Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

2909575 Phoenix Contact AC/DC Power Supplies

Phoenix Contact 2909575 Primary-switched power supply unit, QUINT POWER, Push-in connection, DIN rail mounting, input: 1-phase, output: 24 V DC / 1.3 A
Phoenix Contact

Part#:2909575

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 39

Nov 2, 2024

Primary-switched power supply unit, QUINT POWER, Push-in connection, DIN rail mounting, input: 1-phase, output: 24 V DC / 1.3 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2909575 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Height
    106 mm
  • Degree of protection
    IP20
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Current consumption
    0.46 A (100 V AC)
  • Input fuse
    3.15 A (slow-blow, internal)
  • Connection in series
    yes
  • Output power
    30 W
  • Environmental protection directive
    RoHS Directive 2011/65/EU
  • Efficiency
    typ. 89.2 % (120 V AC)
  • Assembly instructions
    DIN rail mounting
  • Standard - Electrical safety
    IEC 61010-2-201 (SELV)
  • EMC requirements for noise emission
    EN 61000-6-3
  • Standard – Safety extra-low voltage
    IEC 61010-1 (SELV)
  • Contact discharge
    8 kV (Test Level 4)
  • Flicker
    EN 61000-3-3
  • Electromagnetic HF field
    EN 61000-4-3
  • Conducted interference
    EN 61000-4-6
  • Additional text
    Test Level 2
  • Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
  • Input voltage range
    100 V AC ... 240 V AC -15 % ... +10 %
  • Inrush current
    typ. 5.9 A (at 25 °C)
  • Type of protection
    Transient surge protection
  • Static Boost (IStat.Boost)
    1.625 A (≤ 40 °C)
  • Feedback voltage resistance
    ≤ 35 V DC
  • Control deviation
    < 0.5 % (Static load change 10 % ... 90 %)
  • MTBF (IEC 61709, SN 29500)
    > 1904000 h (25 °C)
  • Conductor cross section solid min.
    0.2 mm²
  • Conductor cross section AWG min.
    24
  • Standard - Safety of transformers
    EN 61558-2-16
  • Conducted noise emission
    EN 55016
  • Electrostatic discharge
    EN 61000-4-2
  • Output
    1 kV (Test Level 3 - symmetrical)
  • Signal
    0.5 kV (Test Level 2 - symmetrical)
  • Frequency
    60 Hz
  • Number of periods
    0.5 / 1 / 5 / 50 periods
  • China RoHS
    Environmentally Friendly Use Period = 25;
  • ECLASS 7.0
    27049002
  • Depth
    90 mm
  • Degree of pollution
    2
  • Installation height
    ≤ 5000 m (> 2000 m, observe derating)
  • Protective circuit/component
    Varistor
  • Dynamic Boost (IDyn.Boost)
    2.6 A (≤ 60 °C (5 s))
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • Residual ripple
    < 40 mVPP (with nominal values)
  • Net weight
    0.188 kg
  • Insulation voltage input/output
    4 kV AC (type test)
  • Conductor cross section flexible max.
    2.5 mm²
  • Stripping length
    10 mm
  • Standard - safety for equipment for measurement, control, and laboratory use
    IEC 61010-1
  • Standard – Limitation of mains harmonic currents
    EN 61000-3-2
  • SIQ
    CB-Scheme (IEC 61010-1, IEC 61010-2-201)
  • Harmonic currents
    EN 61000-3-2
  • Frequency range
    50 Hz ... 60 Hz
  • Comments
    Criterion A
  • Surge voltage load (surge)
    EN 61000-4-5
  • Voltage dips
    EN 61000-4-11
  • Pulse-shape magnetic field
    EN 61000-4-9
  • Attenuated sinusoidal oscillations (ring wave)
    EN 61000-4-12
  • Width
    22.5 mm
  • Installation distance top/bottom
    30 mm / 30 mm
  • Ambient temperature (start-up type tested)
    -40 °C
  • Climatic class
    3K3 (in acc. with EN 60721)
  • Frequency range (fN)
    50 Hz ... 60 Hz -10 % ... +10 %
  • Nominal power consumption
    37 VA
  • Nominal output voltage
    24 V DC
  • Setting range of the output voltage (USet)
    24 V DC ... 28 V DC (constant capacity)
  • Typical response time
    500 ms
  • Power loss nominal load max.
    < 3.7 W (120 V AC)
  • Protection class
    II
  • Conductor cross section solid max.
    2.5 mm²
  • Conductor cross section AWG max.
    14
  • Standard - Safe isolation
    IEC 61558-2-16
  • UL approvals
    UL Listed UL 61010-1
  • Noise emission
    EN 55016
  • Discharge in air
    8 kV (Test Level 3)
  • Fast transients (burst)
    EN 61000-4-4
  • I/O/S
    asymmetrical
  • Power frequency magnetic field
    EN 61000-4-8
  • Test level 2
    16.67 Hz 50 Hz 60 Hz (Test Level 4)
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 5.1
    27242213
  • ETIM 7.0
    EC002540
  • UNSPSC 21.0
    39121004
  • Installation distance right/left
    0 mm / 0 mm
  • Ambient temperature (operation)
    -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Max. permissible relative humidity (operation)
    ≤ 95 % (at 25 °C, non-condensing)
  • Dielectric strength maximum
    300 V AC 30 s
  • Discharge current to PE
    < 0.25 mA (264 V AC, 60 Hz)
  • Mains buffering time
    typ. 43 ms (120 V AC)
  • Nominal output current (IN)
    1.3 A
  • Derating
    > 60 °C (2.5%/K)
  • Protection against overvoltage at the output (OVP)
    ≤ 32 V DC
  • Maximum power dissipation in no-load condition
    < 0.4 W (230 V AC)
  • Connection method
    Push-in connection
  • Conductor cross section flexible min.
    0.2 mm²
  • EMC requirements for noise immunity
    EN 61000-6-1
  • Standard - power supply devices for low voltage with DC output
    EN 61204-3
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Test field strength
    1000 A/m
  • Input
    2 kV (symmetrical)
  • Voltage
    300 V (1 s)
  • Voltage dip
    0 %
  • Test level 1
    16.67 Hz 50 Hz 60 Hz (Test Level 2)
  • Criterion A
    Normal operating behavior within the specified limits.
  • ECLASS 11.0
    27040701
  • ECLASS 6.0
    27049000
  • UNSPSC 20.0
    39121004
  • Asymmetrical conducted disturbance variables
    EN 61000-4-16
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • ECLASS 10.0.1
    27040701
  • ETIM 6.0
    EC002540
  • UNSPSC 18.0
    39121004
  • Criterion C
    Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
  • ECLASS 9.0
    27040701
  • UNSPSC 19.0
    39121004
  • UNSPSC 13.2
    39121004

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


This item can ship within 24h!

1-year warranty

$80.61

Stock:

39

Select Qty:

$80.61

$80.61 each

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo