2903153 Phoenix Contact AC/DC Power Supplies

Phoenix Contact 2903153 Primary-switched TRIO POWER power supply with push-in connection for DIN rail mounting, input: 3-phase, output: 24 V DC/5 A
Phoenix Contact

Part#:2903153

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 261

Apr 24, 2024

About the product: Primary-switched TRIO POWER power supply with push-in connection for DIN rail mounting, input: 3-phase, output: 24 V DC/5 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2903153 Phoenix Contact price in the box on the right side or send a quick quote.

2903153 Product Details

  • Depth
    115 mm
  • Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
  • Installation height
    ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
  • Input fuse
    3.15 A (internal (device protection), slow-blow)
  • Protective circuit/component
    Varistor
  • Width
    35 mm
  • Installation distance right/left
    0 mm / 0 mm
  • Height
    130 mm
  • Max. permissible relative humidity (operation)
    ≤ 95 % (at 25 °C, non-condensing)
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Input voltage range
    3x 400 V AC ... 500 V AC -20 % ....+15 %
  • AC frequency range
    50 Hz ... 60 Hz
  • Inrush current
    ≤ 22 A (typical)
  • Nominal output voltage
    24 V DC ±1 %
  • Nominal output current (IN)
    5 A
  • Control deviation
    < 1 % (change in load, static 10 % ... 90 %)
  • Maximum power dissipation in no-load condition
    < 1 W (400 V AC)
  • Insulation voltage input/output
    3 kV AC (type test)
  • Conductor cross section flexible min.
    0.2 mm²
  • EMC requirements for noise emission
    EN 61000-6-3
  • Standard - Electrical safety
    IEC 60950-1/VDE 0805 (SELV)
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • Contact discharge
    6 kV (Test Level 4)
  • Frequency range
    0.15 MHz ... 80 MHz
  • Input
    3 kV (Test Level 3 - symmetrical)
  • China RoHS
    Environmentally Friendly Use Period = 25;
  • ECLASS 4.0
    27040700
  • ETIM 4.0
    EC002540
  • UNSPSC 13.2
    39121004
  • Installation distance top/bottom
    50 mm / 50 mm
  • Climatic class
    3K3 (in acc. with EN 60721)
  • Nominal input voltage range
    3x 400 V AC ... 500 V AC
  • Nominal power consumption
    243.6 VA
  • Power factor (cos phi)
    0.55
  • Setting range of the output voltage (USet)
    24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
  • Derating
    > 60 °C ... 70 °C (2.5%/K)
  • Protection against overvoltage at the output (OVP)
    ≤ 30 V DC
  • Typical response time
    < 1 s
  • Efficiency
    > 91 % (at 400 V AC and nominal values)
  • Conductor cross section solid max.
    1.5 mm²
  • Stripping length
    8 mm
  • EMC requirements for noise immunity
    EN 61000-6-1
  • UL approvals
    UL Listed UL 508
  • Electrostatic discharge
    EN 61000-4-2
  • Comments
    Criterion A
  • Output
    1 kV (Test Level 2 - symmetrical)
  • ECLASS 11.0
    27040701
  • ECLASS 7.0
    27049002
  • ETIM 6.0
    EC002540
  • UNSPSC 18.0
    39121004
  • UNSPSC 21.0
    39121004
  • Degree of protection
    IP20
  • Ambient temperature (start-up type tested)
    -25 °C
  • Degree of pollution
    2
  • Current consumption
    3x 0.4 A (400 V AC)
  • Recommended breaker for input protection
    6 A ... 16 A (Characteristics B, C, D, K)
  • Dynamic Boost (IDyn.Boost)
    7.5 A (5 s)
  • Output power
    120 W
  • Power loss nominal load max.
    < 12 W (480 V AC)
  • Connection method
    Push-in connection
  • Conductor cross section solid min.
    0.2 mm²
  • Standard - Safety of transformers
    EN 61558-2-16 (air clearances and creepage distances only)
  • Rail applications
    EN 50121-4
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Electromagnetic HF field
    EN 61000-4-3
  • Surge voltage load (surge)
    EN 61000-4-5
  • Criterion A
    Normal operating behavior within the specified limits.
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 4.1
    27040700
  • ECLASS 6.0
    27049000
  • UNSPSC 20.0
    39121004
  • Ambient temperature (operation)
    -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Discharge current to PE
    < 0.25 mA
  • Mains buffering time
    typ. 20 ms (400 V AC)
  • Type of protection
    Transient surge protection
  • Connection in series
    yes
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • MTBF (IEC 61709, SN 29500)
    > 2300000 h (25 °C)
  • Mounting position
    horizontal DIN rail NS 35, EN 60715
  • Conductor cross section AWG min.
    24
  • Conductor cross section AWG max.
    16
  • Standard - Safe isolation
    DIN VDE 0100-410
  • Standard – Limitation of mains harmonic currents
    EN 61000-3-2
  • Discharge in air
    8 kV (Test Level 4)
  • Test field strength
    10 V/m (Test Level 3)
  • Signal
    1 kV (Test Level 1 - symmetrical)
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • ECLASS 5.1
    27049000
  • ETIM 7.0
    EC002540
  • UNSPSC 19.0
    39121004
  • Residual ripple
    ≤ 20 mVPP
  • Net weight
    0.4 kg
  • Protection class
    II (in closed control cabinet)
  • Assembly instructions
    alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
  • Conductor cross section flexible max.
    1.5 mm²
  • Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
    EN 50178/VDE 0160 (PELV)
  • Standard – Safety extra-low voltage
    IEC 60950-1 (SELV) and EN 60204-1 (PELV)
  • Conducted noise emission
    EN 55016
  • Fast transients (burst)
    EN 61000-4-4
  • Voltage
    10 V (Test Level 3)
  • Conducted interference
    EN 61000-4-6
  • ECLASS 10.0.1
    27040701
  • ECLASS 5.0
    27049000
  • ECLASS 9.0
    27040701

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

This item can ship within 5 days!

1-year warranty

$193.44

2903153

Stock:

261

Select Qty:

$193.44

$193.44 each

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo