Nov 21, 2024
Feed-through terminal block, nom. voltage: 1000 V, nominal current: 24 A, connection method: Screw connection, number of connections: 2, cross section: 0.14 mm² - 4 mm², AWG: 26 - 12, width: 5.2 mm, height: 46.9 mm, color: gray, mounting type: NS 35/7,5,
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 3044076 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Surge voltage test setpoint 9.8 kV
- Result of flexion and pull-out test Test passed
- Insulating material group I
- Power frequency withstand voltage setpoint 2.2 kV
- Shock form Half-sine
- Conductor cross section flexible, with ferrule with plastic sleeve min. 0.14 mm²
- 2 conductors with same cross section, stranded max. 1.5 mm²
- Ambient temperature (actuation) -5 °C ... 70 °C
- Operating temperature -60 °C ... 105 °C (max. short-term operating temperature 130°C)
- ECLASS 4.0 27141100
- ECLASS 5.1 27141100
- ETIM 2.0 EC000897
- ETIM 7.0 EC000897
- UNSPSC 12.01 39121410
- Maximum power dissipation for nominal condition 0.77 W
- Finger protection guaranteed
- Back of the hand protection guaranteed
- Result of the test for mechanical stability of terminal points (5 x conductor connection) Test passed
- Open side panel Yes
- Nominal current IN 24 A
- Result of surge voltage test Test passed
- Bending test rotation speed 10 rpm
- Setpoint 1 N
- Result of temperature-rise test Test passed
- Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum 0.5 mm²
- Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum 1.5 mm²
- Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum 0.14 mm²
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 4.1 27141100
- ECLASS 7.0 27141120
- ETIM 4.0 EC000897
- UNSPSC 6.01 30211811
- UNSPSC 11 39121410
- Overvoltage category III
- Nominal voltage UN 1000 V
- Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
- Result of tight fit on support Test passed
- Bending test turns 135
- Oscillation, broadband noise test result Test passed
- 2 conductors with same cross section, solid min. 0.14 mm²
- Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum 1.5 mm²
- Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
- Permissible humidity (storage/transport) 30 % ... 70 %
- Conductor cross section flexible, with ferrule with plastic sleeve max. 2.5 mm²
- 2 conductors with same cross section, solid max. 1.5 mm²
- 2 conductors with same cross section, stranded min. 0.14 mm²
- Internal cylindrical gage A3
- Ambient temperature (assembly) -5 °C ... 70 °C
- ECLASS 10.0.1 27141120
- ECLASS 11.0 27141120
- ECLASS 6.0 27141100
- ETIM 3.0 EC000897
- UNSPSC 18.0 39121410
- UNSPSC 19.0 39121410
- UNSPSC 7.0901 39121410
- Short circuit stability result Test passed
- ASD level 1.857 (m/s2)2/Hz
- Test specification, shock test DIN EN 50155 (VDE 0115-200):2008-03
- Relative insulation material temperature index (Elec., UL 746 B) 130 °C
- Rated surge voltage 8 kV
- Bending test conductor cross section/weight 0.14 mm² / 0.2 kg
- Requirement temperature-rise test Increase in temperature ≤ 45 K
- Conductor cross section short circuit testing 4 mm²
- Number of connections 2
- Area of application Railway industry
- Tensile test result Test passed
- Tight fit on carrier NS 35
- Acceleration 5g
- Test frequency f1 = 5 Hz to f2 = 150 Hz
- Short-time current 0.48 kA
- Potentials 1
- Flammability rating according to UL 94 V0
- Result of power-frequency withstand voltage test Test passed
- Result of voltage-drop test Test passed
- Result of thermal test Test passed
- Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2008-03
- Test spectrum Service life test category 1, class B, body mounted
- Test directions X-, Y- and Z-axis (pos. and neg.)
- Static insulating material application in cold -60 °C
- Number of shocks per direction 3
- Calorimetric heat release NFPA 130 (ASTM E 1354) 27,5 MJ/kg
- Proof of thermal characteristics (needle flame) effective duration 30 s
- Test duration per axis 5 h
- Shock test result Test passed
- Surface flammability NFPA 130 (ASTM E 162) passed
- Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
- Width 5.2 mm
- Height NS 35/7,5 47.5 mm
- Specific optical density of smoke NFPA 130 (ASTM E 662) passed
- Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
- Nominal cross section 2.5 mm²
- Color gray
- Length 47.7 mm
- Height NS 35/15 55 mm
- Conductor cross section flexible min. 0.14 mm²
- Connection in acc. with standard CSA
- Max. AWG conductor cross section, flexible 12
- UNSPSC 20.0 39121410
- Conductor cross section solid min. 0.14 mm²
- Shock duration 30 ms
- Number of levels 1
- Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
- Height 46.9 mm
- Tightening torque, min 0.5 Nm
- ETIM 6.0 EC000897
- Conductor cross section solid max. 4 mm²
- Min. AWG conductor cross section, flexible 26
- Conductor cross section flexible, with ferrule without plastic sleeve max. 2.5 mm²
- Smoke gas toxicity NFPA 130 (SMP 800C) passed
- Stripping length 9 mm
- Conductor cross section AWG min. 26
- ECLASS 5.0 27141100
- ECLASS 9.0 27141120
- UNSPSC 13.2 39121410
- UNSPSC 21.0 39121410
- Maximum load current 32 A (with 4 mm² conductor cross section)
- Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 125 °C
- Degree of pollution 3
- Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
- Connection method Screw connection
- Note Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
- Conductor cross section flexible max. 4 mm²
- End cover width 2.2 mm
- Screw thread M3
- Tightening torque max 0.6 Nm
- Conductor cross section AWG max. 12
- Conductor cross section flexible, with ferrule without plastic sleeve min. 0.14 mm²
- Insulating material PA
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 24h!
1-year warranty
$1.40
Stock:
18,078
Select Qty:
$1.40
$1.40 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨