASEEFA 13 ATEX 0103 X
- Input/Other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
- Control drawing 116-0379 (cULus)
- Power Po 30 mW
- Maximum safe voltage 250 V (Attention! This is not the rated voltage.)
- Current Io 13.1 mA
- Voltage Uo 9 V
- Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
- Inputs terminals 1, 2, 3, 4
- EU-type examination certificate BASEEFA 13 ATEX 0102 X
- Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
- Ambient temperature -20 ... 70 °C (-4 ... 158 °F)
- Degree of protection IEC 60529:2001
- Marking II (1)G [Ex ia Ga] IIC ,II (1)D [Ex ia Da] IIIC ,I (M1) [Ex ia Ma] I
- Mass approx. 100 g
- Protection against electrical shock UL 61010-1:2004
- Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
- Electromagnetic compatibility NE 21:2012, EN 61326-3-2:2008
- Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
- Labeling space for labeling at the front
- Display elements LEDs
- Influence of supply voltage < 0.01 % of span
- Configuration via PACTware
- Influence of load ≤ 0.001 % of output value per 100 Ω
- Output/supply, programming input functional insulation, rated insulation voltage 50 V AC, There is no electrical isolation between the programming input and the supply., The programming cable provides galvanic isolation so that ground loops are avoided.
- Reaction time worst case value (sensor breakage and/or sensor short circuit detection enabled), mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s
- Sink Voltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V,, series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V is the source voltage., The maximum value of the resistance is (V - 5)/0.0215 Ω.
- After calibration Pt100:± (0.06 % of measurement value in K + 0.1 % of span + 0.1 K (4-wire connection)), thermocouple:± (0.05 % of measurement value in °C + 0.1 % of span + 1.5 K (1.7 K for types R and S)) , includes ± 1.3 K fault of the cold junction compen
- Source load 0 ... 550 Ω, open-circuit voltage ≤ 18 V
- Influence of ambient temperature Pt100:± (0.0015 % of measurement value in K + 0.006 % of span)/K ΔTamb*), thermocouple:± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K ΔTamb*)), influence of cold junction compe
- Fault signal downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)
- Input resistance ≥ 1 MΩ (-100 ... 100 mV)
- Output Analog current output
- Types of measuring 2-, 3-, 4-wire connection
- Current range 0 ... 20 mA or 4 ... 20 mA
- Potentiometer 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
- Measuring current approx. 200 µA with RTD
- Voltage selectable within the range -100 ... 100 mV
- Measurement loop monitoring sensor breakage, sensor short-circuit
- RTD type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995), type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94), type Cu10, Cu50, Cu100 (P50353-92), type Ni100 (DIN 43760)
- Cold junction compensation external and internal
- Lead resistance max. 50 Ω per line
- Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995), type L (DIN 43710: 1985), type TXK, TXKH, TXA (P8.585-2001)
- Safety Integrity Level (SIL) SIL 2
- Connection terminals 9+, 10- or power feed module/Power Rail
- Rated voltage 19 ... 30 V DC
- Programming interface programming socket
- Ripple within the supply tolerance
- Connection side field side
- Signal type Analog input
- Power dissipation ≤ 0.98 W
- Power consumption max. 0.98 W
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
Related documents KCD2-UT2-EX1 Specs
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price within minutes.
Stock:
2
Select Qty:
Average response time: 11 minutes
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Pepperl + Fuchs
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Pepperl + Fuchs Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Pepperl + Fuchs Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Pepperl + Fuchs, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨