2903144 Phoenix Contact AC/DC Power Supplies
Part#:2903144
Manufacturer:Phoenix Contact
Product Lifecycle:Active
Get a quick Quote!
Primary-switched TRIO POWER power supply with push-in connection for DIN rail mounting, input: 1-phase, output: 24 V DC/5 A
About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2903144 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- UNSPSC 11 39121004
- Width 35 mm
- Ambient temperature (start-up type tested) -25 °C
- Nominal input voltage range 100 V AC ... 240 V AC
- Current consumption 2.2 A (100 V AC)
- Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
- Power factor (cos phi) 0.5
- Connection in series yes
- Typical response time < 1 s
- Net weight 0.45 kg
- Assembly instructions alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
- Conductor cross section flexible min. 0.2 mm²
- Stripping length 8 mm
- Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
- Standard – Limitation of mains harmonic currents EN 61000-3-2
- Contact discharge 6 kV (Test Level 4)
- Input 2 kV (Test Level 3 - symmetrical)
- Conducted interference EN 61000-4-6
- REACh SVHC Lead 7439-92-1
- ECLASS 5.1 27049000
- ETIM 7.0 EC002540
- UNSPSC 21.0 39121004
- Installation distance top/bottom 50 mm / 50 mm
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- AC frequency range 50 Hz ... 60 Hz ±5 Hz
- Frequency range (fN) 50 Hz ... 60 Hz ±10 %
- Type of protection Transient surge protection
- Setting range of the output voltage (USet) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
- Feedback voltage resistance ≤ 35 V DC
- Output power 120 W
- Protection class II (in closed control cabinet)
- Conductor cross section solid max. 1.5 mm²
- EMC requirements for noise immunity EN 61000-6-1
- Rail applications EN 50121-4
- Discharge in air 8 kV (Test Level 4)
- Comments Criterion A
- Surge voltage load (surge) EN 61000-4-5
- Voltage 10 V (Test Level 3)
- ECLASS 10.0.1 27040701
- ETIM 4.0 EC000599
- UNSPSC 6.01 30211502
- UNSPSC 20.0 39121004
- Installation distance right/left 0 mm / 0 mm
- Degree of protection IP20
- Dielectric strength maximum ≤ 300 V AC 15 s
- Discharge current to PE < 0.25 mA
- Mains buffering time typ. 20 ms (120 V AC)
- Protective circuit/component Varistor
- Dynamic Boost (IDyn.Boost) 7.5 A (5 s)
- Protection against overvoltage at the output (OVP) ≤ 30 V DC
- Efficiency > 89 % (for 230 V AC and nominal values)
- Insulation voltage input/output 3 kV AC (type test)
- Conductor cross section flexible max. 1.5 mm²
- Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- Shipbuilding approval DNV GL (EMC B)
- Electromagnetic HF field EN 61000-4-3
- Output 1 kV (Test Level 2 - symmetrical)
- Criterion A Normal operating behavior within the specified limits.
- ECLASS 5.0 27049000
- ETIM 3.0 EC001039
- UNSPSC 13.2 39121004
- Height 130 mm
- Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
- Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
- Degree of pollution 2
- Nominal power consumption 272 VA
- Input fuse 6.3 A (internal (device protection))
- Nominal output voltage 24 V DC ±1 %
- Derating > 60 °C ... 70 °C (2.5%/K)
- Control deviation < 1 % (change in load, static 10 % ... 90 %)
- Maximum power dissipation in no-load condition < 1 W
- Power loss nominal load max. < 16 W
- Mounting position horizontal DIN rail NS 35, EN 60715
- Connection method Push-in connection
- Conductor cross section AWG max. 16
- EMC requirements for noise emission EN 61000-6-3
- Standard - Safe isolation DIN VDE 0100-410
- UL approvals UL Listed UL 508
- Electrostatic discharge EN 61000-4-2
- Fast transients (burst) EN 61000-4-4
- Signal 1 kV (Test Level 2 - asymmetrical)
- ECLASS 11.0 27040701
- ECLASS 4.0 27040700
- ECLASS 9.0 27040701
- ETIM 6.0 EC002540
- UNSPSC 18.0 39121004
- Depth 115 mm
- Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
- Climatic class 3K3 (in acc. with EN 60721)
- Installation height ≤ 5000 m (> 2000 m, observe derating)
- Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
- Inrush current ≤ 16 A (typical)
- Nominal output current (IN) 5 A
- Connection in parallel Yes, for redundancy and increased capacity
- Residual ripple < 50 mVPP (with nominal values)
- MTBF (IEC 61709, SN 29500) > 3380000 h (25 °C)
- Conductor cross section solid min. 0.2 mm²
- Conductor cross section AWG min. 24
- Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only)
- Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
- Mains variation/undervoltage Semi F47-0706
- Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
- Test field strength 10 V/m (Test Level 3)
- Frequency range 0.15 MHz ... 80 MHz
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- ECLASS 4.1 27040700
- ECLASS 7.0 27049002
- ECLASS 6.0 27049000
- UNSPSC 7.0901 39121004
- UNSPSC 12.01 39121004
- UNSPSC 19.0 39121004
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨