3044160 Phoenix Contact Terminal Blocks
Part#:3044160
Manufacturer:Phoenix Contact
Product Lifecycle:Active
In-stock parts: 1932
Nov 14, 2024
Feed-through terminal block, nom. voltage: 1000 V, nominal current: 57 A, connection method: Screw connection, number of connections: 2, cross section: 0.5 mm² - 16 mm², AWG: 20 - 6, width: 10.2 mm, height: 46.9 mm, color: gray, mounting type: NS 35/7,5,
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 3044160 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Result of temperature-rise test Test passed
- Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 125 °C
- Length 47.7 mm
- ECLASS 10.0.1 27141120
- Note Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
- Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum 0.5 mm²
- Operating temperature -60 °C ... 105 °C (max. short-term operating temperature 130°C)
- ETIM 2.0 EC000897
- Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
- Conductor cross section flexible max. 16 mm²
- Conductor cross section flexible, with ferrule with plastic sleeve min. 0.5 mm²
- UNSPSC 21.0 39121410
- UNSPSC 11 39121410
- ETIM 3.0 EC000897
- UNSPSC 6.01 30211811
- UNSPSC 7.0901 39121410
- UNSPSC 20.0 39121410
- 2 conductors with same cross section, stranded max. 4 mm²
- China RoHS Environmentally Friendly Use Period = 50 years
- UNSPSC 19.0 39121410
- UNSPSC 13.2 39121410
- Rated surge voltage 8 kV
- Nominal voltage UN 1000 V
- Bending test conductor cross section/weight 0.5 mm² / 0.3 kg
- Maximum load current 76 A (with 16 mm² conductor cross section)
- Open side panel Yes
- Surge voltage test setpoint 9.6 kV
- Tensile test result Test passed
- Short circuit stability result Test passed
- Result of thermal test Test passed
- Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2018-05
- Test duration per axis 5 h
- Shock duration 18 ms
- Static insulating material application in cold -60 °C
- Smoke gas toxicity NFPA 130 (SMP 800C) passed
- Screw thread M4
- Tightening torque, min 1.5 Nm
- Shock test result Test passed
- Relative insulation material temperature index (Elec., UL 746 B) 130 °C
- Result of surge voltage test Test passed
- Bending test rotation speed 10 rpm
- Conductor cross section short circuit testing 10 mm²
- Ageing test for screwless modular terminal block temperature cycles 192
- Test directions X-, Y- and Z-axis (pos. and neg.)
- Degree of pollution 3
- Nominal current IN 57 A
- Back of the hand protection guaranteed
- Result of the test for mechanical stability of terminal points (5 x conductor connection) Test passed
- Proof of thermal characteristics (needle flame) effective duration 30 s
- Test frequency f1 = 5 Hz to f2 = 250 Hz
- ASD level 6.12 (m/s2)2/Hz
- Number of shocks per direction 3
- Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
- Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
- Height NS 35/15 55 mm
- Connection method Screw connection
- Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
- Result of power-frequency withstand voltage test Test passed
- Calorimetric heat release NFPA 130 (ASTM E 1354) 27,5 MJ/kg
- Width 10.2 mm
- Height 46.9 mm
- Stripping length 10 mm
- Conductor cross section flexible min. 0.5 mm²
- Short-time current 1.2 kA
- Acceleration 30g
- Shock form Half-sine
- Surface flammability NFPA 130 (ASTM E 162) passed
- Test specification, shock test DIN EN 50155 (VDE 0115-200):2008-03
- Specific optical density of smoke NFPA 130 (ASTM E 662) passed
- Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
- Connection in acc. with standard CSA
- Conductor cross section solid min. 0.5 mm²
- ECLASS 11.0 27141120
- Conductor cross section AWG max. 6
- Conductor cross section flexible, with ferrule with plastic sleeve max. 10 mm²
- Internal cylindrical gage A6
- Tightening torque max 1.8 Nm
- Conductor cross section flexible, with ferrule without plastic sleeve min. 0.5 mm²
- 2 conductors with same cross section, stranded min. 0.5 mm²
- Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum 0.5 mm²
- ECLASS 5.1 27141100
- Max. AWG conductor cross section, flexible 6
- Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
- ECLASS 4.1 27141100
- ECLASS 9.0 27141120
- Potentials 1
- Area of application Railway industry
- Bending test turns 135
- Test spectrum Service life test category 2, bogie-mounted
- End cover width 2.2 mm
- Flammability rating according to UL 94 V0
- Result of tight fit on support Test passed
- Requirement temperature-rise test Increase in temperature ≤ 45 K
- Maximum power dissipation for nominal condition 1.82 W
- Tractive force setpoint 100 N
- Setpoint 5 N
- Number of levels 1
- Color gray
- Finger protection guaranteed
- Result of flexion and pull-out test Test passed
- Result of voltage-drop test Test passed
- Tight fit on carrier NS 35
- Conductor cross section tensile test 16 mm²
- Requirements, voltage drop U1 ≤ 3.2 mV; U2 ≤ 1.5 x U1
- Height NS 35/7,5 47.5 mm
- Conductor cross section AWG min. 20
- Ambient temperature (actuation) -5 °C ... 70 °C
- ECLASS 5.0 27141100
- Insulating material group I
- Conductor cross section solid max. 16 mm²
- Permissible humidity (storage/transport) 30 % ... 70 %
- ECLASS 4.0 27141100
- ECLASS 7.0 27141120
- ETIM 7.0 EC000897
- UNSPSC 18.0 39121410
- Nominal cross section 10 mm²
- Conductor cross section flexible, with ferrule without plastic sleeve max. 10 mm²
- Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum 6 mm²
- Insulating material PA
- 2 conductors with same cross section, solid max. 4 mm²
- Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum 2.5 mm²
- Ambient temperature (assembly) -5 °C ... 70 °C
- ECLASS 6.0 27141100
- ETIM 6.0 EC000897
- UNSPSC 12.01 39121410
- Number of connections 2
- Min. AWG conductor cross section, flexible 20
- 2 conductors with same cross section, solid min. 0.5 mm²
- Overvoltage category III
- ETIM 4.0 EC000897
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 24h!
1-year warranty
$2.81
Stock:
1932
Select Qty:
$2.81
$2.81 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨