High-current terminal block, nom. voltage: 1500 V, nominal current: 232 A, connection method: Screw connection, number of connections: 2, cross section: 25 mm² - 95 mm², AWG: 4 - 3/0, width: 25 mm, height: 90 mm, color: gray, mounting type: NS 35/15, NS 3

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 3247419 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Number of connections
    2
  • Insulating material
    PA
  • Degree of pollution
    3
  • Insulating material group
    I
  • Power frequency withstand voltage setpoint
    3.82 kV
  • Potentials
    1
  • Maximum load current
    232 A
  • Shock protection test specification
    DIN EN 50274 (VDE 0660-514):2002-11
  • Result of the test for mechanical stability of terminal points (5 x conductor connection)
    Test passed
  • Result of power-frequency withstand voltage test
    Test passed
  • Requirements, voltage drop
    U1 ≤ 3.2 mV; U2 ≤ 1.5 x U1
  • Conductor cross section short circuit testing
    95 mm²
  • Number of levels
    1
  • Flammability rating according to UL 94
    V0
  • Nominal voltage UN
    1500 V
  • Result of surge voltage test
    Test passed
  • Bending test conductor cross section/weight
    25 mm² / 4.5 kg
  • Result of flexion and pull-out test
    Test passed
  • Tight fit on carrier
    NS 32/NS 35
  • Width
    25 mm
  • Connection in acc. with standard
    IEC 60947-7-1
  • Stripping length
    33 mm
  • Conductor cross section AWG max.
    3/0
  • Conductor cross section flexible max.
    95 mm²
  • Conductor cross section flexible, with ferrule with plastic sleeve min.
    35 mm²
  • Operating temperature
    -60 °C ... 105 °C (max. short-term operating temperature 125°C)
  • Permissible humidity (storage/transport)
    30 % ... 70 %
  • ECLASS 5.1
    27141100
  • ETIM 2.0
    EC000897
  • UNSPSC 7.0901
    39121410
  • UNSPSC 6.01
    30211811
  • Color
    gray
  • Overvoltage category
    III
  • Back of the hand protection
    guaranteed
  • Open side panel
    No
  • Tensile test result
    Test passed
  • Result of tight fit on support
    Test passed
  • Cross section with insertion bridge, solid max.
    95 mm²
  • Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
    16 mm²
  • Ambient temperature (actuation)
    -5 °C ... 70 °C
  • ECLASS 4.0
    27141100
  • ECLASS 9.0
    27141120
  • ECLASS 6.0
    27141100
  • UNSPSC 18.0
    39121410
  • Short circuit stability result
    Test passed
  • Surface flammability NFPA 130 (ASTM E 162)
    passed
  • Tightening torque, min
    15 Nm
  • Conductor cross section solid max.
    95 mm²
  • Max. AWG conductor cross section, flexible
    3/0
  • UNSPSC 19.0
    39121410
  • Nominal current IN
    232 A
  • Surge voltage test setpoint
    14.8 kV
  • Tightening torque max
    20 Nm
  • Conductor cross section flexible, with ferrule with plastic sleeve max.
    95 mm²
  • 2 conductors with same cross section, stranded max.
    35 mm²
  • Ambient temperature (storage/transport)
    -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
  • ECLASS 11.0
    27141120
  • ECLASS 4.1
    27141100
  • Nominal cross section
    95 mm²
  • Rated surge voltage
    8 kV
  • Maximum power dissipation for nominal condition
    7.54 W
  • Min. AWG conductor cross section, flexible
    2
  • ETIM 4.0
    EC000897
  • UNSPSC 13.2
    39121410
  • UNSPSC 21.0
    39121410
  • China RoHS
    Environmentally friendly use period: unlimited = EFUP-e
  • ETIM 3.0
    EC000897
  • ETIM 7.0
    EC000897
  • Bending test turns
    135
  • Conductor cross section tensile test
    95 mm²
  • Result of voltage-drop test
    Test passed
  • Screw thread
    M8
  • Conductor cross section solid min.
    25 mm²
  • Conductor cross section flexible min.
    35 mm²
  • Conductor cross section flexible, with ferrule without plastic sleeve max.
    95 mm²
  • 2 conductors with same cross section, solid min.
    25 mm²
  • 2 conductors with same cross section, solid max.
    35 mm²
  • Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
    35 mm²
  • ECLASS 10.0.1
    27141120
  • UNSPSC 20.0
    39121410
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 3
  • Height NS 35/15
    97.5 mm
  • Connection method
    Screw connection
  • Conductor cross section AWG min.
    4
  • Conductor cross section flexible, with ferrule without plastic sleeve min.
    35 mm²
  • Cross section with insertion bridge, stranded max.
    70 mm²
  • 2 conductors with same cross section, stranded min.
    25 mm²
  • Ambient temperature (assembly)
    -5 °C ... 70 °C
  • ECLASS 5.0
    27141100
  • ECLASS 7.0
    27141120
  • ETIM 6.0
    EC000897
  • UNSPSC 12.01
    39121410
  • Bending test rotation speed
    10 rpm
  • Relative insulation material temperature index (Elec., UL 746 B)
    130 °C
  • Static insulating material application in cold
    -60 °C
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 3
  • Result of temperature-rise test
    Test passed
  • Proof of thermal characteristics (needle flame) effective duration
    30 s
  • Smoke gas toxicity NFPA 130 (SMP 800C)
    passed
  • Calorimetric heat release NFPA 130 (ASTM E 1354)
    28 MJ/kg
  • Note
    Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
  • Result of thermal test
    Test passed
  • Specific optical density of smoke NFPA 130 (ASTM E 662)
    passed
  • Length
    85.5 mm
  • Height NS 32
    95 mm
  • Tractive force setpoint
    351 N
  • Short-time current
    11.4 kA
  • Fire protection for rail vehicles (DIN EN 45545-2) R26
    HL 1 - HL 3
  • Height
    90 mm
  • UNSPSC 11
    39121410
  • Requirement temperature-rise test
    Increase in temperature ≤ 45 K
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
    130 °C
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 3

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo