Nikki Gonzales
Nick Goetz
Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

2864273 Phoenix Contact Electrical Measuring & Monitoring Instruments

Phoenix Contact 2864273 MCR temperature transducer for Pt 100 temperature sensors, configured via DIP switch, with screw connection, not pre-configured
Phoenix Contact

Part#:2864273

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 29

Apr 25, 2024

About the product: MCR temperature transducer for Pt 100 temperature sensors, configured via DIP switch, with screw connection, not pre-configured

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2864273 Phoenix Contact price in the box on the right side or send a quick quote.

2864273 Product Details

  • Height
    93.1 mm
  • Ambient temperature (operation)
    -20 °C ... 65 °C
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Number of outputs
    1
  • Ripple
    < 20 mVPP (at 10 kΩ)
  • Short-circuit current
    approx. 10 mA
  • Stripping length
    12 mm
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Maximum temperature coefficient
    < 0.02 %/K
  • Color
    green
  • Utilization restriction
    EMC: class A product, see manufacturer's declaration in the download area
  • Configurable/programmable
    Yes, unconfigured
  • Load/output load voltage output
    ≥ 10 kΩ
  • Supply voltage range
    19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
  • Power consumption
    < 500 mW
  • Protective circuit
    Transient protection
  • Overvoltage category
    II
  • ECLASS 9.0
    27210129
  • Depth
    101.2 mm
  • Permissible humidity (operation)
    5 % ... 95 % (non-condensing)
  • Noise immunity
    EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
  • Voltage output signal
    0 V ... 10 V
  • Max. current consumption
    < 21 mA (at 24 V DC)
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm²
  • No. of channels
    1
  • Maximum altitude
    ≤ 2000 m
  • Sensor input current
    1 mA (constant)
  • Connection technology
    2-, 3-, 4-conductor
  • Load/output load current output
    < 500 Ω (at 20 mA)
  • Connection method
    Screw connection
  • Screw thread
    M3
  • Transmission error in the set measuring range
    ((100 K / set measurement range [K]) + 0.1)%
  • Rated insulation voltage
    50 V AC/DC
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 2
  • Identification
    UL 508 Recognized
  • Connection in acc. with standard
    CUL
  • Vibration
    B
  • ECLASS 5.1
    27200200
  • ECLASS 7.0
    27200206
  • ETIM 4.0
    EC001446
  • UNSPSC 13.2
    41112105
  • UNSPSC 20.0
    41112105
  • Electrical isolation
    Basic insulation according to EN 61010
  • Noise emission
    EN 61000-6-4
  • Humidity
    B
  • ETIM 2.0
    EC001446
  • UNSPSC 7.0901
    39121008
  • UNSPSC 12.01
    39121008
  • Width
    6.2 mm
  • Degree of protection
    IP20
  • Sensor types (RTD) that can be used
    Pt 100 (IEC 60751/EN 60751)
  • Current output signal
    0 mA ... 20 mA
  • Max. output current
    23 mA
  • Max. output voltage
    approx. 12.5 V
  • Degree of pollution
    2
  • Test voltage, input/output/supply
    1.5 kV (50 Hz, 1 min.)
  • Housing material
    PBT
  • Designation
    Shipbuilding approval
  • Electromagnetic compatibility
    Conformance with EMC directive
  • Assembly instructions
    The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
  • Standards/regulations
    EN 61000-4-6
  • Temperature
    B
  • Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 2
  • Typical deviation from the measuring range final value
    10 %
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 10.0.1
    27210129
  • ECLASS 6.0
    27200200
  • ETIM 6.0
    EC002919
  • UNSPSC 11
    39121008
  • UNSPSC 21.0
    41112105
  • Conductor cross section AWG
    26 ... 12
  • Mounting position
    any
  • Certificate
    DNV GL TAA00002R0
  • EMC
    A
  • ECLASS 11.0
    27210129
  • ECLASS 4.0
    27200200
  • ETIM 7.0
    EC002919
  • UNSPSC 6.01
    30211506
  • Transmission error in the full measuring range
    ≤ 0,2 %
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 2
  • UNSPSC 18.0
    41112105
  • Nominal supply voltage
    24 V DC
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 4.1
    27200200
  • ECLASS 5.0
    27200200
  • ETIM 3.0
    EC001446
  • UNSPSC 19.0
    41112105

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

This item can ship within 5 days!

1-year warranty

$244.39

2864273

Stock:

29

Select Qty:

$244.39

$244.39 each

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo