Nikki Gonzales
Nick Goetz
Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

2902019 Phoenix Contact Electrical Measuring & Monitoring Instruments

Phoenix Contact 2902019 3-way signal conditioner, with configurable input/output, for electrical isolation and conversion of analog signals in the mV and V range, unipolar as well as bipolar. Screw connection technology, standard configuration.
Phoenix Contact

Part#:2902019

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

About the product: 3-way signal conditioner, with configurable input/output, for electrical isolation and conversion of analog signals in the mV and V range, unipolar as well as bipolar. Screw connection technology, standard configuration.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2902019 Phoenix Contact price in the box on the right side or send a quick quote.

2902019 Product Details

  • UNSPSC 21.0
    39121008
  • UNSPSC 6.01
    30211502
  • Depth
    119.2 mm
  • Maximum altitude
    ≤ 2000 m
  • max. input voltage
    33 V
  • Voltage input signal
    -50 mV ... 50 mV (via DIP switch)
  • Voltage output signal
    0 V ... 5 V (via DIP switch)
  • Ripple
    < 20 mVPP (at 600 Ω)
  • Conductor cross section flexible
    0.14 mm² ... 2.5 mm²
  • Maximum transmission error
    ≤ 0.1 % (of final value)
  • Vibration
    A
  • ECLASS 11.0
    27210120
  • ECLASS 4.0
    27210100
  • ECLASS 10.0.1
    27210120
  • Ambient temperature (operation)
    -40 °C ... 70 °C
  • Configurable/programmable
    Yes
  • Input resistance of voltage input
    > 10 kΩ
  • Nominal supply voltage
    24 V DC
  • Stripping length
    10 mm
  • Conductor cross section AWG
    24 ... 12 (flexible)
  • Electromagnetic compatibility
    Conformance with EMC directive
  • Rated insulation voltage
    300 V
  • Standards/regulations
    EN 61000-4-6
  • ECLASS 6.0
    27210100
  • ECLASS 9.0
    27210120
  • UNSPSC 11
    39121004
  • UNSPSC 19.0
    39121008
  • Width
    6.2 mm
  • Degree of protection
    IP20 (not assessed by UL)
  • Max. output current
    22 mA
  • Load/output load current output
    ≤ 600 Ω (at 20 mA)
  • Power consumption
    ≤ 800 mW (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
  • Screw thread
    M3
  • Torque
    0.5 Nm ... 0.6 Nm
  • Step response (10-90%)
    < 8.5 ms (with 30 Hz filter)
  • EMC
    A
  • ECLASS 4.1
    27210100
  • ETIM 7.0
    EC002653
  • ETIM 4.0
    EC002653
  • UNSPSC 18.0
    39121008
  • Height
    109.81 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Number of inputs
    1
  • Number of outputs
    1
  • Load/output load voltage output
    ≥ 10 kΩ
  • Supply voltage range
    9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
  • Conductor cross section solid
    0.2 mm² ... 1.5 mm² (with ferrule)
  • Limit frequency (3 dB)
    30 Hz (via DIP switch)
  • Electrical isolation
    Reinforced insulation in accordance with IEC 61010-1
  • Humidity
    B
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 5.0
    27210100
  • ECLASS 7.0
    27210120
  • UNSPSC 13.2
    39121008
  • UNSPSC 7.0901
    39121004
  • ECLASS 5.1
    27210100
  • Permissible humidity (operation)
    5 % ... 95 % (non-condensing)
  • ETIM 6.0
    EC002653
  • Noise immunity
    EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
  • Short-circuit current
    < 32 mA
  • Current output signal
    0 mA ... 20 mA (via DIP switch)
  • UNSPSC 12.01
    39121004
  • UNSPSC 20.0
    39121008
  • Typical current consumption
    25 mA (Current output, at 24 V DC incl. load)
  • Connection method
    Screw connection
  • No. of channels
    1
  • Maximum temperature coefficient
    0.01 %/K
  • Housing material
    PBT
  • Noise emission
    EN 61000-6-4
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 2
  • REACh SVHC
    Lead 7439-92-1
  • Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • Color
    gray
  • Overvoltage category
    II
  • Test voltage, input/output/supply
    3 kV (50 Hz, 1 min.)
  • Temperature
    B
  • Designation
    Shipbuilding approval
  • Certificate
    DNV GL TAA00002UA
  • Protective circuit
    Transient protection
  • Mounting position
    any
  • Assembly instructions
    The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
  • Degree of pollution
    2
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 2
  • Identification
    UL 508 Listed
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 2

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

2902019

Select Qty:

Average response time: 11 minutes

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo