Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

2924016 Phoenix Contact Electrical Measuring & Monitoring Instruments

Phoenix Contact 2924016 Ex i repeater power supply and input signal conditioner, HART. Transmits supplied or active 0/4 - 20 mA signals from the hazardous area to a load (active or passive) in the safe area. 3-way electrical isolation; SIL 2 according to IEC 61508, with push-in
Phoenix Contact

Part#:2924016

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

Ex i repeater power supply and input signal conditioner, HART. Transmits supplied or active 0/4 - 20 mA signals from the hazardous area to a load (active or passive) in the safe area. 3-way electrical isolation; SIL 2 according to IEC 61508, with push-in

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2924016 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Overvoltage category
    II
  • Ambient temperature (operation)
    -20 °C ... 60 °C (Any mounting position)
  • Permissible humidity (operation)
    10 % ... 95 % (non-condensing)
  • Degree of protection
    IP20 (not assessed by UL)
  • Signal output
    Current output (active and passive)
  • Output behavior in the event of an error
    0 mA (Cable break in the input)
  • Power dissipation
    < 0.75 W (24 V DC / 20 mA / 1000 Ω)
  • Conductor cross section solid
    0.2 mm² ... 1.5 mm²
  • Temperature coefficient, typical
    < 0.004 %/K
  • Color
    gray
  • Electrical isolation
    375 V (Peak value in accordance with IEC/EN 60079-11)
  • Width
    12.5 mm
  • Maximum altitude
    ≤ 2000 m
  • Current input signal
    0 mA ... 20 mA
  • Polarization and surge protection
    Yes
  • Output ripple
    < 20 mVrms
  • Max. internal inductance Li
    negligible
  • Standards/regulations
    GB 3626.20
  • ATEX
     II (1) G [Ex ia Ga] IIC
  • DNV GL-Humidity
    B
  • EMC
    A
  • UNSPSC 7.0901
    39121008
  • Stripping length
    8 mm
  • Connection name
    Test socket
  • Maximum temperature coefficient
    < 0.01 %/K
  • Status display
    Green LED (supply voltage)
  • Housing material
    PA 6.6-FR
  • Insulation
    Safe isolation in accordance with IEC/EN 61010-1
  • Integrity requirement
    IEC 61508 - High demand
  • Safety Integrity Level (SIL)
    2
  • Max. output voltage Uo
    25.2 V
  • UNSPSC 18.0
    39121008
  • Max. external capacitance Co
    820 nF
  • No. of channels
    1
  • Interference emission
    EN 61000-6-4
  • Electromagnetic compatibility
    Conformance with EMC directive
  • Test voltage
    2.5 kV AC (50 Hz, 1 min.)
  • λDU
    5 x 10-8 (50 FIT)
  • λSD
    0
  • Probability of a hazardous failure per hour (PFHD)
    4,99 x 10-8
  • Safety-related maximum voltage Um
    253 V AC (125 V DC)
  • UNSPSC 12.01
    39121008
  • UNSPSC 6.01
    30211506
  • Height
    116 mm
  • Depth
    114.5 mm
  • Transmitter supply voltage
    > 16 V (20 mA)
  • Current output signal
    0 mA ... 20 mA (active)
  • Nominal supply voltage
    24 V DC
  • Power consumption
    < 1.8 W (20 mA / 1000 Ω)
  • Conductor cross section AWG
    24 ... 16
  • Utilization restriction
    EMC: class A product, see manufacturer's declaration in the download area
  • Signal input
    Passive current input, intrinsically safe
  • Transmission Behavior
    1:1 to input signal
  • Designation
    INMETRO
  • Max. current consumption
    < 44 mA (24 V DC / 20 mA / 1000 Ω)
  • UNSPSC 21.0
    39121008
  • Input voltage Ui
    ≤ 30 V
  • Noise immunity
    EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
  • Load/output load current output
    < 1000 Ω (20 mA)
  • Degree of pollution
    2
  • ETIM 7.0
    EC002653
  • UNSPSC 11
    39121008
  • UNSPSC 20.0
    39121008
  • Noise emission
    EN 61000-6-4
  • DNV GL-Vibration
    A
  • Certificate
    DNV 18.0136 X
  • Ambient temperature (storage/transport)
    -40 °C ... 80 °C
  • Voltage drop
    < 3.5 V (in input isolating amplifier operation)
  • Connection method
    Push-in connection
  • Underload/overload signal range
    0 mA ... 24 mA (Extended transmission range for diagnostics)
  • Probability of a hazardous failure on demand (PFDAVG)
    2.40 x 10-4 (1 year)
  • Max. external inductivity Lo
    4 mH
  • Safe Failure Fraction (SFF)
    90.7 %
  • Max. output current Io
    93 mA
  • Group
    IIC
  • Maximum transmission error
    < 0.1 % (of final value)
  • HART function
    Yes
  • Max. output power Po
    587 mW
  • Conformance
    CE-compliant, additionally EN 61326
  • DNV GL-Temperature
    B
  • DNV GL-EMC
    A
  • DNV GL-Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • ECLASS 11.0
    27210120
  • ETIM 4.0
    EC002653
  • Max. diameter
    2 mm
  • Conductor cross section flexible
    0.2 mm² ... 1.5 mm²
  • Transmission error, typical
    < 0.05 % (of final value)
  • Step response (10-90%)
    < 200 µs (for jump 4 mA ... 20 mA, load 600 Ω)
  • λSU
    4.867 x 10-7 (486.7 FIT)
  • Equipment type
    Type A
  • λDD
    0
  • Diagnostic coverage (DC)
    DCS=0 %, DCD=0 %
  • Additional text
    and EN 61326
  • Max. internal capacitance Ci
    negligible
  • UL, USA/Canada
    UL 61010 Listed
  • Temperature
    B
  • Vibration
    A
  • ECLASS 10.0.1
    27210120
  • ECLASS 5.0
    27210100
  • ECLASS 5.1
    27210100
  • ETIM 6.0
    EC002653
  • UNSPSC 13.2
    39121008
  • Supply voltage range
    19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
  • Protocols supported
    HART
  • Operation
    Signal conditioner operation
  • Input current Ii
    ≤ 150 mA
  • IECEx
    [Ex ia Ga] IIC
  • Identification
    [Ex ia Ga] IIC/IIB
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 6.0
    27210100
  • ECLASS 7.0
    27210120
  • ECLASS 9.0
    27210120
  • UNSPSC 19.0
    39121008
  • Rated insulation voltage
    300 Vrms
  • Typical deviation from the measuring range final value
    1 %
  • Humidity
    B
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 4.0
    27210100
  • ECLASS 4.1
    27210100

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo