Nikki Gonzales
Nick Goetz
Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

LC1D12G7 Schneider Electric Industrial Automation Components

Schneider Electric LC1D12G7 Schneider Electric LC1D12G7 is a magnetic contactor from the Deca sub-range, featuring screw connections and designed with 3 poles (3P; 3NO). It has a rated current of 25A for AC-1 and 12A for AC-3 at 440Vac, with a mounting mode suitable for DIN rail installation. The net width of the contactor is 45 mm, and it offers a degree of protection rated at IP20. The control voltage (AC) ranges from 96-132Vac at 50Hz and 102-132Vac at 60Hz, with a nominal control voltage of 120Vac. The rated operating voltage (Ue) is up to 690 V, and it includes 1 Normally Open (NO) auxiliary contact and 1 Normally Closed (NC) auxiliary contact, both of the instantaneous type (1NO+1NC). The rated impulse voltage (Uimp) is 6 kV. Its rated active power in AC-3 ranges from 3kW at 220-230Vac to 7.5kW at 660-690Vac. The rated power in horsepower (HP) varies from 0.5HP at 115Vac in single-phase to 10HP at 575-600Vac in three-phase, according to UL/CSA standards. The mechanical durability of the LC1D12G7 is rated at 15 million operations at no load, and its electrical durability with load is rated at 2 million operations. The rated voltage (AC) for phase-to-phase connections is 690 V.
Schneider Electric

Part#:LC1D12G7

Manufacturer:Schneider Electric

Product Lifecycle:Active

In-stock parts: 24

Sep 16, 2024

Schneider Electric LC1D12G7 is a magnetic contactor from the Deca sub-range, featuring screw connections and designed with 3 poles (3P; 3NO). It has a rated current of 25A for AC-1 and 12A for AC-3 at 440Vac, with a mounting mode suitable for DIN rail installation. The net width of the contactor is 45 mm, and it offers a degree of protection rated at IP20. The control voltage (AC) ranges from 96-132Vac at 50Hz and 102-132Vac at 60Hz, with a nominal control voltage of 120Vac. The rated operating voltage (Ue) is up to 690 V, and it includes 1 Normally Open (NO) auxiliary contact and 1 Normally Closed (NC) auxiliary contact, both of the instantaneous type (1NO+1NC). The rated impulse voltage (Uimp) is 6 kV. Its rated active power in AC-3 ranges from 3kW at 220-230Vac to 7.5kW at 660-690Vac. The rated power in horsepower (HP) varies from 0.5HP at 115Vac in single-phase to 10HP at 575-600Vac in three-phase, according to UL/CSA standards. The mechanical durability of the LC1D12G7 is rated at 15 million operations at no load, and its electrical durability with load is rated at 2 million operations. The rated voltage (AC) for phase-to-phase connections is 690 V.

About the manufacturer: Schneider Electric is one of the manufacturers that offers Industrial Automation Components that you can order at Quotebeam.com. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.

Check out the LC1D12G7 Schneider Electric price in the box on the right side or send a quick quote.

Product Details

  • Product Certifications
    DNV GOST GL CSA BV LROS (Lloyds register of shipping) UL RINA CCC
  • Standards
    CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
  • [Icw] Rated Short-Time Withstand Current
    105 A 104 °F (40 °C) - 10 s power circuit 210 A 104 °F (40 °C) - 1 s power circuit 30 A 104 °F (40 °C) - 10 min power circuit 61 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circu
  • Motor Power Kw
    3 kW 220...230 V AC 50/60 Hz AC-3) 5.5 kW 380...400 V AC 50/60 Hz AC-3) 5.5 kW 415...440 V AC 50/60 Hz AC-3) 7.5 kW 500 V AC 50/60 Hz AC-3) 7.5 kW 660...690 V AC 50/60 Hz AC-3) 3.7 kW 400 V AC 50/60 Hz AC-4)
  • [Ui] Rated Insulation Voltage
    Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL
  • Motor Power HP (UL / CSA)
    0.5 hp 115 V at AC 50/60 Hz for 1 phase 2 hp 230/240 V at AC 50/60 Hz for 1 phase 3 hp 200/208 V at AC 50/60 Hz for 3 phase 3 hp 230/240 V at AC 50/60 Hz for 3 phase 7.5 hp 460/480 V at AC 50/60 Hz for 3 phase 10 hp 575/600 V at A
  • Tightening Torque
    Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lb
  • Control Circuit Voltage Limits
    0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz 0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz 0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz 1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
  • Connections - Terminals
    Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible
  • Irms Rated Making Capacity
    250 A 440 V power circuit IEC 60947 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1
  • Utilisation Category
    AC-3 AC-4 AC-1
  • Non-Overlap Time
    1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
  • Hold-In Power Consumption In VA
    7.5 VA 60 Hz 0.3 68 °F (20 °C)) 7 VA 50 Hz 0.3 68 °F (20 °C))
  • Safety Reliability Level
    B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Mounting Support
    Rail Plate
  • Operating Time
    12...22 ms closing 4...19 ms opening
  • Auxiliary Contacts Type
    Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
  • Contactor Application
    Motor control Resistive load
  • Electrical Durability
    2 Mcycles 12 A AC-3 <= 440 V 0.8 Mcycles 25 A AC-1 <= 440 V
  • Associated Fuse Rating
    10 A gG signalling circuit IEC 60947-5-1 40 A gG <= 690 V type 1 power circuit 25 A gG <= 690 V type 2 power circuit
  • Inrush Power In VA
    70 VA 60 Hz 0.75 68 °F (20 °C)) 70 VA 50 Hz 0.75 68 °F (20 °C))
  • Power Dissipation Per Pole
    0.36 W AC-3 1.56 W AC-1
  • [Ue] Rated Operational Voltage
    Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
  • [Ie] Rated Operational Current
    25 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit 12 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
  • [Ith] Conventional Free Air Thermal Current
    25 A 140 °F (60 °C) power circuit 10 A 140 °F (60 °C) signalling circuit
  • Insulation Resistance
    > 10 MOhm signalling circuit
  • Signalling Circuit Frequency
    25...400 Hz
  • Heat Dissipation
    2…3 W 50/60 Hz
  • Coil Technology
    Without built-in suppressor module
  • Minimum Switching Current
    5 mA signalling circuit
  • Minimum Switching Voltage
    17 V signalling circuit
  • Maximum Operating Rate
    3600 cyc/h 140 °F (60 °C)
  • Mechanical Durability
    15 Mcycles
  • Front Cover
    With
  • Rated Breaking Capacity
    250 A 440 V power circuit IEC 60947
  • Average Impedance
    2.5 mOhm - Ith 25 A 50 Hz power circuit
  • [Uimp] Rated Impulse Withstand Voltage
    6 kV IEC 60947
  • Overvoltage Category
    III
  • Control Circuit Type
    AC 50/60 Hz
  • Poles Description
    3P
  • Auxiliary Contact Composition
    1 NO + 1 NC
  • [Uc] Control Circuit Voltage
    120 V AC 50/60 Hz
  • Power Pole Contact Composition
    3 NO
  • Device Short Name
    LC1D
  • Product Or Component Type
    Contactor
  • Product Name
    TeSys D
  • Range
    TeSys

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging



This item can ship within 24h!

1-year warranty

$120.00

Stock:

24

Select Qty:

$120.00

$120.00 each

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Schneider Electric

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Schneider Electric Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Schneider Electric Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Schneider Electric, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo