LC1K1201P7 Schneider Electric Industrial Automation Components
Part#:LC1K1201P7
Manufacturer:Schneider Electric
Product Lifecycle:Active
Get a quick Quote!
Schneider Electric LC1K1201P7 is a magnetic contactor within the K sub-range, featuring screw connections and designed with 3 poles (3P; 3NO). It has a rated current of 20A under AC-1 and 12A at 440Vac under AC-3 conditions. The contactor's net width is 45 mm and it offers a degree of protection rated at IP20. The control voltage (AC) ranges from 184-264Vac (230Vac nominal; 50Hz/60Hz; 0.8...1.15 x Uc), with a rated operating voltage (Ue) of 690 V. This model includes 0 normally open (NO) auxiliary contacts and 1 normally closed (NC) auxiliary contact. The rated impulse voltage (Uimp) is 8 kV. It supports rated active power of 3kW at 220-230Vac, 5.5kW at 380-415Vac and 440Vac, 4kW at 500Vac, and 4kW at 660-690Vac, all under AC-3 conditions. The mechanical durability of the LC1K1201P7, at no load, is rated for 10,000,000 operations, and it has a phase-to-phase rated voltage (AC) of 690 V.
About the manufacturer: Schneider Electric is one of the manufacturers that offers Industrial Automation Components that you can order at Quotebeam.com. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.
Check out the LC1K1201P7 Schneider Electric price in the box on the right side or send a quick quote.
Product Details
- Motor Power Kw 4 kW 480 V AC 50/60 Hz AC-3 4 kW 500...600 V AC 50/60 Hz AC-3 4 kW 660...690 V AC 50/60 Hz AC-3 2.2 kW 400 V AC 50/60 Hz AC-4 3 kW 220...230 V AC 50/60 Hz AC-3 5.5 kW 380...415 V AC 50/60 Hz AC-3 5.5 kW 440 V AC 50/60 Hz AC-3
- [Icw] Rated Short-Time Withstand Current 115 A 122 °F (50 °C) - 1 s power circuit 105 A 122 °F (50 °C) - 5 s power circuit 100 A 122 °F (50 °C) - 10 s power circuit 75 A 122 °F (50 °C) - 30 s power circuit 55 A 122 °F (50 °C) - 1 min power circuit 50 A 122 °F (50 °C) - 3
- [Ui] Rated Insulation Voltage Power circuit 600 V UL 508 Power circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-5-1 Signalling circuit 600 V UL 508 Power circuit 600 V CSA C22.2 No 14 Signalling circuit
- Connections - Terminals screw clamp terminals 1 0.00…0.01 in² (1.5…4 mm²)solid screw clamp terminals 1 0.00…0.01 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.00…0.00 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.00…
- Mechanical Robustness Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 Shocks contac
- Associated Fuse Rating 25 A gG <= 440 V power circuit 25 A aM power circuit 10 A gG signalling circuit IEC 60947 10 A gG signalling circuit VDE 0660
- Rated Breaking Capacity 110 A 440 V IEC 60947 80 A 500 V IEC 60947 70 A 660...690 V IEC 60947
- Utilisation Category AC-1 AC-3 AC-4
- [Ie] Rated Operational Current 20 A 122 °F (50 °C)) <= 440 V AC AC-1 power circuit 12 A<= 440 V AC AC-3 power circuit 16 A 158 °F (70 °C)) 690 V AC AC-1 power circuit
- Irms Rated Making Capacity 110 A AC signalling circuit IEC 60947 144 A AC power circuit NF C 63-110 144 A AC power circuit IEC 60947
- Tightening Torque 11.51 lbf.in (1.3 N.m) screw clamp terminals Philips No 2 11.51 lbf.in (1.3 N.m) screw clamp terminals flat Ø 6 mm
- Contactor Application Resistive load Motor control
- Operating Time 10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing
- [Ue] Rated Operational Voltage Power circuit 690 V AC 50/60 Hz Signalling circuit <= 690 V AC 50/60 Hz
- Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- [Ith] Conventional Free Air Thermal Current 20 A 122 °F (50 °C) power circuit 10 A 122 °F (50 °C) signalling circuit
- Electrical Durability 0.3 Mcycles 20 A AC-1 <= 440 V 1.3 Mcycles 12 A AC-3 <= 440 V
- Control Circuit Voltage Limits Operational: 0.8...1.15 Uc (at <50 °C) Drop-out: 0.2...0.75 Uc (at <50 °C)
- Mounting Support Rail Plate
- Depth 2.24 in (57 mm)
- Net Weight 0.40 lb(US) (0.18 kg)
- Non Overlap Distance 0.02 in (0.5 mm)
- Width 1.77 in (45 mm)
- Height 2.28 in (58 mm)
- Mechanical Durability 10 Mcycles
- Maximum Operating Rate 3600 cyc/h
- Minimum Switching Voltage 17 V signalling circuit
- Signalling Circuit Frequency <= 400 Hz
- Minimum Switching Current 5 mA signalling circuit
- Auxiliary Contacts Type type instantaneous 1 NC
- Insulation Resistance > 10 MOhm for signalling circuit
- Inrush Power In VA 30 VA 68 °F (20 °C))
- Average Impedance 3 mOhm - Ith 20 A 50 Hz power circuit
- Heat Dissipation 1.3 W
- Hold-In Power Consumption In VA 4.5 VA 68 °F (20 °C))
- Auxiliary Contact Composition 1 NC
- Overvoltage Category III
- [Uimp] Rated Impulse Withstand Voltage 8 kV
- [Uc] Control Circuit Voltage 230 V AC 50/60 Hz
- Control Circuit Type AC at 50/60 Hz
- Product Or Component Type Contactor
- Poles Description 3P
- Device Short Name LC1K
- Power Pole Contact Composition 3 NO
- Device Application Control
- Product Name TeSys K
- Range TeSys
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
Related documents LC1K1201P7 Specs
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Schneider Electric
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Schneider Electric Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Schneider Electric Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Schneider Electric, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨