KFD2-UT2-EX1-1 Pepperl + Fuchs Electronic Components
Part#:KFD2-UT2-EX1-1
Manufacturer:Pepperl + Fuchs
Product Lifecycle:Active
Get a quick Quote!
Universal Temperature Converter, 1-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Voltage output 0/1 V ... 5 V, Configurable by PACTware, Line ult (LFD) and sensor burnout detection, Up to SIL 2 a
Check out the KFD2-UT2-EX1-1 Pepperl + Fuchs price in the box on the right side or send a quick quote.
Product Details
- IECEx certificate IECEx TUN 07.0003, IECEx CML 16.0126X
- Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
- Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000
- Power Po 50 mW
- Certificate TÜV 02 ATEX 1797 X
- Input/Other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
- IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I, Ex nA IIC T4 Gc
- Control drawing 116-0410
- Maximum safe voltage 250 V (Attention! This is not the rated voltage.)
- Current Io 22 mA
- Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
- EU-type examination certificate CESI 04 ATEX 143
- Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
- Marking II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
- Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
- Input Ex ia
- Protection against electrical shock UL 61010-1:2004
- Inputs terminals 1, 2, 3, 4
- Voltage Uo 9 V
- Mass approx. 130 g
- Electromagnetic compatibility NE 21:2006
- Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
- Degree of protection IEC 60529:2001
- Configuration via PACTware
- Influence of supply voltage < 0.01 % of span
- Output/supply, programming input functional insulation, rated insulation voltage 50 V AC, There is no electrical isolation between the programming input and the supply., The programming cable provides galvanic isolation so that ground loops are avoided.
- Fault signal downscale 0 V or 0.5 V, upscale 5.375 V
- Display elements LEDs
- Reaction time worst case value (sensor breakage and/or sensor short circuit detection enabled), mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s
- Influence of ambient temperature Pt100:± (0.0015 % of measurement value in K + 0.0075 % of span)/K ΔTamb*), thermocouple:± (0.02 K + 0.005 % of measurement value in °C + 0.0075 % of span)/K ΔTamb*), influence of cold junction comp
- Labeling space for labeling at the front
- Voltage selectable within the range -100 ... 100 mV
- After calibration Pt100:± (0.06 % of measurement value in K + 0.1 K (4-wire connection)), thermocouple:± (0.05 % of measurement value in °C + 1 K (1.2 K for types R and S)) , includes ± 0.8 K fault of the cold junction compensation (CJC), mV:± 50 µV,
- Voltage output 0 ... 5 V or 1 ... 5 V ; output resistance: ≤ 5 Ω ; load: ≥ 10 kΩ
- Input resistance ≥ 1 MΩ (-100 ... 100 mV)
- Potentiometer 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
- Cold junction compensation external and internal
- Measurement loop monitoring sensor breakage, sensor short-circuit
- Signal type Analog input
- Lead resistance max. 50 Ω per line
- RTD type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995), type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94), type Cu10, Cu50, Cu100 (P50353-92), type Ni100 (DIN 43760)
- Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995), type L (DIN 43710: 1985), type TXK, TXKH, TXA (P8.585-2001)
- Measuring current approx. 200 µA with RTD
- Types of measuring 2-, 3-, 4-wire connection
- Connection terminals 14+, 15- or power feed module/Power Rail
- Programming interface programming socket
- Connection side field side
- Power consumption max. 0.64 W
- Ripple within the supply tolerance
- Rated voltage 20 ... 30 V DC
- Power dissipation ≤ 0.64 W
- Safety Integrity Level (SIL) SIL 2
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
Related documents KFD2-UT2-EX1-1 Specs
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Pepperl + Fuchs
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Pepperl + Fuchs Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Pepperl + Fuchs Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Pepperl + Fuchs, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨