Nikki Gonzales
Nick Goetz
Bryan Obida

We are online

Monday - Friday 6AM - 6PM PST

2866789 Phoenix Contact AC/DC Power Supplies

Phoenix Contact 2866789 Primary-switched power supply unit, QUINT POWER, Screw connection, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input: 1-phase, output: 24 V DC / 40 A
Phoenix Contact

Part#:2866789

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 10

Apr 25, 2024

About the product: Primary-switched power supply unit, QUINT POWER, Screw connection, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input: 1-phase, output: 24 V DC / 40 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2866789 Phoenix Contact price in the box on the right side or send a quick quote.

2866789 Product Details

  • Height
    130 mm
  • Installation distance top/bottom
    50 mm / 50 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Input voltage range
    85 V AC ... 264 V AC
  • Depth
    125 mm
  • Depth with alternative assembly
    183 mm
  • Ambient temperature (operation)
    -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Climatic class
    3K3 (in acc. with EN 60721)
  • Nominal input voltage range
    100 V AC ... 240 V AC
  • Mains buffering time
    > 35 ms (120 V AC)
  • Type of protection
    Transient surge protection
  • Nominal output voltage
    24 V DC ±1 %
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • Maximum power dissipation in no-load condition
    14 W
  • MTBF (IEC 61709, SN 29500)
    > 900000 h (25 °C)
  • Protection class
    I
  • Conductor cross section solid min.
    0.2 mm²
  • Screw thread
    M3
  • Standard – Safety extra-low voltage
    IEC 60950-1 (SELV) and EN 60204-1 (PELV)
  • Width with alternative assembly
    122 mm
  • Ambient temperature (start-up type tested)
    -40 °C
  • Max. permissible relative humidity (operation)
    ≤ 95 % (at 25 °C, non-condensing)
  • Discharge current to PE
    < 3.5 mA
  • Recommended breaker for input protection
    16 A ... 20 A (AC: Characteristics B, C, D, K)
  • Nominal output current (IN)
    40 A (-25 °C ... 60 °C, UOUT = 24 V DC)
  • Protection against overvoltage at the output (OVP)
    < 35 V DC
  • Output power
    960 W
  • Insulation voltage output / PE
    500 V DC (routine test)
  • Conductor cross section solid max.
    6 mm²
  • Stripping length
    10 mm
  • Standard – Limitation of mains harmonic currents
    EN 61000-3-2
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Width
    180 mm
  • Height with alternative assembly
    130 mm
  • Degree of pollution
    2
  • Dielectric strength maximum
    300 V AC
  • Frequency range DC
    0 Hz
  • Input fuse
    20 A (slow-blow, internal)
  • Setting range of the output voltage (USet)
    18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
  • Selective Fuse Breaking (ISFB)
    215 A (12 ms)
  • Feedback voltage resistance
    max. 35 V DC
  • Typical response time
    < 0.7 s
  • Net weight
    3.3 kg
  • Insulation voltage input / PE
    3.5 kV AC (type test)
  • Assembly instructions
    alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
  • Conductor cross section flexible min.
    0.2 mm²
  • Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
    EN 50178/VDE 0160 (PELV)
  • Rail applications
    EN 50121-4
  • Electrostatic discharge
    EN 61000-4-2
  • Test field strength
    10 V/m (Test Level 3)
  • Wireless telephone simulation
    ENV 50204
  • China RoHS
    Environmentally Friendly Use Period = 25;
  • ECLASS 5.1
    27049000
  • ETIM 4.0
    EC000599
  • UNSPSC 12.01
    39121004
  • UNSPSC 18.0
    39121004
  • Installation distance right/left
    5 mm / 5 mm
  • Degree of protection
    IP20
  • Installation height
    4000 m
  • AC frequency range
    45 Hz ... 65 Hz
  • Nominal power consumption
    1157 VA
  • Inrush current
    < 15 A (typical)
  • Protective circuit/component
    Varistor, gas-filled surge arrester
  • Derating
    60 °C ... 70 °C (2.5%/K)
  • Connection in series
    yes
  • Efficiency
    > 92 % (for 230 V AC and nominal values)
  • Mounting position
    horizontal DIN rail NS 35, EN 60715
  • Conductor cross section AWG min.
    24
  • EMC requirements for noise immunity
    EN 61000-6-1
  • Standard - Electrical safety
    IEC 60950-1/VDE 0805 (SELV)
  • Standard - Safe isolation
    DIN VDE 0100-410
  • Standard - Equipment safety
    BG (design tested)
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • Frequency range
    0.15 MHz ... 80 MHz
  • Comments
    Criterion A
  • Signal
    1 kV (Test Level 2 - asymmetrical)
  • Conducted interference
    EN 61000-4-6
  • Frequency
    900 MHz
  • Field intensity
    20 V/m
  • ECLASS 4.1
    27040700
  • ECLASS 5.0
    27049000
  • ECLASS 6.0
    27049000
  • ECLASS 7.0
    27049002
  • UNSPSC 6.01
    30211502
  • UNSPSC 21.0
    39121004
  • Current consumption
    8.8 A (120 V AC)
  • Power factor (cos phi)
    0.88
  • POWER BOOST (IBoost)
    45 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC )
  • Residual ripple
    < 30 mVPP (with nominal values)
  • Power loss nominal load max.
    80 W
  • Insulation voltage input/output
    4 kV AC (type test)
  • Connection method
    Screw connection
  • Conductor cross section flexible max.
    4 mm²
  • Conductor cross section AWG max.
    10
  • EMC requirements for noise emission
    EN 61000-6-3
  • Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment
    EN 50178
  • UL approvals
    UL Listed UL 508
  • Shipbuilding approval
    DNV GL (EMC A), ABS, LR, RINA, NK, BV
  • Electromagnetic HF field
    EN 61000-4-3
  • Input
    2 kV (Test Level 3 - symmetrical)
  • Voltage
    10 V (Test Level 3)
  • Criterion A
    Normal operating behavior within the specified limits.
  • ECLASS 11.0
    27040701
  • ECLASS 4.0
    27040700
  • ETIM 2.0
    EC001039
  • UNSPSC 7.0901
    39121004
  • UNSPSC 19.0
    39121004
  • CSA
    CSA-C22.2 No. 107.1-01
  • Discharge in air
    15 kV (Test Level 4)
  • Fast transients (burst)
    EN 61000-4-4
  • Surge voltage load (surge)
    EN 61000-4-5
  • I/O/S
    asymmetrical
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 9.0
    27040701
  • ETIM 7.0
    EC002540
  • UNSPSC 11
    39121004
  • UNSPSC 20.0
    39121004
  • Contact discharge
    8 kV (Test Level 4)
  • Output
    1 kV (Test Level 2 - symmetrical)
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • ECLASS 10.0.1
    27040701
  • ETIM 3.0
    EC001039
  • ETIM 6.0
    EC002540
  • UNSPSC 13.2
    39121004

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

This item can ship within 3 days!

1-year warranty

$531.45

2866789

Stock:

10

Select Qty:

$531.45

$531.45 each

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo