2811572 Phoenix Contact Electrical Measuring & Monitoring Instruments

Phoenix Contact 2811572 Configurable 3-way isolating amplifier with safe electrical isolation, 24 V, power bridging. DIP switches on the front, over 1600 signal conversions can be set. Order configuration, spring-cage connection, SIL.
Phoenix Contact

Part#:2811572

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

About the product: Configurable 3-way isolating amplifier with safe electrical isolation, 24 V, power bridging. DIP switches on the front, over 1600 signal conversions can be set. Order configuration, spring-cage connection, SIL.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2811572 Phoenix Contact price in the box on the right side or send a quick quote.

2811572 Product Details

  • Depth
    114.5 mm
  • Number of inputs
    1
  • Height
    116 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • max. input voltage
    ± 100 V
  • Load/output load voltage output
    ≥ 1 kΩ (10 V)
  • Current output signal
    0 mA ... 5 mA
  • Vibration
    A
  • ECLASS 10.0.1
    27210120
  • ECLASS 5.1
    27210100
  • Conductor cross section solid
    0.2 mm² ... 1.5 mm²
  • Alignment zero
    ± 4 %
  • Overvoltage category
    II
  • Electromagnetic compatibility
    Conformance with EMC directive
  • Mounting position
    any
  • DNV GL-Vibration
    A
  • DNV GL-Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • ETIM 6.0
    EC002653
  • UNSPSC 19.0
    39121008
  • Width
    12.5 mm
  • Maximum altitude
    ≤ 2000 m
  • Number of outputs
    1
  • Max. input current
    ± 100 mA
  • ECLASS 9.0
    27210120
  • Load/output load current output
    ≤ 600 Ω (20 mA; active)
  • Connection method
    Push-in connection
  • Conductor cross section flexible
    0.2 mm² ... 1.5 mm²
  • Maximum transmission error
    ≤ 0.1 % (Compared to the final value)
  • Step response (10-90%)
    35 µs (at 10 kHz)
  • Rated insulation voltage
    300 V AC
  • Housing material
    PA 6.6-FR
  • ATEX
     II 3 G Ex nA IIC T4 Gc
  • UL, USA/Canada
    UL 61010 Listed
  • DNV GL-EMC
    A
  • Humidity
    B
  • ECLASS 4.0
    27210100
  • ETIM 4.0
    EC002653
  • UNSPSC 12.01
    39121008
  • UNSPSC 20.0
    39121008
  • Ambient temperature (operation)
    -20 °C ... 70 °C
  • Voltage input signal
    0 mV ... 50 mV
  • Input resistance current input
    approx. 10 Ω (± 10 mA DC ... ± 100 mA DC)
  • Ripple
    < 10 mVrms
  • Stripping length
    8 mm
  • No. of channels
    1
  • Alignment span
    ± 4 %
  • Protective circuit
    Transient protection
  • Test voltage, input/output/supply
    2.5 kV (50 Hz, 1 min.)
  • IECEx
    Ex nA IIC T4 Gc
  • Identification
    2
  • EMC
    A
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 6.0
    27210100
  • UNSPSC 6.01
    30211506
  • UNSPSC 13.2
    39121008
  • Utilization restriction
    EMC: class A product, see manufacturer's declaration in the download area
  • Degree of protection
    IP20 (not assessed by UL)
  • Current input signal
    0 mA ... 1 mA (Configurable via DIP switches)
  • Input resistance of voltage input
    approx. 1 MΩ (±1 V DC ...  ±100 V DC)
  • Supply voltage range
    12 V DC ... 24 V DC (-20 % / +25 %)
  • Color
    gray
  • DNV GL-Humidity
    B
  • Temperature
    B
  • Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • ECLASS 11.0
    27210120
  • ECLASS 7.0
    27210120
  • ETIM 7.0
    EC002653
  • UNSPSC 21.0
    39121008
  • UNSPSC 18.0
    39121008
  • Min. input voltage
    ± 50 mV
  • Voltage output signal
    0 V ... 10 V (Configurable via DIP switches)
  • Configurable/programmable
    Yes, can be switched
  • Power consumption
    ≤ 700 mW
  • Conductor cross section AWG
    24 ... 16
  • Limit frequency (3 dB)
    10 kHz (Can be switched to 30 Hz)
  • Maximum temperature coefficient
    0.0075 %/K
  • Degree of pollution
    2
  • Designation
    Safety Integrity Level (SIL, IEC 61508)
  • Conformance
    CE-compliant
  • Standards/regulations
    GB 3836.1
  • DNV GL-Temperature
    B
  • Certificate
    DNV GL TAA000020C
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 4.1
    27210100
  • ECLASS 5.0
    27210100
  • UNSPSC 11
    39121008
  • UNSPSC 7.0901
    39121008

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

2811572

Select Qty:

Average response time: 11 minutes

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo