2924087 Phoenix Contact Electrical Measuring & Monitoring Instruments
Part#:2924087
Manufacturer:Phoenix Contact
Product Lifecycle:Active
In-stock parts: 1
04/23/2024
About the product: Ex i NAMUR isolating amplifier, 2-channel. For operating proximity sensors and switches in Ex areas. The signals are transmitted via relay outputs (N/O contact) to the safe area. Line fault detection (LFD), 3-way isolation, SIL 2.
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2924087 Phoenix Contact price in the box on the right side or send a quick quote.
2924087 Product Details
- Degree of protection IP20 (not assessed by UL)
- Non-load voltage ~ 8 V DC
- Ambient temperature (operation) -20 °C ... 60 °C (Any mounting position)
- Switching points (attenuated) < 1.2 mA (blocking)
- Short-circuit current ~ 8 mA
- Mechanical service life 107 cycles
- Maximum switching capacity 500 VA
- Power dissipation < 1 W
- No. of channels 2
- Degree of pollution 2
- Equipment type Type A
- Safe Failure Fraction (SFF) 78 %
- λDU 6.2 x 10-8 (62 FIT)
- Max. internal capacitance Ci 11 nF
- Standards/regulations GB 3626.20
- DNV GL-Humidity B
- Width 12.5 mm
- Depth 114.5 mm
- Switching points (unattenuated) > 2.1 mA (conductive)
- Available input sources NAMUR proximity sensors (EN 60947-5-6)
- Switching frequency ≤ 20 Hz (without load)
- Power consumption 0.8 W
- Conductor cross section AWG 24 ... 16
- Housing material PA 6.6-FR
- Designation EAC Ex
- Insulation Safe isolation in accordance with IEC/EN 61010-1
- Rated insulation voltage 300 Vrms
- λSD 1 x 10-9 (1 FIT)
- Diagnostic coverage (DC) DCS = 0.4 %, DCD = 8 %
- Max. output current Io 10 mA
- Max. external capacitance Co 1 µF
- Evaluation criterion A
- ATEX II (1) G [Ex ia Ga] IIC
- Humidity B
- Vibration A
- Height 116 mm
- Permissible humidity (operation) 5 % ... 95 % (non-condensing)
- Noise immunity EN 61000-6-2 EN 61326
- Switching hysteresis < 0.2 mA
- Switching output Relay output
- Max. current consumption 35 mA (24 V DC)
- Stripping length 8 mm
- Conductor cross section solid 0.2 mm² ... 1.5 mm²
- Status display Green LED (supply voltage)
- Overvoltage category III
- Safety Integrity Level (SIL) 2
- Probability of a hazardous failure on demand (PFDAVG) 3.01 x 10-4 (1 year)
- Max. output power Po 25 mW
- Max. external inductivity Lo 10 µH
- UL, USA/Canada Class I Div 2; IS for Class I, II, III Div 1
- IECEx [Ex ia Ga] IIC
- Certificate RU C-DE.AB72.B.00093/19
- Enclosure Required protection according to the Rules shall be provided upon installation on board
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Maximum altitude ≤ 2000 m
- Ambient temperature (storage/transport) -40 °C ... 80 °C
- Signal input Intrinsically safe
- Contact type 1 N/O contact per channel
- Maximum switching voltage 250 V AC (2 A)
- Supply voltage range 19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
- Conductor cross section flexible 0.2 mm² ... 1.5 mm²
- Electrical isolation 375 V (Peak value in accordance with IEC/EN 60079-11)
- Test voltage 2.5 kV AC (50 Hz, 1 min.)
- λDD 6 x 10-9 (6 FIT)
- Max. output voltage Uo 9.6 V
- Additional text and EN 61326
- Conformance CE-compliant, additionally EN 61326
- DNV GL-EMC B
- DNV GL-Vibration A
- EMC B
- ECLASS 5.0 27210100
- ECLASS 5.1 27210100
- UNSPSC 7.0901 39121008
- UNSPSC 18.0 39121008
- Line fault detection Break 0.05 mA < IIN < 0.35 mA
- Contact material AgSnO2, hard gold-plated
- Nominal supply voltage 24 V DC
- Connection method Push-in connection
- Color gray
- Integrity requirement IEC 61508 - Low demand
- λSU 2.48 x 10-7 (248 FIT)
- Max. internal inductance Li negligible
- Group IIC
- Safety-related maximum voltage Um 253 V AC (125 V DC)
- DNV GL-Temperature B
- Identification [Ex ia Ga] IIC
- ECLASS 10.0.1 27210121
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 7.0 27210121
- ETIM 3.0 EC001485
- ETIM 4.0 EC001485
- UNSPSC 20.0 39121008
- DNV GL-Enclosure Required protection according to the Rules shall be provided upon installation on board
- Temperature B
- REACh SVHC Lead 7439-92-1
- ECLASS 4.1 27210100
- ETIM 2.0 EC001485
- ETIM 7.0 EC001485
- UNSPSC 13.2 39121008
- UNSPSC 21.0 39121008
- ECLASS 11.0 27210121
- UNSPSC 6.01 30211506
- UNSPSC 11 39121008
- ECLASS 4.0 27210100
- ECLASS 9.0 27210121
- UNSPSC 19.0 39121008
- ECLASS 6.0 27210100
- ETIM 6.0 EC001485
- UNSPSC 12.01 39121008
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.
This item can ship within 3 days!
1-year warranty
$240.98
2924087
Stock:
1
Select Qty:
$240.98
$240.98 each
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Relevant products
Do you have questions?
We’re here for you ✨