Nikki Gonzales
Nick Goetz
Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

2865340 Phoenix Contact Electrical Measuring & Monitoring Instruments

Phoenix Contact 2865340 Ex i repeater power supply and input signal conditioner, HART. Transmits supplied or active 0/4 - 20 mA signals from the hazardous area to a load (active or passive) in the safe area. 3-way electrical isolation; SIL 2 according to IEC 61508, with screw co
Phoenix Contact

Part#:2865340

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 13

04/18/2024

About the product: Ex i repeater power supply and input signal conditioner, HART. Transmits supplied or active 0/4 - 20 mA signals from the hazardous area to a load (active or passive) in the safe area. 3-way electrical isolation; SIL 2 according to IEC 61508, with screw co

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2865340 Phoenix Contact price in the box on the right side or send a quick quote.

2865340 Product Details

  • Transmitter supply voltage
    > 16 V (20 mA)
  • Voltage drop
    < 3.5 V (in input isolating amplifier operation)
  • Nominal supply voltage
    24 V DC
  • Conductor cross section AWG
    24 ... 14
  • Maximum transmission error
    < 0.1 % (of final value)
  • Temperature coefficient, typical
    < 0.004 %/K
  • Overvoltage category
    II
  • Polarization and surge protection
    Yes
  • Current output signal
    0 mA ... 20 mA (active)
  • λDU
    5 x 10-8 (50 FIT)
  • Diagnostic coverage (DC)
    DCS=0 %, DCD=0 %
  • Max. output voltage Uo
    25.2 V
  • Max. external capacitance Co
    820 nF
  • Utilization restriction
    EMC: class A product, see manufacturer's declaration in the download area
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • No. of channels
    1
  • Step response (10-90%)
    < 200 µs (for jump 4 mA ... 20 mA, load 600 Ω)
  • Interference emission
    EN 61000-6-4
  • Test voltage
    2.5 kV AC (50 Hz, 1 min.)
  • Integrity requirement
    IEC 61508 - High demand
  • Input voltage Ui
    ≤ 30 V
  • Standards/regulations
    GB 3626.20
  • UL, USA/Canada
    UL 61010 Listed
  • DNV GL-Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • Humidity
    B
  • Height
    112.5 mm
  • Maximum altitude
    ≤ 2000 m
  • Noise immunity
    EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
  • Underload/overload signal range
    0 mA ... 24 mA (Extended transmission range for diagnostics)
  • Transmission Behavior
    1:1 to input signal
  • Output ripple
    < 20 mVrms
  • Load/output load current output
    < 1000 Ω (20 mA)
  • Torque
    0.5 Nm ... 0.6 Nm
  • Transmission error, typical
    < 0.05 % (of final value)
  • Degree of pollution
    2
  • Power consumption
    < 1.8 W (20 mA / 1000 Ω)
  • Connection name
    Test socket
  • Current input signal
    0 mA ... 20 mA
  • Width
    12.5 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 80 °C
  • Depth
    114.5 mm
  • Permissible humidity (operation)
    10 % ... 95 % (non-condensing)
  • Supply voltage range
    19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
  • Power dissipation
    < 0.75 W (24 V DC / 20 mA / 1000 Ω)
  • Connection method
    Screw connection
  • Nominal supply voltage range
    19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
  • Stripping length
    7 mm
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm²
  • Max. diameter
    2 mm
  • Electromagnetic compatibility
    Conformance with EMC directive
  • Color
    gray
  • Protocols supported
    HART
  • Safety Integrity Level (SIL)
    2
  • Signal output
    Current output (active and passive)
  • Designation
    INMETRO
  • Maximum temperature coefficient
    < 0.01 %/K
  • Electrical isolation
    375 V (Peak value in accordance with IEC/EN 60079-11)
  • Equipment type
    Type A
  • λSD
    0
  • Operation
    Signal conditioner operation
  • Group
    IIC
  • Input current Ii
    ≤ 150 mA
  • Max. internal capacitance Ci
    negligible
  • Noise emission
    EN 61000-6-4
  • DNV GL-Vibration
    A
  • Identification
    [Ex ia Ga] IIC/IIB
  • EMC
    A
  • Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • ECLASS 4.1
    27210100
  • ECLASS 6.0
    27210100
  • ECLASS 7.0
    27210120
  • ETIM 6.0
    EC002653
  • UNSPSC 13.2
    39121008
  • UNSPSC 20.0
    39121008
  • Degree of protection
    IP20 (not assessed by UL)
  • Max. current consumption
    < 44 mA (24 V DC / 20 mA / 1000 Ω)
  • Screw thread
    M3
  • Status display
    Green LED (supply voltage)
  • HART function
    Yes
  • Safe Failure Fraction (SFF)
    90.7 %
  • Probability of a hazardous failure per hour (PFHD)
    4,99 x 10-8
  • Additional text
    and EN 61326
  • Max. internal inductance Li
    negligible
  • DNV GL-Temperature
    B
  • DNV GL-EMC
    A
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 10.0.1
    27210120
  • ECLASS 5.0
    27210100
  • ETIM 4.0
    EC002653
  • UNSPSC 6.01
    30211506
  • UNSPSC 21.0
    39121008
  • Ambient temperature (operation)
    -20 °C ... 60 °C (Any mounting position)
  • Signal input
    Passive current input, intrinsically safe
  • Output behavior in the event of an error
    0 mA (Cable break in the input)
  • Housing material
    PA 6.6-FR
  • Rated insulation voltage
    300 Vrms
  • Insulation
    Safe isolation in accordance with IEC/EN 61010-1
  • λDD
    0
  • Max. output power Po
    587 mW
  • Safety-related maximum voltage Um
    253 V AC (125 V DC)
  • ATEX
     II (1) G [Ex ia Ga] IIC
  • DNV GL-Humidity
    B
  • Temperature
    B
  • Vibration
    A
  • ECLASS 11.0
    27210120
  • ECLASS 5.1
    27210100
  • ETIM 7.0
    EC002653
  • UNSPSC 11
    39121008
  • UNSPSC 18.0
    39121008
  • λSU
    4.867 x 10-7 (486.7 FIT)
  • Probability of a hazardous failure on demand (PFDAVG)
    2.40 x 10-4 (1 year)
  • Max. output current Io
    93 mA
  • Max. external inductivity Lo
    4 mH
  • Typical deviation from the measuring range final value
    1 %
  • Conformance
    CE-compliant, additionally EN 61326
  • IECEx
    [Ex ia Ga] IIC
  • Certificate
    DNV 18.0136 X
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 4.0
    27210100
  • ECLASS 9.0
    27210120
  • UNSPSC 7.0901
    39121008
  • UNSPSC 12.01
    39121008
  • UNSPSC 19.0
    39121008

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

This item can ship within 3 days!

1-year warranty

$270.26

2865340

Stock:

13

Select Qty:

$270.26

$270.26 each

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo