Nikki Gonzales
Nick Goetz
Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

LC1D09BD Schneider Electric Automation components

Schneider Electric LC1D09BD Schneider Electric - LC1D09BD
Schneider Electric

Part#:LC1D09BD

Manufacturer:Schneider Electric

Product Lifecycle:Active

In-stock parts: 17

May 18, 2024

About the product: Schneider Electric - LC1D09BD

About the manufacturer: Schneider Electric is one of the manufacturers that offers Automation components that you can order at Quotebeam.com. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.

Check out the LC1D09BD Schneider Electric price in the box on the right side or send a quick quote.

LC1D09BD Product Details

  • Product Certifications
    LROS (Lloyds register of shipping) CSA UL GOST DNV CCC GL BV RINA
  • Standards
    CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
  • Motor Power HP (UL / CSA)
    1 hp 230/240 V at AC 50/60 Hz for 1 phase 2 hp 200/208 V at AC 50/60 Hz for 3 phase 2 hp 230/240 V at AC 50/60 Hz for 3 phase 5 hp 460/480 V at AC 50/60 Hz for 3 phase 7.5 hp 575/600 V at AC 50/60 Hz for 3 phase 0.33 hp 115 V at A
  • Motor Power Kw
    2.2 kW 220...230 V AC 50/60 Hz AC-3) 4 kW 380...400 V AC 50/60 Hz AC-3) 4 kW 415...440 V AC 50/60 Hz AC-3) 5.5 kW 500 V AC 50/60 Hz AC-3) 5.5 kW 660...690 V AC 50/60 Hz AC-3) 2.2 kW 400 V AC 50/60 Hz AC-4)
  • [Ui] Rated Insulation Voltage
    Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL
  • [Icw] Rated Short-Time Withstand Current
    105 A 104 °F (40 °C) - 10 s power circuit 210 A 104 °F (40 °C) - 1 s power circuit 30 A 104 °F (40 °C) - 10 min power circuit 61 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circu
  • Tightening Torque
    Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lb
  • Control Circuit Voltage Limits
    0.1...0.25 Uc -40…158 °F (-40…70 °C) drop-out DC 0.7...1.25 Uc -40…140 °F (-40…60 °C) operational DC 1...1.25 Uc 140…158 °F (60…70 °C) operational DC
  • Utilisation Category
    AC-4 AC-1 AC-3
  • Associated Fuse Rating
    10 A gG signalling circuit IEC 60947-5-1 25 A gG <= 690 V type 1 power circuit 20 A gG <= 690 V type 2 power circuit
  • Connections - Terminals
    Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible
  • Irms Rated Making Capacity
    250 A 440 V power circuit IEC 60947 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1
  • Electrical Durability
    0.6 Mcycles 25 A AC-1 <= 440 V 2 Mcycles 9 A AC-3 <= 440 V
  • Operating Time
    53.55...72.45 ms closing 16...24 ms opening
  • Auxiliary Contacts Type
    Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
  • Safety Reliability Level
    B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Power Dissipation Per Pole
    1.56 W AC-1 0.2 W AC-3
  • Non-Overlap Time
    1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
  • Contactor Application
    Motor control Resistive load
  • [Ue] Rated Operational Voltage
    Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
  • [Ie] Rated Operational Current
    9 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit 25 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
  • Mounting Support
    Plate Rail
  • [Ith] Conventional Free Air Thermal Current
    25 A 140 °F (60 °C) power circuit 10 A 140 °F (60 °C) signalling circuit
  • Insulation Resistance
    > 10 MOhm signalling circuit
  • Minimum Switching Current
    5 mA signalling circuit
  • Signalling Circuit Frequency
    25...400 Hz
  • Minimum Switching Voltage
    17 V signalling circuit
  • Hold-In Power Consumption In W
    5.4 W 68 °F (20 °C)
  • Inrush Power In W
    5.4 W 68 °F (20 °C))
  • Time Constant
    28 ms
  • Coil Technology
    Built-in bidirectional peak limiting diode suppressor
  • Mechanical Durability
    30 Mcycles
  • Maximum Operating Rate
    3600 cyc/h 140 °F (60 °C)
  • Front Cover
    With
  • Average Impedance
    2.5 mOhm - Ith 25 A 50 Hz power circuit
  • Rated Breaking Capacity
    250 A 440 V power circuit IEC 60947
  • Auxiliary Contact Composition
    1 NO + 1 NC
  • Overvoltage Category
    III
  • [Uimp] Rated Impulse Withstand Voltage
    6 kV IEC 60947
  • [Uc] Control Circuit Voltage
    24 V DC
  • Power Pole Contact Composition
    3 NO
  • Device Short Name
    LC1D
  • Product Name
    TeSys D
  • Control Circuit Type
    DC standard
  • Product Or Component Type
    Contactor
  • Poles Description
    3P
  • Range
    TeSys

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.


This item can ship within 5 days!

1-year warranty

$66.13

LC1D09BD

Stock:

17

Select Qty:

$66.13

$66.13 each

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo