Nikki Gonzales
Nick Goetz
Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

3211896 Phoenix Contact Terminal Blocks

Phoenix Contact 3211896 Feed-through terminal block, nom. voltage: 800 V, nominal current: 24 A, connection method: Push-in connection, number of connections: 3, cross section: 0.14 mm² - 4 mm², AWG: 26 - 12, width: 5.2 mm, color: gray, mounting type: NS 35/7,5, NS 35/15
Phoenix Contact

Part#:3211896

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 46321

Sep 22, 2024

Feed-through terminal block, nom. voltage: 800 V, nominal current: 24 A, connection method: Push-in connection, number of connections: 3, cross section: 0.14 mm² - 4 mm², AWG: 26 - 12, width: 5.2 mm, color: gray, mounting type: NS 35/7,5, NS 35/15

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 3211896 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Potentials
    1
  • Insulating material
    PA
  • Overvoltage category
    III
  • Maximum load current
    28 A (with 4 mm² conductor cross section, rigid)
  • Back of the hand protection
    guaranteed
  • Power frequency withstand voltage setpoint
    2 kV
  • Tensile test result
    Test passed
  • Setpoint
    1 N
  • Short-time current
    0.48 kA
  • Ageing test for screwless modular terminal block temperature cycles
    192
  • Test frequency
    f1 = 5 Hz to f2 = 150 Hz
  • Shock test result
    Test passed
  • Test specification, shock test
    DIN EN 50155 (VDE 0115-200):2008-03
  • Static insulating material application in cold
    -60 °C
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 3
  • Conductor cross section flexible, with ferrule with plastic sleeve min.
    0.34 mm²
  • Operating temperature
    -60 °C ... 105 °C (max. short-term operating temperature 130°C)
  • Ambient temperature (assembly)
    -5 °C ... 70 °C
  • ECLASS 11.0
    27141120
  • ECLASS 5.1
    27141100
  • ETIM 2.0
    EC000897
  • ETIM 7.0
    EC000897
  • UNSPSC 13.2
    39121410
  • UNSPSC 20.0
    39121410
  • Number of connections
    3
  • Nominal cross section
    2.5 mm²
  • Insulating material group
    I
  • Open side panel
    Yes
  • Finger protection
    guaranteed
  • Bending test rotation speed
    10 rpm
  • Bending test conductor cross section/weight
    0.14 mm² / 0.2 kg
  • Requirement temperature-rise test
    Increase in temperature ≤ 45 K
  • Result of thermal test
    Test passed
  • Oscillation, broadband noise test result
    Test passed
  • Acceleration
    5g
  • Shock form
    Half-sine
  • Shock duration
    30 ms
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
    125 °C
  • Number of levels
    1
  • Rated surge voltage
    8 kV
  • Maximum power dissipation for nominal condition
    0.77 W
  • Nominal voltage UN
    800 V
  • Result of surge voltage test
    Test passed
  • Result of the test for mechanical stability of terminal points (5 x conductor connection)
    Test passed
  • Bending test turns
    135
  • Result of tight fit on support
    Test passed
  • Result of voltage-drop test
    Test passed
  • Short circuit stability result
    Test passed
  • Result of aging test
    Test passed
  • Test specification, oscillation, broadband noise
    DIN EN 50155 (VDE 0115-200):2008-03
  • ASD level
    0.02 g²/Hz
  • Test directions
    X-, Y- and Z-axis (pos. and neg.)
  • Number of shocks per direction
    3
  • Surface flammability NFPA 130 (ASTM E 162)
    passed
  • Calorimetric heat release NFPA 130 (ASTM E 1354)
    27,5 MJ/kg
  • End cover width
    2.2 mm
  • Connection
    1 level
  • Stripping length
    8 mm ... 10 mm
  • Conductor cross section AWG min.
    26
  • Color
    gray
  • Flammability rating according to UL 94
    V0
  • Nominal current IN
    24 A
  • Shock protection test specification
    DIN EN 50274 (VDE 0660-514):2002-11
  • Result of power-frequency withstand voltage test
    Test passed
  • Result of flexion and pull-out test
    Test passed
  • Tight fit on carrier
    NS 35
  • Result of temperature-rise test
    Test passed
  • Conductor cross section short circuit testing
    4 mm²
  • Proof of thermal characteristics (needle flame) effective duration
    30 s
  • Test spectrum
    Service life test category 1, class B, body mounted
  • Test duration per axis
    5 h
  • Relative insulation material temperature index (Elec., UL 746 B)
    130 °C
  • Specific optical density of smoke NFPA 130 (ASTM E 662)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 3
  • Width
    5.2 mm
  • Height NS 35/7,5
    43 mm
  • Connection in acc. with standard
    CSA
  • Conductor cross section solid min.
    0.34 mm²
  • Min. AWG conductor cross section, flexible
    26
  • Conductor cross section flexible max.
    4 mm²
  • Conductor cross section flexible, with ferrule without plastic sleeve max.
    2.5 mm²
  • Connection cross sections directly pluggable
    0.34 mm² 4 mm²
  • Permissible humidity (storage/transport)
    30 % ... 70 %
  • ECLASS 5.0
    27141100
  • ECLASS 7.0
    27141120
  • ETIM 3.0
    EC000897
  • ETIM 6.0
    EC000897
  • UNSPSC 18.0
    39121410
  • Smoke gas toxicity NFPA 130 (SMP 800C)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 3
  • Fire protection for rail vehicles (DIN EN 45545-2) R26
    HL 1 - HL 3
  • Length
    49 mm
  • Height NS 35/15
    50.5 mm
  • Connection method
    Push-in connection
  • Conductor cross section AWG max.
    12
  • Conductor cross section flexible min.
    0.14 mm²
  • Max. AWG conductor cross section, flexible
    14
  • Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
    0.5 mm²
  • Ambient temperature (storage/transport)
    -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
  • China RoHS
    Environmentally friendly use period: unlimited = EFUP-e
  • ECLASS 4.0
    27141100
  • ECLASS 4.1
    27141100
  • ETIM 4.0
    EC000897
  • UNSPSC 6.01
    30211811
  • UNSPSC 12.01
    39121410
  • UNSPSC 19.0
    39121410
  • Conductor cross section solid max.
    4 mm²
  • Conductor cross section flexible, with ferrule without plastic sleeve min.
    0.34 mm²
  • Conductor cross section flexible, with ferrule with plastic sleeve max.
    2.5 mm²
  • Internal cylindrical gage
    A3
  • Ambient temperature (actuation)
    -5 °C ... 70 °C
  • ECLASS 10.0.1
    27141120
  • ECLASS 6.0
    27141100
  • ECLASS 9.0
    27141120
  • UNSPSC 7.0901
    39121410
  • UNSPSC 11
    39121410
  • UNSPSC 21.0
    39121410

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


This item can ship within 24h!

1-year warranty

$2.52

Stock:

46321

Select Qty:

$2.52

$2.52 each

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo