3210185 Phoenix Contact Terminal Blocks
Part#:3210185
Manufacturer:Phoenix Contact
Product Lifecycle:Active
In-stock parts: 45
Nov 27, 2024
Disconnect terminal block, nom. voltage: 400 V, nominal current: 20 A, connection method: Push-in connection, cross section: 0.14 mm² - 4 mm², AWG: 26 - 12, length: 62 mm, width: 5.2 mm, color: gray, mounting: NS 35/7,5, NS 35/15
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 3210185 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Potentials 1
- Degree of pollution 3
- Maximum power dissipation for nominal condition 0.77 W
- Back of the hand protection guaranteed
- Finger protection guaranteed
- Power frequency withstand voltage setpoint 1.89 kV
- Bending test conductor cross section/weight 0.14 mm² / 0.2 kg
- Requirement temperature-rise test Increase in temperature ≤ 45 K
- Result of thermal test Test passed
- Oscillation, broadband noise test result Test passed
- Acceleration 30g
- Test specification, shock test DIN EN 50155 (VDE 0115-200):2018-05
- Shock duration 18 ms
- Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
- Width 5.2 mm
- Height NS 35/7,5 36.5 mm
- Connection 1 level
- Min. AWG conductor cross section, flexible 26
- Conductor cross section flexible, with ferrule without plastic sleeve min. 0.34 mm²
- Permissible humidity (storage/transport) 30 % ... 70 %
- ECLASS 11.0 27141126
- ECLASS 6.0 27141100
- ECLASS 5.1 27141100
- ETIM 4.0 EC000902
- UNSPSC 12.01 39121410
- UNSPSC 20.0 39121410
- Number of levels 1
- Rated surge voltage 6 kV
- Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
- Result of flexion and pull-out test Test passed
- Tight fit on carrier NS 35
- Setpoint 1 N
- Ageing test for screwless modular terminal block temperature cycles 192
- Test frequency f1 = 5 Hz to f2 = 250 Hz
- Test duration per axis 5 h
- Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 125 °C
- Static insulating material application in cold -60 °C
- Calorimetric heat release NFPA 130 (ASTM E 1354) 27,5 MJ/kg
- Height 35.3 mm
- Connection in acc. with standard CSA
- Conductor cross section AWG max. 12
- Internal cylindrical gage A3
- Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
- Ambient temperature (actuation) -5 °C ... 70 °C
- China RoHS Environmentally friendly use period: unlimited = EFUP-e
- ETIM 2.0 EC000897
- ETIM 6.0 EC000902
- UNSPSC 6.01 30211811
- UNSPSC 21.0 39121410
- Note Current and voltage are determined by the plug used.
- Number of connections 2
- Insulating material PA
- Insulating material group I
- Nominal current IN 20 A
- Result of surge voltage test Test passed
- Bending test turns 135
- Result of tight fit on support Test passed
- Short-time current 0.3 kA
- Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2018-05
- ASD level 6.12 (m/s2)2/Hz
- Shock form Half-sine
- Relative insulation material temperature index (Elec., UL 746 B) 130 °C
- Specific optical density of smoke NFPA 130 (ASTM E 662) passed
- Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
- Stripping length 8 mm ... 10 mm
- Connection method Push-in connection
- Conductor cross section flexible min. 0.14 mm²
- Conductor cross section flexible, with ferrule without plastic sleeve max. 2.5 mm²
- Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum 0.5 mm²
- Operating temperature -60 °C ... 105 °C (max. short-term operating temperature 130°C)
- ECLASS 4.0 27141100
- ECLASS 5.0 27141100
- ECLASS 9.0 27141126
- UNSPSC 7.0901 39121410
- UNSPSC 18.0 39121410
- UNSPSC 19.0 39121410
- Color gray
- Overvoltage category III
- Nominal voltage UN 400 V
- Open side panel Yes
- Result of the test for mechanical stability of terminal points (5 x conductor connection) Test passed
- Tensile test result Test passed
- Result of voltage-drop test Test passed
- Conductor cross section short circuit testing 2.5 mm²
- Proof of thermal characteristics (needle flame) effective duration 30 s
- Result of aging test Test passed
- Test directions X-, Y- and Z-axis (pos. and neg.)
- Surface flammability NFPA 130 (ASTM E 162) passed
- Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
- Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
- Length 62 mm
- Conductor cross section solid max. 4 mm²
- Conductor cross section flexible max. 4 mm²
- Conductor cross section flexible, with ferrule with plastic sleeve min. 0.34 mm²
- Connection cross sections directly pluggable 0.34 mm² 4 mm²
- Ambient temperature (assembly) -5 °C ... 70 °C
- ECLASS 4.1 27141100
- ETIM 3.0 EC000897
- UNSPSC 11 39121410
- Nominal cross section 2.5 mm²
- Flammability rating according to UL 94 V0
- Maximum load current 20 A (with 4 mm² conductor cross section, rigid)
- Result of power-frequency withstand voltage test Test passed
- Bending test rotation speed 10 rpm
- Result of temperature-rise test Test passed
- Short circuit stability result Test passed
- Test spectrum Service life test category 2, bogie-mounted
- Shock test result Test passed
- Number of shocks per direction 3
- Smoke gas toxicity NFPA 130 (SMP 800C) passed
- End cover width 2.2 mm
- Height NS 35/15 44 mm
- Conductor cross section solid min. 0.34 mm²
- Conductor cross section AWG min. 26
- Max. AWG conductor cross section, flexible 14
- Conductor cross section flexible, with ferrule with plastic sleeve max. 2.5 mm²
- ECLASS 10.0.1 27141126
- ECLASS 7.0 27141126
- ETIM 7.0 EC000902
- UNSPSC 13.2 39121410
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 24h!
1-year warranty
$3.97
Stock:
45
Select Qty:
$3.97
$3.97 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨