About the manufacturer: Schneider Electric is one of the manufacturers that offers Automation Components that you can order at Quotebeam.com. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.
Check out the LC1D123B7 Schneider Electric price in the box on the right side or send a quick quote.
LC1D123B7 Product Details
- Series: LC1D
- Type: Non-Reversing
- Size: 0
- Inductive Ampere: 0
- Poles: 3
- Enclosure: IP20
- Resistive Ampere: 0
- Mounting: Rail
- Power/Voltage: 0.5 HP at 115 Volt AC 50/60 Hertz 1-Phase
- Construction Standard: IEC
- Amps: 16 A at 440 Volt AC (AC-1)
- Approval: UL
- Shipping Height: 3.00 In.
- UPC: 389110802903
- Auxiliary Contact: 1NO-1NC
- Coil Voltage: 24 VAC 50/60 Hertz
- Shipping Width: 5.00 In.
- Shipping Length: 5.00 In.
- Shipping Weight: 0.85 lbs.
- Product Certifications CSA CCC RINA BV GOST GL DNV UL LROS (Lloyds register of shipping)
- [Ui] Rated Insulation Voltage Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL
- Motor Power Kw 3 kW 220...230 V AC 50/60 Hz AC-3) 5.5 kW 380...400 V AC 50/60 Hz AC-3) 5.5 kW 415...440 V AC 50/60 Hz AC-3) 7.5 kW 500 V AC 50/60 Hz AC-3) 7.5 kW 660...690 V AC 50/60 Hz AC-3) 3.7 kW 400 V AC 50/60 Hz AC-4)
- Standards CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
- Motor Power HP (UL / CSA) 0.5 hp 115 V at AC 50/60 Hz for 1 phase 2 hp 230/240 V at AC 50/60 Hz for 1 phase 3 hp 200/208 V at AC 50/60 Hz for 3 phase 3 hp 230/240 V at AC 50/60 Hz for 3 phase 7.5 hp 460/480 V at AC 50/60 Hz for 3 phase 10 hp 575/600 V at A
- [Icw] Rated Short-Time Withstand Current 105 A 104 °F (40 °C) - 10 s power circuit 210 A 104 °F (40 °C) - 1 s power circuit 30 A 104 °F (40 °C) - 10 min power circuit 61 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circu
- Connections - Terminals Power circuit spring terminals 1 0.00 in² (2.5 mm²)flexible without cable end Power circuit spring terminals 2 0.00 in² (2.5 mm²)flexible without cable end Control circuit spring terminals 1 0.00 in² (2.5 mm²)flexible without cable end Cont
- Control Circuit Voltage Limits 0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz 0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz 0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz 1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
- Irms Rated Making Capacity 250 A 440 V power circuit IEC 60947 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1
- Associated Fuse Rating 10 A gG signalling circuit IEC 60947-5-1 40 A gG <= 690 V type 1 power circuit 25 A gG <= 690 V type 2 power circuit
- Utilisation Category AC-1 AC-4 AC-3
- Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Auxiliary Contacts Type Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
- Operating Time 12...22 ms closing 4...19 ms opening
- Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
- [Ue] Rated Operational Voltage Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
- [Ith] Conventional Free Air Thermal Current 10 A 140 °F (60 °C) signalling circuit 16 A 140 °F (60 °C) power circuit
- Mounting Support Plate Rail
- Contactor Application Motor control Resistive load
- Inrush Power In VA 70 VA 60 Hz 0.75 68 °F (20 °C)) 70 VA 50 Hz 0.75 68 °F (20 °C))
- Hold-In Power Consumption In VA 7.5 VA 60 Hz 0.3 68 °F (20 °C)) 7 VA 50 Hz 0.3 68 °F (20 °C))
- [Ie] Rated Operational Current 16 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit 12 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
- Power Dissipation Per Pole 0.36 W AC-3 1.56 W AC-1
- Electrical Durability 2 Mcycles 12 A AC-3 <= 440 V 0.8 Mcycles 25 A AC-1 <= 440 V
- Minimum Switching Voltage 17 V signalling circuit
- Insulation Resistance > 10 MOhm signalling circuit
- Minimum Switching Current 5 mA signalling circuit
- Signalling Circuit Frequency 25...400 Hz
- Heat Dissipation 2…3 W 50/60 Hz
- Mechanical Durability 15 Mcycles
- Maximum Operating Rate 3600 cyc/h 140 °F (60 °C)
- Coil Technology Without built-in suppressor module
- Front Cover With
- Rated Breaking Capacity 250 A 440 V power circuit IEC 60947
- Average Impedance 2.5 mOhm - Ith 16 A 50 Hz power circuit
- Overvoltage Category III
- [Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947
- Auxiliary Contact Composition 1 NO + 1 NC
- [Uc] Control Circuit Voltage 24 V AC 50/60 Hz
- Control Circuit Type AC 50/60 Hz
- Product Name TeSys D
- Power Pole Contact Composition 3 NO
- Product Or Component Type Contactor
- Poles Description 3P
- Device Short Name LC1D
- Range TeSys
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.
Related documents LC1D123B7 Specs
This item can ship within 5 days!
1-year warranty
$43.37
LC1D123B7
Stock:
70
Select Qty:
$43.37
$43.37 each
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Relevant products
Do you have questions?
We’re here for you ✨