LTMR100MBD Schneider Electric Industrial Automation Components

Schneider Electric LTMR100MBD Schneider Electric LTMR100MBD, part of the LTMR (TeSys T) sub-range, is designed for motor management with a variety of control modes including local via terminal block, local via HMI terminal, and remote via network. It supports operating modes such as overload, independent, reverser, 2-step, 2-speed, and custom mode. The part offers comprehensive fault management capabilities with manual, automatic, and remote reset options, alongside protection fault counters, protection alarm counters, diagnostic fault counters, motor control function counters, and fault history. It features fault diagnostics for internal watchdog faults, controller internal temperature, temperature sensor connection, current connection, voltage connection, motor control commands, control configuration checksum, and loss of communication. Motor statistics provided include the number of motor control commands, operating time, number of starts per hour, last start I max, and duration of last start. Thermal overload statistics cover time to trip and time to restart, while system operating statistics include run, on, start, alarm, and fault indicators. The connection type is 3 measurement current transformers with screw-clamp terminals, and it uses the Modbus communication protocol. It is a 3 Pole device with protection functions for thermal overload, motor temperature, phase imbalance, phase failure, phase reversal, long starting time, locked rotor, minimum and maximum current load limit variation, earth fault, and frequent starting. Rated current ranges from 5-100 A with protection settings adjustable for various conditions. The supply voltage is 24 V DC, and the rated voltage for AC phase-to-phase is up to 690 V at 50-60Hz. Measurement functions include current/phase, earth current, average current, current imbalance between phases, thermal capacity level, and motor temperature rise, accommodating a wide range of monitoring and protection needs for motor management.
Schneider Electric

Part#:LTMR100MBD

Manufacturer:Schneider Electric

Product Lifecycle:Active

In-stock parts: 1

Nov 14, 2024

Schneider Electric LTMR100MBD, part of the LTMR (TeSys T) sub-range, is designed for motor management with a variety of control modes including local via terminal block, local via HMI terminal, and remote via network. It supports operating modes such as overload, independent, reverser, 2-step, 2-speed, and custom mode. The part offers comprehensive fault management capabilities with manual, automatic, and remote reset options, alongside protection fault counters, protection alarm counters, diagnostic fault counters, motor control function counters, and fault history. It features fault diagnostics for internal watchdog faults, controller internal temperature, temperature sensor connection, current connection, voltage connection, motor control commands, control configuration checksum, and loss of communication. Motor statistics provided include the number of motor control commands, operating time, number of starts per hour, last start I max, and duration of last start. Thermal overload statistics cover time to trip and time to restart, while system operating statistics include run, on, start, alarm, and fault indicators. The connection type is 3 measurement current transformers with screw-clamp terminals, and it uses the Modbus communication protocol. It is a 3 Pole device with protection functions for thermal overload, motor temperature, phase imbalance, phase failure, phase reversal, long starting time, locked rotor, minimum and maximum current load limit variation, earth fault, and frequent starting. Rated current ranges from 5-100 A with protection settings adjustable for various conditions. The supply voltage is 24 V DC, and the rated voltage for AC phase-to-phase is up to 690 V at 50-60Hz. Measurement functions include current/phase, earth current, average current, current imbalance between phases, thermal capacity level, and motor temperature rise, accommodating a wide range of monitoring and protection needs for motor management.

About the manufacturer: Schneider Electric is one of the manufacturers that offers Industrial Automation Components that you can order at Quotebeam.com. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.

Check out the LTMR100MBD Schneider Electric price in the box on the right side or send a quick quote.

Product Details

  • Measurement Accuracy
    5...15 % earth fault current internal measurement 1 % voltage 100...830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 Temperature 5 % active and reactive power 0,02
  • Network And Machine Diagnosis Type
    Remaining operating time before overload tripping Phase fault and earth fault trip counters Fault recording Waiting time after overload tripping Motor control command recording Event recording Starting current and time T
  • Protection Type
    Thermal overload protection Phase unbalance Overload (long time) Phase failure Thermal protection Power factor variation Reverse polarity protection Overload Locked rotor Load fluctuation Earth-leakage pro
  • Electromagnetic Compatibility
    Electrostatic discharge, 3 8 kV air, 6 kV contact)EN/IEC 61000-4-2) Radiated RF fields, 3 10 V/m)EN/IEC 61000-4-3) Fast transients immunity test, level 3 2 kV)EN/IEC 61000-4-4) Fast transients immunity test, level 4 4 kV)EN/IEC 61000-4-4)
  • Connections - Terminals
    Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible with cable end Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 1 0.00…0.00 in² (0.25…2
  • [Uimp] Rated Impulse Withstand Voltage
    6 kV current or voltage measurement circuit EN/IEC 60947-4-1 0.8 kV communication circuit EN/IEC 60947-4-1 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1
  • [Ui] Rated Insulation Voltage
    690 V EN/IEC 60947-1 690 V CSA C22.2 No 14 690 V UL 508
  • Bus Type
    Modbus 2-wire RS 485 1...247 1.2...19.2 kbit/s, RJ45 2 shielded twisted pairs Modbus 2-wire RS 485 1...247 1.2...19.2 kbit/s, terminal block 2 shielded twisted pairs
  • Permissible Power
    480 VA AC-15), Ie = 2 A, 500000 cycles output) 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
  • Metering Type
    Phase current I1, I2, I3 RMS Temperature Average current Iavg Earth-fault current Imbalance current
  • Load Current
    5 A 250 V AC logic output 5 A 30 V DC logic output
  • Associated Fuse Rating
    4 A gG output 0.5 A gG control circuit
  • Contacts Type And Composition
    1 NO + 1 NC fault signal 3 NO
  • Web Services
    Web server
  • Compatibility Code
    LTMR
  • Height
    2.40 in (61 mm)
  • Width
    3.58 in (91 mm)
  • Depth
    4.82 in (122.5 mm)
  • Net Weight
    1.17 lb(US) (0.53 kg)
  • Pollution Degree
    3
  • Tightening Torque
    Control circuit 4.43…5.31 lbf.in (0.5…0.6 N.m) flat 0.12 in (3 mm)
  • Overvoltage Category
    III
  • Connection Pitch
    0.20 in (5.08 mm)
  • Maximum Output Switching Frequency
    2 Hz
  • Maximum Operating Rate
    1800 cyc/h
  • Current State 1 Guaranteed
    Logic input < 15 V 2...15 mA 15 ms
  • Current State 0 Guaranteed
    Logic input < 5 V <= 15 mA 5 ms
  • Input Current
    7 mA
  • Logic Input Number
    6
  • Short-Circuit Withstand
    100 kA EN/IEC 60947-4-1
  • Communication Port Protocol
    Modbus
  • Supply Voltage Limits
    20.4…26.24 V DC
  • Current Consumption
    56...127 mA
  • Product Or Component Type
    Motor controller
  • Measurement Current
    5…100 A
  • Device Application
    Equipment monitoring and control
  • [Us] Rated Supply Voltage
    24 V DC
  • Device Short Name
    LTMR
  • Product Name
    TeSys T
  • Range
    TeSys

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging



This item can ship within 5 days!

1-year warranty

$588.72

Stock:

1

Select Qty:

$588.72

$588.72 each

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Schneider Electric

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Schneider Electric Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Schneider Electric Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Schneider Electric, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

LTMR08DFM Part Image. Manufactured by Schneider Electric.

LTMR08DFM

Verified stock: 0

Schneider Electric LTMR08DFM, part of the LTMR (TeSys T) sub-range, is designed for comprehensive motor management and protection. It supports various control modes including local operation via terminal block or HMI terminal, and remote operation via network. The operating modes it accommodates are Overload, Independent, Reverser, 2-step, 2-speed, and "Custom" mode. Fault management capabilities include manual, automatic, and remote reset options, alongside extensive fault statistics such as protection fault counters, protection alarm counters, diagnostic fault counters, motor control function counters, fault history, and more. It features fault diagnostics for internal watchdog faults, controller internal temperature, temperature sensor, current, and voltage connections, motor control commands, control configuration checksum, and loss of communication. Motor and thermal overload statistics provide insights into motor control commands, operating time, starts per hour, last start I max, duration of last start, time to trip, and time to restart. System operating statistics cover run, on, start, alarm, and fault statuses. The connection type is through 3 measurement current transformers with a screw-clamp mechanism. It uses the DeviceNet communication protocol and is a 3 Pole device. Protection functions include thermal overload, motor temperature monitoring with up to 3 sensors, phase imbalance, phase failure, phase reversal, long starting time, locked rotor, minimum and maximum current load limit variation, and earth fault detection. It also features protection against frequent starting to prevent motor overheating. The rated current ranges from 0.4-8 A, with a maximum of 800 A using CT. Protection settings are comprehensive, covering thermal overload, motor temperature, phase imbalance, phase failure, phase reversal, long starting time, locked rotor, current load limit variations, and earth fault with specific thresholds and response times. The supply voltage is AC 100-240 V, with a rated voltage for phase-to-phase of 690 V at 50-60Hz. The minimum current is 0.4 A, and the maximum is 8 A. Measurement functions include current/phase, earth current, average current, current imbalance between phases, thermal capacity level, and motor temperature rise.

Schneider Electric

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo