About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2902027 Phoenix Contact price in the box on the right side or send a quick quote.
2902027 Product Details
- Width 6.2 mm
- Degree of protection IP20 (not assessed by UL)
- max. input voltage 12 V
- Number of outputs 1
- Max. output voltage approx. 12.3 V
- Load/output load current output ≤ 600 Ω (at 20 mA)
- Connection method Push-in connection
- Conductor cross section AWG 24 ... 12 (flexible)
- Depth 119.2 mm
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Number of inputs 1
- Input resistance current input approx. 50 Ω (+0.7 V for test diode)
- Current output signal 0 mA ... 20 mA (via DIP switch)
- Min. switching current 100 µA
- Power consumption ≤ 1 W (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
- No. of channels 1
- Mounting position any
- Standards/regulations EN 61000-4-6
- Height 109.81 mm
- Maximum altitude ≤ 2000 m
- Voltage input signal 0 V ... 10 V (via DIP switch)
- Max. input current 24 mA
- Voltage output signal 0 V ... 10 V (via DIP switch)
- Max. output current 24.6 mA
- Contact type 1 N/O contact
- Max. switching current 100 mA (at 30 V)
- Typical current consumption 32 mA (24 V DC)
- Conductor cross section flexible 0.14 mm² ... 2.5 mm²
- Housing material PBT
- Load/output load voltage output ≥ 10 kΩ
- Ripple < 20 mVPP (at 600 Ω)
- Minimum switching voltage 1 V
- Nominal supply voltage 24 V DC
- Maximum transmission error 0.1 % (of final value)
- ATEX II 3 G Ex nA IIC T4 Gc X
- Ambient temperature (operation) -40 °C ... 70 °C
- Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
- Identification UL 508 Listed
- Certificate DNV GL TAA000021E
- EMC A
- ECLASS 7.0 27210120
- UNSPSC 18.0 39121008
- Humidity B
- REACh SVHC Lead 7439-92-1
- ECLASS 4.1 27210100
- ECLASS 9.0 27210120
- UNSPSC 20.0 39121008
- Conductor cross section solid 0.2 mm² ... 2.5 mm² (with ferrule)
- Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
- Designation Shipbuilding approval
- DNV GL-Humidity B
- Configurable/programmable Yes
- Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
- Typical deviation from the measuring range final value 2.8 %
- UL, USA/Canada UL 508 Listed
- Conformance CE-compliant
- Test voltage, input/output/supply 3 kV (50 Hz, 1 min.)
- Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
- Assembly instructions The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
- Degree of pollution 2
- Noise emission EN 61000-6-4
- Temperature coefficient, typical 0.01 %/K
- Electromagnetic compatibility Conformance with EMC directive
- Overvoltage category II
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 4.0 27210100
- Current input signal 0 mA ... 20 mA (via DIP switch)
- Output name Switching output
- Supply voltage range 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
- Stripping length 10 mm
- Status display Yellow LED (switching output)
- DNV GL-Temperature B
- DNV GL-EMC A
- Vibration A
- ECLASS 6.0 27210100
- ETIM 4.0 EC002653
- Maximum switching voltage 30 V DC
- Electrical isolation Reinforced insulation in accordance with IEC 61010-1
- ECLASS 11.0 27210120
- ECLASS 5.1 27210100
- ETIM 7.0 EC002653
- Permissible humidity (operation) 5 % ... 95 % (non-condensing)
- Maximum temperature coefficient 0.01 %/K
- Rated insulation voltage 300 V (effective)
- DNV GL-Vibration A
- Temperature B
- ECLASS 5.0 27210100
- ETIM 6.0 EC002653
- UNSPSC 21.0 39121008
- Input resistance of voltage input > 120 kΩ
- Color gray
- DNV GL-Enclosure Required protection according to the Rules shall be provided upon installation on board
- Enclosure Required protection according to the Rules shall be provided upon installation on board
- ECLASS 10.0.1 27210120
- UNSPSC 13.2 39121008
- UNSPSC 19.0 39121008
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
2902027
Select Qty:
Average response time: 11 minutes
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Relevant products
Do you have questions?
We’re here for you ✨