Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

LC1D50AG7 Schneider Electric Industrial Automation Components

Schneider Electric LC1D50AG7 Schneider Electric LC1D50AG7 is a magnetic contactor from the Deca sub-range, featuring an EverLink(TM) terminal design and screw connections. It is a 3-pole (3P; 3NO) contactor with a rated current of 80A (AC-1) and 50A (440Vac; AC-3). Designed for DIN rail mounting, it has a net width of 55 mm and offers a degree of protection of IP20. The control voltage (AC) ranges from 96-132Vac (120Vac nominal; 50Hz; 0.8...1.1 x Uc) to 102-132Vac (120Vac nominal; 60Hz; 0.85...1.1 x Uc), with a rated operating voltage (Ue) of 690 V. It includes 1 normally open (NO) auxiliary contact and 1 normally closed (NC) auxiliary contact, both of the instantaneous type (1NO+1NC). The rated impulse voltage (Uimp) is 6 kV. Its rated active power (kW) spans from 15kW (220-230Vac; AC-3) to 33kW (660-690Vac; AC-3), and the rated power (HP) ranges from 3HP (115Vac; single-phase; 50Hz/60Hz; UL/CSA) to 40HP (575-600Vac; 3-phase; 50Hz/60Hz; UL/CSA). The mechanical durability is rated at 6,000,000 operations, and the electrical durability (with load) is 1,450,000 operations. The rated voltage (AC) - phase-to-phase is 690 V.
Schneider Electric

Part#:LC1D50AG7

Manufacturer:Schneider Electric

Product Lifecycle:Active

In-stock parts: 29

Nov 14, 2024

Schneider Electric LC1D50AG7 is a magnetic contactor from the Deca sub-range, featuring an EverLink(TM) terminal design and screw connections. It is a 3-pole (3P; 3NO) contactor with a rated current of 80A (AC-1) and 50A (440Vac; AC-3). Designed for DIN rail mounting, it has a net width of 55 mm and offers a degree of protection of IP20. The control voltage (AC) ranges from 96-132Vac (120Vac nominal; 50Hz; 0.8...1.1 x Uc) to 102-132Vac (120Vac nominal; 60Hz; 0.85...1.1 x Uc), with a rated operating voltage (Ue) of 690 V. It includes 1 normally open (NO) auxiliary contact and 1 normally closed (NC) auxiliary contact, both of the instantaneous type (1NO+1NC). The rated impulse voltage (Uimp) is 6 kV. Its rated active power (kW) spans from 15kW (220-230Vac; AC-3) to 33kW (660-690Vac; AC-3), and the rated power (HP) ranges from 3HP (115Vac; single-phase; 50Hz/60Hz; UL/CSA) to 40HP (575-600Vac; 3-phase; 50Hz/60Hz; UL/CSA). The mechanical durability is rated at 6,000,000 operations, and the electrical durability (with load) is 1,450,000 operations. The rated voltage (AC) - phase-to-phase is 690 V.

About the manufacturer: Schneider Electric is one of the manufacturers that offers Industrial Automation Components that you can order at Quotebeam.com. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.

Check out the LC1D50AG7 Schneider Electric price in the box on the right side or send a quick quote.

Product Details

  • Product Certifications
    DNV GOST UL LROS (Lloyds register of shipping) GL RINA BV CSA CCC
  • [Ui] Rated Insulation Voltage
    Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL Power circuit 690 V IEC 60947-4-1
  • Motor Power HP (UL / CSA)
    3 hp 115 V at AC 50/60 Hz for 1 phase 7.5 hp 230/240 V at AC 50/60 Hz for 1 phase 15 hp 200/208 V at AC 50/60 Hz for 3 phase 15 hp 230/240 V at AC 50/60 Hz for 3 phase 40 hp 460/480 V at AC 50/60 Hz for 3 phase 40 hp 575/600 V at
  • [Icw] Rated Short-Time Withstand Current
    400 A 104 °F (40 °C) - 10 s power circuit 810 A 104 °F (40 °C) - 1 s power circuit 84 A 104 °F (40 °C) - 10 min power circuit 208 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circ
  • Standards
    CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
  • Control Circuit Voltage Limits
    0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 60 Hz 0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz 1...1.1 Uc 140…158 °F (60…70 °C) operational AC 60 Hz
  • Connections - Terminals
    Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)fle
  • Irms Rated Making Capacity
    140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 900 A 440 V power circuit IEC 60947
  • Tightening Torque
    Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 70.81 lbf.in (8 N.m) EverLink BTR screw connectors 0.04…0.05 in² (25…35 mm²) hexagon
  • Associated Fuse Rating
    10 A gG signalling circuit IEC 60947-5-1 100 A gG <= 690 V type 1 power circuit 100 A gG <= 690 V type 2 power circuit
  • Utilisation Category
    AC-1 AC-4 AC-3
  • Auxiliary Contacts Type
    Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
  • [Ith] Conventional Free Air Thermal Current
    10 A 140 °F (60 °C) signalling circuit 80 A 140 °F (60 °C) power circuit
  • Contactor Application
    Resistive load Motor control
  • [Ie] Rated Operational Current
    50 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit 80 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
  • Operating Time
    4...19 ms opening 12...26 ms closing
  • Power Dissipation Per Pole
    3.7 W AC-3 9.6 W AC-1
  • [Ue] Rated Operational Voltage
    Power circuit: <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
  • Electrical Durability
    1.45 Mcycles 50 A AC-3 <= 440 V 1.1 Mcycles 80 A AC-1 <= 440 V
  • Mounting Support
    Rail Plate
  • Safety Reliability Level
    B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Non-Overlap Time
    1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
  • Motor Power Kw
    15 kW 220...230 V AC 50/60 Hz AC-3) 22 kW 380...400 V AC 50/60 Hz AC-3) 30 kW 500 V AC 50/60 Hz AC-3) 33 kW 660...690 V AC 50/60 Hz AC-3) 25 kW 415 V AC 50/60 Hz AC-3) 30 kW 440 V AC 50/60 Hz AC-3) 11 kW 400 V AC 50/60 Hz AC-
  • Insulation Resistance
    > 10 MOhm for signalling circuit
  • Minimum Switching Current
    5 mA signalling circuit
  • Mechanical Durability
    6 Mcycles
  • Signalling Circuit Frequency
    25...400 Hz
  • Heat Dissipation
    4…5 W 60 Hz
  • Hold-In Power Consumption In VA
    13 VA 60 Hz 0.3 68 °F (20 °C))
  • Minimum Switching Voltage
    17 V signalling circuit
  • Inrush Power In VA
    140 VA 60 Hz 0.75 68 °F (20 °C))
  • Coil Technology
    Without built-in suppressor module
  • Maximum Operating Rate
    3600 cyc/h 140 °F (60 °C)
  • Front Cover
    With
  • Rated Breaking Capacity
    900 A 440 V power circuit IEC 60947
  • Average Impedance
    1.5 mOhm - Ith 80 A 50 Hz power circuit
  • [Uc] Control Circuit Voltage
    120 V AC 60 Hz
  • Overvoltage Category
    III
  • [Uimp] Rated Impulse Withstand Voltage
    6 kV IEC 60947
  • Auxiliary Contact Composition
    1 NO + 1 NC
  • Control Circuit Type
    AC 60 Hz
  • Power Pole Contact Composition
    3 NO
  • Product Or Component Type
    Contactor
  • Device Short Name
    LC1D
  • Range
    TeSys
  • Poles Description
    3P
  • Product Name
    TeSys D

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging



This item can ship within 24h!

1-year warranty

$248.40

Stock:

29

Select Qty:

$248.40

$248.40 each

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Schneider Electric

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Schneider Electric Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Schneider Electric Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Schneider Electric, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo