Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

3004388 Phoenix Contact Terminal Blocks

Phoenix Contact 3004388 Feed-through terminal block, nom. voltage: 800 V, nominal current: 32 A, connection method: Screw connection, number of connections: 2, cross section: 0.2 mm² - 6 mm², AWG: 24 - 10, width: 6.2 mm, color: blue, mounting type: NS 35/7,5, NS 35/15, NS 32
Phoenix Contact

Part#:3004388

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 1476

Nov 7, 2024

Feed-through terminal block, nom. voltage: 800 V, nominal current: 32 A, connection method: Screw connection, number of connections: 2, cross section: 0.2 mm² - 6 mm², AWG: 24 - 10, width: 6.2 mm, color: blue, mounting type: NS 35/7,5, NS 35/15, NS 32

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 3004388 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
    0.25 mm²
  • ETIM 3.0
    EC000897
  • ETIM 4.0
    EC000897
  • ECLASS 7.0
    27141120
  • UNSPSC 11
    39121410
  • UNSPSC 20.0
    39121410
  • Surface flammability NFPA 130 (ASTM E 162)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 3
  • Height NS 35/15
    54.5 mm
  • Stripping length
    8 mm
  • Conductor cross section AWG max.
    10
  • Conductor cross section flexible, with ferrule with plastic sleeve min.
    0.25 mm²
  • 2 conductors with same cross section, solid max.
    1.5 mm²
  • Internal cylindrical gage
    A4
  • Ambient temperature (actuation)
    -5 °C ... 70 °C
  • ECLASS 4.0
    27141100
  • Number of levels
    1
  • Nominal cross section
    4 mm²
  • Insulating material group
    I
  • Degree of pollution
    3
  • Maximum power dissipation for nominal condition
    1.02 W
  • Shock protection test specification
    IEC 60529:2001-02
  • Result of surge voltage test
    Test passed
  • Result of flexion and pull-out test
    Test passed
  • Tensile test result
    Test passed
  • Tight fit on carrier
    NS 32/NS 35
  • Requirement temperature-rise test
    Increase in temperature ≤ 45 K
  • Result of thermal test
    Test passed
  • Static insulating material application in cold
    -60 °C
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 3
  • End cover width
    1.8 mm
  • Length
    42.5 mm
  • Screw thread
    M3
  • Conductor cross section solid min.
    0.2 mm²
  • Conductor cross section flexible min.
    0.2 mm²
  • Conductor cross section flexible, with ferrule without plastic sleeve max.
    4 mm²
  • Cross section with insertion bridge, solid max.
    4 mm²
  • 2 conductors with same cross section, stranded max.
    1.5 mm²
  • ECLASS 6.0
    27141100
  • UNSPSC 12.01
    39121410
  • UNSPSC 19.0
    39121410
  • Number of connections
    2
  • Flammability rating according to UL 94
    V0
  • Color
    blue
  • Overvoltage category
    III
  • Nominal current IN
    32 A
  • Power frequency withstand voltage setpoint
    2 kV
  • Finger protection
    guaranteed
  • Bending test rotation speed
    10 rpm
  • Setpoint
    5 N
  • Short circuit stability result
    Test passed
  • Relative insulation material temperature index (Elec., UL 746 B)
    130 °C
  • Specific optical density of smoke NFPA 130 (ASTM E 662)
    passed
  • Width
    6.2 mm
  • Connection method
    Screw connection
  • Conductor cross section AWG min.
    24
  • Connection in acc. with standard
    CSA
  • Conductor cross section flexible max.
    4 mm²
  • Conductor cross section flexible, with ferrule without plastic sleeve min.
    0.25 mm²
  • 2 conductors with same cross section, stranded min.
    0.2 mm²
  • Ambient temperature (assembly)
    -5 °C ... 70 °C
  • Rated surge voltage
    8 kV
  • Open side panel
    Yes
  • Back of the hand protection
    guaranteed
  • Bending test conductor cross section/weight
    0.2 mm² / 0.2 kg
  • Result of voltage-drop test
    Test passed
  • Short-time current
    0.48 kA
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
    125 °C
  • Smoke gas toxicity NFPA 130 (SMP 800C)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R26
    HL 1 - HL 3
  • Height NS 32
    52 mm
  • Tightening torque, min
    0.6 Nm
  • Conductor cross section solid max.
    6 mm²
  • UNSPSC 21.0
    39121410
  • Nominal voltage UN
    800 V
  • Result of power-frequency withstand voltage test
    Test passed
  • Result of tight fit on support
    Test passed
  • Result of temperature-rise test
    Test passed
  • Conductor cross section short circuit testing
    4 mm²
  • Calorimetric heat release NFPA 130 (ASTM E 1354)
    27,5 MJ/kg
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 3
  • Height NS 35/7,5
    47 mm
  • Potentials
    1
  • Bending test turns
    135
  • Ambient temperature (storage/transport)
    -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
  • Insulating material
    PA
  • Result of the test for mechanical stability of terminal points (5 x conductor connection)
    Test passed
  • Proof of thermal characteristics (needle flame) effective duration
    30 s
  • Maximum load current
    41 A (with 6 mm² conductor cross section)
  • Max. AWG conductor cross section, flexible
    12
  • Cross section with insertion bridge, stranded max.
    4 mm²
  • ECLASS 11.0
    27141120
  • ETIM 7.0
    EC000897
  • UNSPSC 7.0901
    39121410
  • ECLASS 5.1
    27141100
  • ETIM 2.0
    EC000897
  • UNSPSC 13.2
    39121410
  • Tightening torque max
    0.8 Nm
  • Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
    1.5 mm²
  • Operating temperature
    -60 °C ... 105 °C (max. short-term operating temperature 130°C)
  • ECLASS 10.0.1
    27141120
  • ECLASS 5.0
    27141100
  • Conductor cross section flexible, with ferrule with plastic sleeve max.
    2.5 mm²
  • 2 conductors with same cross section, solid min.
    0.2 mm²
  • Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum
    0.5 mm²
  • Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
    2.5 mm²
  • Permissible humidity (storage/transport)
    30 % ... 70 %
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 9.0
    27141120
  • UNSPSC 18.0
    39121410
  • Min. AWG conductor cross section, flexible
    24
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 4.1
    27141100
  • ETIM 6.0
    EC000897
  • UNSPSC 6.01
    30211811

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


This item can ship within 24h!

1-year warranty

$3.72

Stock:

1476

Select Qty:

$3.72

$3.72 each

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo