B&R X20CSO6300 X20 safe digital output module, coated, 6 safe type B1 digital outputs, 24 VDC, 0.2 A, OSSD <10 µs
B&R

Part#:X20CSO6300

Manufacturer:B&R

Product Lifecycle:Active

Get a quick Quote!

X20 safe digital output module, coated, 6 safe type B1 digital outputs, 24 VDC, 0.2 A, OSSD <10 µs

Check out the X20CSO6300 B&R price in the box on the right side or send a quick quote.

Product Details

  • Temperature Operation Horizontal mounting orientation
    -25 to 60°C
  • Relative humidity Storage
    5 to 95%, non-condensing
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd openSAFETY wired
    Negligible
  • Temperature Operation Vertical mounting orientation
    -25 to 50°C
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd Per channel
    <1*10-10
  • Relative humidity Transport
    5 to 95%, non-condensing
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd openSAFETY wireless
    <1*10-14 * Number of openSAFETY packets per hour
  • Relative humidity Operation
    Up to 100%, condensing
  • Temperature Derating
    See section "Derating".
  • Temperature Storage
    -40 to 85°C
  • Temperature Transport
    -40 to 85°C
  • Mounting orientation Vertical
    Yes
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 SFF
    >60% if parameter "Disable OSSD = Yes - Warning", ; >90% if parameter "Disable OSSD = No"
  • Mounting orientation Horizontal
    Yes
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 Proof test interval (PT)
    20 years
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFD
    <2*10-5
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 SIL CL
    SIL 2 if parameter "Disable OSSD = Yes - Warning", ; SIL 3 if parameter "Disable OSSD = No"
  • EN ISO 13849-1:2015 DC
    >60% if parameter "Disable OSSD = Yes - Warning", ; >94% if parameter "Disable OSSD = No"
  • EN ISO 13849-1:2015 PL
    PL d if parameter "Disable OSSD = Yes - Warning", ; PL e if parameter "Disable OSSD = No"
  • EN ISO 13849-1:2015 MTTFD
    2500 years
  • EN ISO 13849-1:2015 Mission time
    Max. 20 years
  • Certifications HazLoc
    cCSAus 244665; Process control equipment; for hazardous locations; Class I, Division 2, Groups ABCD, T5
  • Certifications Functional safety
    cULus FSPC E361559; Energy and industrial systems; Certified for functional safety; ANSI UL 1998:2013
  • Certifications DNV
    In preparation
  • Certifications UL
    cULus E115267; Industrial control equipment
  • EN ISO 13849-1:2015 Category
    Cat. 3 if parameter "Disable OSSD = Yes - Warning", ; Cat. 4 if parameter "Disable OSSD = No"
  • Certifications EAC
    Yes
  • Certifications ATEX
    Zone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X
  • Power consumption Internal I/O
    1.4 W
  • Power consumption Bus
    0.32 W
  • Blackout mode Function
    Module functionality
  • Certifications UKCA
    Yes
  • Certifications CE
    Yes
  • Electrical isolation Channel - Channel
    No
  • System requirements Safety Release
    1.7 or later
  • Blackout mode Standalone mode
    No
  • Diagnostics Outputs
    Yes, using LED status indicator and software
  • Electrical isolation Channel - Bus
    Yes
  • Blackout mode Scope
    Module
  • System requirements Automation Runtime
    V3.08 or later
  • System requirements SafeDESIGNER
    3.1.0 or later
  • Pitch
    25+0.2 mm
  • Note
    Order 1x safety-keyed terminal block separately.; Order 1x safety-keyed bus module separately.
  • Diagnostics Module run/error
    Yes, using LED status indicator and software
  • System requirements mapp Technology Package
    mapp Safety 5.7.0 or later
  • System requirements Automation Studio
    4.0.16 or later
  • Max. switching frequency
    See section "Inrush current behavior for output channels".
  • Degree of protection per EN 60529
    IP20
  • IOUT
    <100 µA
  • Max. capacitive load
    100 nF
  • Switching voltage
    I/O power supply minus voltage drop due to RDS(on)
  • Braking voltage when switching off inductive loads
    Max. 45 VDC
  • Installation elevation above sea level
    0 to 2000 m, no limitation
  • RDS(on)
    4.7 Ω
  • IGND
    <70 mA
  • Test pulse length
    Max. 10 µs
  • Output protection
    See section "Inrush current behavior for output channels".
  • Leakage current when the output is switched off
    <100 µA
  • Insulation voltage between channel and bus
    500 Veff
  • Error detection time
    1 s
  • Total nominal current
    1.2 A
  • Max. I/O cycle time
    1 ms
  • Nominal output current
    0.2 A
  • Variant
    FET, 2x positive switching, type B1, output level readable
  • Peak short-circuit current
    See section "Inrush current behavior for output channels".
  • Voltage range
    24 VDC -15% / +20%
  • Quantity
    6
  • B&R ID code
    0xDD88
  • Status indicators
    I/O function per channel, operating state, module status
  • Nominal voltage
    24 VDC
  • I/O module
    6 safe type B1 digital outputs, 24 VDC, 0.2 A, OSSD <10 µs
  • Integrated protection
    Reverse polarity protection
  • Additional power dissipation caused by actuators (resistive) [W]
    1.128

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging



1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of B&R

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

B&R Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many B&R Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from B&R, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo