2902999 Phoenix Contact AC/DC Power Supplies
Part#:2902999
Manufacturer:Phoenix Contact
Product Lifecycle:Active
In-stock parts: 2
Nov 22, 2024
Primary-switched UNO POWER power supply for DIN rail mounting, input: 1-phase, output: 12 V DC/55 W
About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2902999 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Mains buffering time > 20 ms (120 V AC)
- Protective circuit/component Varistor
- Protection against overvoltage at the output (OVP) ≤ 25 V DC
- Connection in parallel Yes, for redundancy and increased capacity
- Net weight 0.2 kg
- ECLASS 5.0 27049000
- Ambient temperature (operation) -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K)
- Climatic class 3K3 (in acc. with EN 60721)
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Degree of protection IP20
- Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
- Nominal input voltage range 100 V AC ... 240 V AC
- Inrush current < 30 A (typical)
- Nominal output voltage 12 V DC ±1 %
- Connection in series yes
- Control deviation < 1 % (change in load, static 10 % ... 90 %)
- MTBF (IEC 61709, SN 29500) > 865000 h (40 °C)
- Housing material Polycarbonate
- Conductor cross section solid min. 0.2 mm²
- Stripping length 8 mm
- Standard - Electrical safety IEC 62368-1/VDE 0805 (SELV)
- Mains variation/undervoltage EN 61000-4-11
- Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
- Degree of pollution 2
- Frequency range (fN) 50 Hz ... 60 Hz 10 %
- Nominal power consumption 127 VA
- Power factor (cos phi) 0.49
- Feedback voltage resistance < 25 V DC
- Power loss nominal load max. < 8 W
- Protection class II (in closed control cabinet)
- Assembly instructions alignable: 0 mm horizontally, 30 mm vertically
- Conductor cross section flexible max. 2.5 mm²
- Screw thread M3
- Standard – Limitation of mains harmonic currents EN 61000-3-2
- Contact discharge 6 kV (Test Level 3)
- Comments Criterion A
- Surge voltage load (surge) EN 61000-4-5
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- ECLASS 4.0 27040700
- Input voltage range 85 V AC ... 264 V AC
- Current consumption 1.3 A (100 V AC)
- Type of protection Transient surge protection
- Input fuse 2 A (slow-blow, internal)
- Test field strength 10 V/m
- AC frequency range 50 Hz ... 60 Hz -10 % ... +10 %
- Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
- Nominal output current (IN) 4.6 A (-25 °C ... 55 °C)
- Residual ripple < 30 mVPP (with nominal values)
- Output power 55 W
- Conductor cross section flexible min. 0.2 mm²
- Foot latch material POM (Polyoxymethylen)
- EMC requirements for noise immunity EN 61000-6-1
- Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)
- UL approvals UL/C-UL listed UL 508
- Discharge in air 8 kV (Test Level 3)
- Output 1 kV (Test Level 2 - symmetrical)
- Voltage 10 V (Test Level 3)
- ECLASS 10.0.1 27040701
- ECLASS 5.1 27049000
- Width 35 mm
- Installation distance right/left 0 mm / 0 mm
- Typical response time < 1 s
- Standard - Safe isolation DIN VDE 0100-410
- Electromagnetic HF field EN 61000-4-3
- Frequency range 150 kHz ... 80 MHz
- Voltage dips EN 61000-4-11
- China RoHS Environmentally Friendly Use Period = 25;
- Criterion A Normal operating behavior within the specified limits.
- ECLASS 7.0 27049002
- ETIM 6.0 EC002540
- ETIM 3.0 EC001039
- Depth 84 mm
- Installation distance top/bottom 30 mm / 30 mm
- Maximum power dissipation in no-load condition < 0.3 W
- Connection method Screw connection
- Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
- Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
- Fast transients (burst) EN 61000-4-4
- Conducted interference EN 61000-4-6
- ECLASS 6.0 27049000
- ETIM 7.0 EC002540
- UNSPSC 6.01 30211502
- UNSPSC 12.01 39121004
- UNSPSC 21.0 39121004
- Ambient temperature (start-up type tested) -25 °C
- Derating 55 °C ... 70 °C (2.5%/K)
- Conductor cross section solid max. 2.5 mm²
- EMC requirements for noise emission EN 61000-6-3
- Standard - Safety of transformers EN 61558-2-16
- CSA CAN/CSA-C22.2 No. 60950-1-07
- Electrostatic discharge EN 61000-4-2
- ECLASS 9.0 27040701
- UNSPSC 11 39121004
- UNSPSC 19.0 39121004
- UNSPSC 18.0 39121004
- Height 90 mm
- Efficiency typ. 87 % (120 V AC)
- Insulation voltage input/output 4 kV AC (type test)
- Mounting position horizontal DIN rail NS 35, EN 60715
- Conductor cross section AWG max. 14
- Conductor cross section AWG min. 24
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- Input 2 kV (Test Level 3 - symmetrical)
- ECLASS 11.0 27040701
- ECLASS 4.1 27040700
- ETIM 4.0 EC000599
- UNSPSC 7.0901 39121004
- UNSPSC 13.2 39121004
- UNSPSC 20.0 39121004
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 24h!
1-year warranty
$64.60
Stock:
2
Select Qty:
$64.60
$64.60 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨