1046800 Phoenix Contact DC/DC Converters
Part#:1046800
Manufacturer:Phoenix Contact
Product Lifecycle:Active
In-stock parts: 7
Nov 5, 2024
Primary-switched DC/DC converter, QUINT POWER, DIN rail mounting, SFB Technology (Selective Fuse Breaking), Screw connection, input: 24 V DC , output: 24 V DC / 5 A
About the manufacturer: Phoenix Contact is one of the manufacturers that offers DC/DC Converters that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 1046800 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Weight0.6 kg
- Typical current consumption 6.9 A (24 V DC)
- Inrush current integral (I2t) < 0.05 A2s
- Production test B 2 kV DC
- Connection method Screw connection
- Conductor cross section flexible 0.2 mm² ... 1.5 mm²
- Dynamic Boost (IDyn.Boost) 10 A (5 s)
- Selective Fuse Breaking (ISFB) 30 A (15 ms)
- Feedback voltage resistance ≤ 35 V DC
- UIn > 0.8 x UInNom (LED off)
- Default Output power ON (>40 kΩ/24 V DC/open bridge between REM and SGnd)
- Output current 5 A
- Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
- Height 130 mm
- Electric strength, max. 35 V DC (60 s)
- Typical response time 300 ms (from SLEEP MODE)
- Input fuse 15 A (slow-blow, internal)
- Production test D 0.5 kV DC
- Input voltage range 18 V DC ... 32 V DC
- Switch-on time < 1 s
- Type test (IEC/EN 60950-1) A 2 kV DC
- Type test (IEC/EN 60950-1) D 0.5 kV DC
- Production test C 0.5 kV DC
- Nominal output voltage (UN) 24 V DC
- Magnetic circuit breaker tripping A1 ... A4 / B2 / C1 ... C2 / Z1 ... Z4
- System deviation, dynamic < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
- System deviation, input voltage change < 0.1 % (change in input voltage ±10 %)
- Rise time < 1 s (UOUT (10 % ... 90 %))
- POut > 100 % (LED lights up yellow, output power > 120 W)
- Signal option Output current
- Reference potential to OUT1, OUT2, REM
- Voltage 1 kV
- Main converter stage 50 kHz ... 420 kHz (Main converter stage)
- Depth 125 mm
- Depth with alternative assembly 39 mm
- Efficiency typ. 92.2 % (24 V DC)
- Maximum altitude ≤ 5000 m (> 2000 m, observe derating)
- Overvoltage category EN 62477-1 III
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- DNV GL noise radiation Class B
- Electromagnetic HF field EN 61000-4-3
- Frequency range 50 Hz ... 60 Hz
- Signal 2 kV (Test Level 3 - asymmetrical)
- Frequency 0 Hz
- Test level 2 150 Hz 1.5 kHz (Test Level 3)
- Test level 6 0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 3)
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- REACh SVHC Lead 7439-92-1
- ETIM 6.0 EC002046
- Mains buffering typ. 14 ms (24 V DC)
- Insulation voltage input/output 4 kV DC (type test)
- Type test (IEC/EN 60950-1) C 0.5 kV DC
- Stripping length 8 mm
- Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) 0.2 mm² ... 1.5 mm²
- Setting range of the output voltage (USet) 24 V DC ... 29.5 V DC (> 24 V DC, constant capacity)
- Short-circuit-proof yes
- Connection in parallel Yes, for redundancy and increased capacity
- Types of signaling LED
- Connection labeling 3.4 +
- Maximum contact load 24 V DC
- MTBF (IEC 61709, SN 29500) > 1600000 h (25 °C)
- Time 520000 h
- Protection class Special with SELV input and output
- Side element version Aluminum
- Height with alternative assembly 130 mm
- Digital 0 V DC
- Inrush current limitation typical 1 A
- Type test (IEC/EN 60950-1) B 4 kV DC
- Production test A 2 kV DC
- Conductor cross section solid 0.2 mm² ... 1 mm²
- Conductor cross section AWG 24 ... 16
- Static Boost (IStat.Boost) 6.25 A
- No-load proof yes
- Connection in series yes
- UOut > 0.9 x USet (LED lights up green)
- Switch contact floating
- Temperature 30 °C
- Hood version Stainless steel X6Cr17
- Width with alternative assembly 122 mm
- Power loss nominal load max. < 10 W
- Climatic class 3K3 (EN 60721)
- EMC requirements for noise immunity EN 61000-6-1
- Standards/regulations EN 61000-4-29
- Additional text Test Level 2
- Electrostatic discharge EN 61000-4-2
- Output 1 kV (Test Level 3 - symmetrical)
- I/O/S asymmetrical
- Voltage dip 0 %
- Damped oscillating magnetic field EN 61000-4-10
- Input, output (test level 1) 100 kHz 1 MHz (Test Level 2 - symmetrical)
- Attenuated oscillating wave EN 61000-4-18
- ECLASS 11.0 27210901
- Flexible conductor cross section (ferrule with plastic sleeve) 0.2 mm² ... 0.75 mm²
- Nominal output current (IN) 5 A
- System deviation, static < 1 % (change in load, static 10 % ... 90 %)
- Residual ripple < 10 mVPP
- Protection against overvoltage at the output (OVP) ≤ 32 V DC
- Analog 4 mA ... 20 mA ±5 % (Load ≤400 Ω)
- Function Signal ground
- Auxiliary converter stage 190 kHz ... 220 kHz (Auxiliary converter stage)
- Degree of protection IP20
- Width 36 mm
- Power dissipation SLEEP MODE < 1 W
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Vibration (operation) 5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)
- Overvoltage category EN 61010-1 II
- Designation Shipbuilding
- Identification ABS
- Contact discharge 8 kV (Test Level 4)
- Comments Criterion A
- Surge voltage load (surge) EN 61000-4-5
- Asymmetrical conducted disturbance variables EN 61000-4-16
- Test level 4 15 kHz 150 kHz (Test Level 3)
- Test level 3 1.5 kHz 15 kHz (Test Level 3)
- Input, output (test level 3) 10 MHz (Test Level 2 - asymmetrical)
- ECLASS 10.0.1 27210901
- Maximum power dissipation in no-load condition < 2 W
- Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
- Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
- Degree of pollution 2
- Standard designation Mains variation/undervoltage
- Conducted noise emission EN 55016
- Noise emission EN 55016
- Discharge in air 15 kV (Test Level 4)
- Input 1 kV (Test Level 3 - symmetrical)
- Conducted interference EN 61000-4-6
- Voltage dips EN 61000-4-29
- Test level 1 15 Hz 150 Hz (Test Level 3)
- Alternating component of DC voltage EN 61000-4-17
- Signals (test level 2) 100 kHz 1 MHz (Test Level 2 - asymmetrical)
- Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
- ECLASS 9.0 27210901
- Ambient temperature (start-up type tested) -40 °C
- Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
- EMC requirements for noise emission EN 61000-6-3
- EMC requirements, power plant IEC 61850-3
- Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
- DNV GL conducted interference Class B
- Test field strength 100 A/m
- Fast transients (burst) EN 61000-4-4
- Power frequency magnetic field EN 61000-4-8
- Pulse-shape magnetic field EN 61000-4-9
- Test level 5 16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
- Input, output (test level 2) 100 kHz 1 MHz (Test Level 2 - asymmetrical)
- Criterion A Normal operating behavior within the specified limits.
- Signals (test level 1) 100 kHz 1 MHz (Test Level 2 - symmetrical)
- ETIM 7.0 EC002046
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 24h!
1-year warranty
$249.10
Stock:
7
Select Qty:
$249.10
$249.10 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨