Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

KCD2-STC-EX1.ES Pepperl + Fuchs Electronic Components

Pepperl + Fuchs KCD2-STC-EX1.ES SMART Transmitter Power Supply, 1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Line ult detection (LFD), Housing width 12.5 m
Pepperl + Fuchs

Part#:KCD2-STC-EX1.ES

Manufacturer:Pepperl + Fuchs

Product Lifecycle:Active

Get a quick Quote!

SMART Transmitter Power Supply, 1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Line ult detection (LFD), Housing width 12.5 m

Check out the KCD2-STC-EX1.ES Pepperl + Fuchs price in the box on the right side or send a quick quote.

Product Details

  • Supplementary information
    Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
  • IECEx marking
    [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I, Ex ec IIC T4 Gc
  • IECEx certificate
    IECEx CES 11.0001X
  • Certificate
    CESI 19 ATEX 005 X
  • Directive 2014/34/EU
    EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015
  • Internal inductance
    negligible
  • Control drawing
    116-0378 (cULus)
  • UL approval
    E106378
  • Current
    100 mA
  • Input
    Ex ia
  • Equipment
    terminals 1+, 2-
  • Power
    630 mW
  • Internal capacitance
    5.7 nF
  • Voltage
    25.2 V
  • Maximum safe voltage
    253 V AC (Attention! Umis no rated voltage.)
  • Dimensions
    12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
  • Electromagnetic compatibility
    NE 21:2017, For further information see system description.
  • Marking
    Ex-HexagonII (1)G [Ex ia Ga] IIC, Ex-HexagonII (1)D [Ex ia Da] IIIC, Ex-HexagonI (M1) [Ex ia Ma] I
  • Mounting
    on 35 mm DIN mounting rail acc. to EN 60715:2001
  • Labeling
    space for labeling at the front
  • Ambient temperature
    -20 ... 70 °C (-4 ... 158 °F)
  • EU-type examination certificate
    CESI 10 ATEX 071
  • Mass
    approx. 100 g
  • Input/Output
    safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
  • Directive 2014/30/EU
    EN 61326-1:2013 (industrial locations)
  • Degree of protection
    IEC 60529:2001
  • Configuration
    via DIP switches
  • Control elements
    DIP switch
  • Display elements
    LEDs
  • Input/power supply
    safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
  • Output/power supply
    Basic isolation acc. to EN 61010-1 rated insulation voltage ≤ 50 V
  • Rise time/fall time
    ≤ 20 ms
  • Settling time
    ≤ 200 ms
  • Frequency range
    field side into the control side: bandwidth with 1 mAppsignal 0 ... 3 kHz (-3 dB), control side into the field side: bandwidth with 0.5 Vppsignal 0 ... 3 kHz (-3 dB)
  • Influence of ambient temperature
    < 2 µA/K (0 ... 70 °C (32 ... 158 °F)); < 4 µA/K (-20 ... 0 °C (-4 ... 32 °F)) (source mode and sink mode 4 ... 20 mA), < 0.5 mV/K (0 ... 70 °C (32 ... 158 °F)); < 1 mV/K (-20 ... 0 °C (-4 ... 32 °F)) (source mode 1 ... 5 V)
  • Deviation
    at 20 °C (68 °F), ≤ ± 20 µA incl. calibration, linearity, hysteresis, loads and supply voltage fluctuations (source mode and sink mode 4 ... 20 mA), ≤ 10 mV incl. calibration, linearity, hysteresis and fluctuations of supply voltage (source mode 1 ... 5
  • Output type
    fault bus signal , open collector transistor
  • Output signal
    source mode: 4 ... 20 mA or 1 ... 5 V (internal resistor: 250 Ω, 0.1 %), sink mode: 4 ... 20 mA, operating voltage 16 ... 28 V, For additional internal or external loads the voltage drop has to be considered, e. g. 250 Ω x 20 mA = 5 V.
  • Available voltage
    ≥ 15 V at 20 mA terminals 1+, 2-
  • Load
    0 ... 300 Ω (source mode)
  • Voltage drop
    approx. 5 V on terminals 3+, 4-
  • Line fault detection
    downscaling ≤ 3 mA ; upscaling ≥ 22 mA
  • Input signal
    4 ... 20 mA , limited to approx. 27 mA reverse polarity protected
  • Connection side
    field side
  • Power dissipation
    ≤ 800 mW
  • Safety Integrity Level (SIL)
    SIL 3
  • Rated voltage
    19 ... 30 V DC
  • Ripple
    ≤ 10 %
  • Rated current
    ≤ 50 mA
  • Connection
    Power Rail or terminals 9+, 10-
  • Power consumption
    ≤ 1.2 W
  • Signal type
    Analog input
  • Systematic capability (SC)
    SC 3

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging



Related documents KCD2-STC-EX1.ES Specs

1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Pepperl + Fuchs

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Pepperl + Fuchs Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Pepperl + Fuchs Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Pepperl + Fuchs, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo