3050086 Phoenix Contact Terminal Blocks
Part#:3050086
Manufacturer:Phoenix Contact
Product Lifecycle:Active
In-stock parts: 92
Nov 22, 2024
Feed-through terminal block, nom. voltage: 500 V, nominal current: 17.5 A, connection method: Fast/plug-in connection, number of connections: 2, cross section: 0.25 mm² - 1.5 mm², AWG: 24 - 16, width: 5.2 mm, color: blue, mounting type: NS 35/7,5, NS 35/1
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 3050086 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Number of connections 2
- Color blue
- Overvoltage category III
- Nominal current IN 17.5 A
- Number of levels 1
- Flammability rating according to UL 94 V0
- Maximum power dissipation for nominal condition 0.56 W
- Nominal voltage UN 500 V
- Bending test turns 135
- Requirements, voltage drop U1 ≤ 3,2 mVU2 ≤ 1,5 x U1dT ≤ 45 K
- Result of thermal test Test passed
- Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2018-05
- Shock form Half-sine
- Shock duration 30 ms
- Insulating material PA
- Insulating material group I
- Maximum load current 17.5 A (with 1.5 mm² conductor cross section)
- Result of surge voltage test Test passed
- Nominal cross section 1.5 mm²
- Rated surge voltage 6 kV
- Open side panel Yes
- Power frequency withstand voltage setpoint 1.89 kV
- Tight fit on carrier NS 35
- Conductor cross section short circuit testing 1.5 mm²
- Ageing test for screwless modular terminal block temperature cycles 192
- ASD level 0.964 (m/s2)2/Hz
- Test duration per axis 5 h
- Test directions X-, Y- and Z-axis (pos. and neg.)
- Surface flammability NFPA 130 (ASTM E 162) passed
- Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
- Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
- Height NS 35/15 46.8 mm
- Conductor cross section solid max. 1.5 mm²
- Conductor cross section flexible max. 1.5 mm²
- Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
- Operating temperature -60 °C (see derating curve)
- ECLASS 11.0 27141120
- ECLASS 7.0 27141120
- ETIM 4.0 EC000897
- ETIM 7.0 EC000897
- UNSPSC 7.0901 39121410
- UNSPSC 19.0 39121410
- Potentials 1
- Area of application Railway industry
- Degree of pollution 3
- Surge voltage test setpoint 7.3 kV
- Result of tight fit on support Test passed
- Short-time current 0.18 kA
- Proof of thermal characteristics (needle flame) effective duration 30 s
- Oscillation, broadband noise test result Test passed
- Acceleration 5g
- Shock test result Test passed
- Relative insulation material temperature index (Elec., UL 746 B) 130 °C
- Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 130 °C
- Calorimetric heat release NFPA 130 (ASTM E 1354) 28 MJ/kg
- Width 5.2 mm
- Length 53.5 mm
- Connection method Fast/plug-in connection
- Conductor cross section AWG min. 24
- Material wire insulation PVC / PE
- Max. AWG conductor cross section, flexible 16
- Permissible humidity (storage/transport) 30 % ... 70 %
- China RoHS Environmentally friendly use period: unlimited = EFUP-e
- ECLASS 4.0 27141100
- ETIM 2.0 EC000897
- UNSPSC 6.01 30211811
- UNSPSC 12.01 39121410
- UNSPSC 18.0 39121410
- Result of power-frequency withstand voltage test Test passed
- Bending test rotation speed 10 rpm
- Requirement temperature-rise test Increase in temperature ≤ 45 K
- Short circuit stability result Test passed
- Test spectrum Service life test category 2, bogie-mounted
- Test frequency f1 = 5 Hz to f2 = 150 Hz
- Number of shocks per direction 3
- Static insulating material application in cold -60 °C
- Smoke gas toxicity NFPA 130 (SMP 800C) passed
- Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
- End cover width 2.2 mm
- Connection in acc. with standard CSA
- Conductor cross section solid min. 0.25 mm²
- Conductor cross section flexible min. 0.25 mm²
- Max. wire diameter incl. insulation 3 mm
- Ambient temperature (assembly) -5 °C ... 70 °C
- Ambient temperature (actuation) -5 °C ... 70 °C
- ECLASS 5.0 27141100
- ECLASS 9.0 27141120
- ETIM 6.0 EC000897
- UNSPSC 11 39121410
- UNSPSC 21.0 39121410
- Specific optical density of smoke NFPA 130 (ASTM E 662) passed
- Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
- Height NS 35/7,5 39.3 mm
- Connection 1st level connection right
- Conductor cross section AWG max. 16
- Min. AWG conductor cross section, flexible 24
- Internal cylindrical gage A3
- ECLASS 10.0.1 27141120
- ECLASS 4.1 27141100
- ECLASS 5.1 27141100
- ECLASS 6.0 27141100
- ETIM 3.0 EC000897
- UNSPSC 13.2 39121410
- UNSPSC 20.0 39121410
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 24h!
1-year warranty
$2.07
Stock:
92
Select Qty:
$2.07
$2.07 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.