X20 power supply module, with integrated safe cutoff function, for internal I/O power supply, 24 VDC, 10 A, 1 safe type B1 digital output, 24 VDC, 10 A, without OSSD, note the list of permitted modules in the potential group
Check out the X20SP1130 B&R price in the box on the right side or send a quick quote.
Product Details
- Temperature Operation Vertical mounting orientation 0 to 35°C
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd openSAFETY wireless <1*10-14 * Number of openSAFETY packets per hour
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd openSAFETY wired Negligible
- Temperature Operation Horizontal mounting orientation 0 to 60°C
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd Per channel <1*10-10
- Relative humidity Transport 5 to 95%, non-condensing
- Relative humidity Storage 5 to 95%, non-condensing
- Relative humidity Operation 5 to 95%, non-condensing
- Temperature Transport -40 to 85°C
- Temperature Storage -40 to 85°C
- Mounting orientation Horizontal Yes
- Temperature Derating See section "Derating".
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFD <2*10-5
- Mounting orientation Vertical Yes
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 Proof test interval (PT) 20 years
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 SIL CL SIL 3
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 SFF >90%
- EN ISO 13849-1:2015 MTTFD 2500 years
- EN ISO 13849-1:2015 Mission time Max. 20 years
- EN ISO 13849-1:2015 DC >94%
- Certifications DNV In preparation
- Certifications KC Yes
- EN ISO 13849-1:2015 Category Cat. 4
- EN ISO 13849-1:2015 PL PL e
- Certifications EAC Yes
- Certifications UL cULus E115267; Industrial control equipment
- Certifications HazLoc cCSAus 244665; Process control equipment; for hazardous locations; Class I, Division 2, Groups ABCD, T5
- Certifications ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X
- Certifications UKCA Yes
- Certifications Functional safety cULus FSPC E361559; Energy and industrial systems; Certified for functional safety; ANSI UL 1998:2013
- Blackout mode Standalone mode No
- Electrical isolation Channel - Bus Yes
- Certifications CE Yes
- Power consumption Internal I/O 1.5 W
- Quantity 1
- Blackout mode Function Module functionality
- Fuse Required line fuse: Max. 10 A, slow-blow
- Power consumption Bus 0.2 W
- Blackout mode Scope Module
- System requirements SafeDESIGNER 2.70 or later
- Diagnostics Outputs Yes, using LED status indicator and software
- Diagnostics Module run/error Yes, using LED status indicator and software
- System requirements mapp Technology Package mapp Safety 5.7.0 or later
- Reverse polarity protection No
- System requirements Safety Release 1.2 or later
- Input voltage 24 VDC -15% / +20%
- Max. I/O cycle time 800 µs
- System requirements Automation Runtime 3.00 or later
- System requirements Automation Studio 3.0.81.15 or later
- Pitch 25+0.2 mm
- Note Order 1x safety-keyed terminal block separately.; Order 1x safety-keyed bus module separately.
- Degree of protection per EN 60529 IP20
- Additional power dissipation caused by actuators (resistive) [W] 3
- Installation elevation above sea level 0 to 2000 m, no limitation
- IOUT <1 mA
- IGND <50 mA
- Max. capacitive load 1 mF
- Minimum load 15 mA
- Test pulse length Without test pulse
- I/O module 1 safe type B1 digital output, 24 VDC, 10 A, without OSSD, note list of permitted modules in the potential group
- Status indicators I/O function per channel, operating state, module status
- B&R ID code 0x1DBF
- Leakage current when the output is switched off 1 mA
- Switching voltage I/O power supply minus voltage drop due to RDS(on)
- Max. switching frequency 5 times per minute with max. 2 Hz; Hardware upgrade 2.2.0.0 and later: 120 times per minute with max. 2 Hz; See section "Inrush current behavior for output channels" and table "Switching inductive loads".
- RDS(on) 30 mΩ
- Peak short-circuit current See section "Inrush current behavior for output channels".
- Insulation voltage between channel and bus 500 Veff
- Diagnostic status Output monitoring, current measurement (shutdown in the event of overcurrent)
- Error detection time 2 s
- Nominal output current 10 A
- Braking voltage when switching off inductive loads 1 VDC
- Output protection See section "Inrush current behavior for output channels".
- Nominal voltage 24 VDC
- Variant FET, 2x positive switching, type B1, output level readable
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of B&R
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
B&R Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many B&R Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from B&R, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨