Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

LC1K0910D7 Schneider Electric Industrial Automation Components

Schneider Electric LC1K0910D7 Schneider Electric LC1K0910D7 is a magnetic contactor from the K sub-range, featuring screw connections and three poles (3P; 3NO). It has a rated current of 20A under AC-1 and 9A at 440Vac under AC-3 conditions. The net width of the contactor is 45 mm, and it offers a degree of protection of IP20. The control voltage (AC) ranges from 33.6-48.3Vac (42Vac nominal; 50Hz/60Hz; 0.8...1.15 x Uc), with a rated operating voltage (Ue) of 690 V. This model includes 1 Normally Open (NO) auxiliary contact but does not have Normally Closed (NC) auxiliary contacts. The rated impulse voltage (Uimp) is 8 kV, and the rated active power ranges from 2.2kW at 220-230Vac to 4kW at 660-690Vac under AC-3 conditions. The mechanical durability of the LC1K0910D7, at no load, is rated at 10,000,000 operations, and the rated voltage (AC) phase-to-phase is 690 V.
Schneider Electric

Part#:LC1K0910D7

Manufacturer:Schneider Electric

Product Lifecycle:Active

Get a quick Quote!

Schneider Electric LC1K0910D7 is a magnetic contactor from the K sub-range, featuring screw connections and three poles (3P; 3NO). It has a rated current of 20A under AC-1 and 9A at 440Vac under AC-3 conditions. The net width of the contactor is 45 mm, and it offers a degree of protection of IP20. The control voltage (AC) ranges from 33.6-48.3Vac (42Vac nominal; 50Hz/60Hz; 0.8...1.15 x Uc), with a rated operating voltage (Ue) of 690 V. This model includes 1 Normally Open (NO) auxiliary contact but does not have Normally Closed (NC) auxiliary contacts. The rated impulse voltage (Uimp) is 8 kV, and the rated active power ranges from 2.2kW at 220-230Vac to 4kW at 660-690Vac under AC-3 conditions. The mechanical durability of the LC1K0910D7, at no load, is rated at 10,000,000 operations, and the rated voltage (AC) phase-to-phase is 690 V.

About the manufacturer: Schneider Electric is one of the manufacturers that offers Industrial Automation Components that you can order at Quotebeam.com. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.

Check out the LC1K0910D7 Schneider Electric price in the box on the right side or send a quick quote.

Product Details

  • Motor Power Kw
    2.2 kW 220...230 V AC 50/60 Hz AC-3 4 kW 380...415 V AC 50/60 Hz AC-3 4 kW 440 V AC 50/60 Hz AC-3 4 kW 480 V AC 50/60 Hz AC-3 4 kW 500...600 V AC 50/60 Hz AC-3 4 kW 660...690 V AC 50/60 Hz AC-3 2.2 kW 400 V AC 50/60 Hz AC-4
  • Rated Breaking Capacity
    110 A 415 V IEC 60947 110 A 440 V IEC 60947 80 A 500 V IEC 60947 110 A 220...230 V IEC 60947 110 A 380...400 V IEC 60947 70 A 660...690 V IEC 60947
  • Associated Fuse Rating
    25 A gG <= 440 V power circuit 25 A aM power circuit 10 A gG signalling circuit IEC 60947 10 A gG signalling circuit VDE 0660
  • Mechanical Robustness
    Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 Shocks contac
  • Irms Rated Making Capacity
    110 A AC power circuit NF C 63-110 110 A AC power circuit IEC 60947 110 A AC signalling circuit IEC 60947
  • [Ie] Rated Operational Current
    20 A 122 °F (50 °C)) <= 440 V AC AC-1 power circuit 9 A<= 440 V AC AC-3 power circuit 16 A 158 °F (70 °C)) 690 V AC AC-1 power circuit
  • Utilisation Category
    AC-3 AC-1 AC-4
  • Safety Reliability Level
    B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Operating Time
    10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing
  • Control Circuit Voltage Limits
    Operational: 0.8...1.15 Uc (at <50 °C) Drop-out: 0.2...0.75 Uc (at <50 °C)
  • Contactor Application
    Resistive load Motor control
  • [Ith] Conventional Free Air Thermal Current
    20 A 122 °F (50 °C) power circuit 10 A 122 °F (50 °C) signalling circuit
  • Minimum Switching Voltage
    17 V signalling circuit
  • Minimum Switching Current
    5 mA signalling circuit
  • Non Overlap Distance
    0.02 in (0.5 mm)
  • Signalling Circuit Frequency
    <= 400 Hz
  • Auxiliary Contacts Type
    Instantaneous 1 NO
  • Insulation Resistance
    > 10 MOhm for signalling circuit
  • Maximum Operating Rate
    3600 cyc/h
  • Hold-In Power Consumption In VA
    4.5 VA 68 °F (20 °C))
  • Heat Dissipation
    1.3 W
  • Inrush Power In VA
    30 VA 68 °F (20 °C))
  • Average Impedance
    3 mOhm - Ith 20 A 50 Hz power circuit
  • Overvoltage Category
    III
  • Auxiliary Contact Composition
    1 NO
  • [Uc] Control Circuit Voltage
    42 V AC 50/60 Hz
  • Control Circuit Type
    AC at 50/60 Hz
  • Poles Description
    3P
  • Product Name
    TeSys K
  • Power Pole Contact Composition
    3 NO
  • Device Application
    Control
  • Product Or Component Type
    Contactor
  • Device Short Name
    LC1K
  • Range
    TeSys

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging



1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Schneider Electric

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Schneider Electric Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Schneider Electric Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Schneider Electric, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo