Nikki Gonzales
Nick Goetz
Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

2320908 Phoenix Contact AC/DC Power Supplies

Phoenix Contact 2320908 Primary-switched QUINT POWER power supply for DIN rail mounting with SFB (Selective Fuse Breaking) Technology, with protective coating, input: 1-phase, output: 24 V DC/5 A
Phoenix Contact

Part#:2320908

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 27

04/19/2024

About the product: Primary-switched QUINT POWER power supply for DIN rail mounting with SFB (Selective Fuse Breaking) Technology, with protective coating, input: 1-phase, output: 24 V DC/5 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2320908 Phoenix Contact price in the box on the right side or send a quick quote.

2320908 Product Details

  • Height with alternative assembly
    130 mm
  • Degree of pollution
    2
  • Frequency range DC
    0 Hz
  • Input voltage range
    85 V AC ... 264 V AC
  • Current consumption
    1.2 A (120 V AC)
  • Protective circuit/component
    Varistor
  • POWER BOOST (IBoost)
    7.5 A (-25°C ... 40°C permanent, UOUT = 24 V DC )
  • Feedback voltage resistance
    max. 35 V DC
  • Residual ripple
    < 40 mVPP (with nominal values)
  • Insulation voltage input / PE
    3.5 kV AC (type test)
  • Mounting position
    horizontal DIN rail NS 35, EN 60715
  • Degree of protection
    IP20
  • Discharge current to PE
    < 3.5 mA
  • Inrush current
    < 15 A
  • Input fuse
    5 A (slow-blow, internal)
  • Nominal output current (IN)
    5 A (-25 °C ... 60 °C, UOUT = 24 V DC)
  • Control deviation
    < 1 % (change in load, static 10 % ... 90 %)
  • Power loss nominal load max.
    15 W
  • Efficiency
    > 90 % (for 230 V AC and nominal values)
  • Net weight
    0.7 kg
  • Assembly instructions
    alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
  • Nominal input voltage range
    100 V AC ... 240 V AC
  • AC frequency range
    45 Hz ... 65 Hz
  • Nominal power consumption
    141 VA
  • Type of protection
    Transient surge protection
  • Nominal output voltage
    24 V DC ±1 %
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • Connection in series
    yes
  • Output power
    120 W
  • Maximum power dissipation in no-load condition
    3 W
  • MTBF (IEC 61709, SN 29500)
    > 1134000 h (25 °C)
  • Insulation voltage output / PE
    500 V DC (routine test)
  • Connection method
    Pluggable screw connection
  • Screw thread
    M3
  • Conductor cross section AWG min.
    20
  • Contact discharge
    4 kV (Test Level 2)
  • Frequency range
    0.15 MHz ... 80 MHz
  • Comments
    Criterion B
  • Vibration (operation)
    < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
  • Certificate
    IEC 60950-1 (2nd Edition)
  • Rail applications
    EN 50121-4
  • IECEx
    Ex nA nC IIC T4 Gc
  • ECLASS 5.1
    27049000
  • ECLASS 7.0
    27049002
  • ECLASS 9.0
    27040701
  • ETIM 6.0
    EC002540
  • UNSPSC 11
    39121004
  • UNSPSC 13.2
    39121004
  • Dielectric strength maximum
    300 V AC
  • Recommended breaker for input protection
    6 A ... 16 A (AC: Characteristics B, C, D, K)
  • Mains buffering time
    typ. 55 ms (120 V AC)
  • Setting range of the output voltage (USet)
    18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
  • Typical response time
    < 0.15 s
  • Insulation voltage input/output
    4 kV AC (type test)
  • Protection class
    I
  • Conductor cross section solid max.
    2.5 mm²
  • Conductor cross section flexible min.
    0.2 mm²
  • Stripping length
    7 mm
  • Noise immunity
    EN 61000-6-2:2005
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Standards/regulations
    EN 61000-6-3
  • Low Voltage Directive
    Conformance with LV directive 2006/95/EC
  • Standard - Equipment safety
    BG (design tested)
  • Shock
    18 ms, 30g, in each space direction (according to IEC 60068-2-27)
  • DeviceNet approval
    DeviceNet™ Power Supply Conformance Tested
  • ATEX
     II 3 G Ex nA nC IIC T4 Gc
  • China RoHS
    Environmentally Friendly Use Period = 25;
  • ECLASS 6.0
    27049000
  • ECLASS 5.0
    27049000
  • ETIM 4.0
    EC000599
  • ETIM 7.0
    EC002540
  • ETIM 5.0
    EC002540
  • UNSPSC 12.01
    39121004
  • Conductor cross section solid min.
    0.2 mm²
  • Conductor cross section flexible max.
    2.5 mm²
  • Conductor cross section AWG max.
    12
  • Noise emission
    EN 55011 (EN 55022)
  • Connection in acc. with standard
    CSA
  • Test field strength
    3 V/m (Test Level 2)
  • Shipbuilding approval
    DNV GL (EMC A)
  • Standard – Limitation of mains harmonic currents
    EN 61000-3-2
  • UL approvals
    UL/C-UL listed UL 508
  • Approval - requirement of the semiconductor industry with regard to mains voltage dips
    SEMI F47-0706 Compliance Certificate
  • Noxious gas test
    ISA-S71.04-1985 G3 Harsh Group A
  • Overvoltage category (EN 62477-1)
    III
  • ECLASS 4.0
    27040700
  • ECLASS 4.1
    27040700
  • ECLASS 8.0
    27049002
  • UNSPSC 6.01
    30211502
  • UNSPSC 7.0901
    39121004
  • Width with alternative assembly
    122 mm
  • Depth
    125 mm
  • Installation height
    5000 m
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Selective Fuse Breaking (ISFB)
    30 A (12 ms)
  • Protection against overvoltage at the output (OVP)
    < 32 V DC
  • Voltage
    10 V (Test Level 3)
  • Standard - Electrical safety
    IEC 60950-1/VDE 0805 (SELV)
  • Max. permissible relative humidity (operation)
    100 % (at 25 °C, non-condensing)
  • Derating
    60 °C ... 70 °C (2.5%/K)
  • Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
    EN 50178/VDE 0160 (PELV)
  • Width
    40 mm
  • Climatic class
    3K3 (in acc. with EN 60721)
  • Standard – Safety extra-low voltage
    IEC 60950-1 (SELV) and EN 60204-1 (PELV)
  • Height
    130 mm
  • Depth with alternative assembly
    43 mm
  • Ambient temperature (operation)
    -40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Standard - Safe isolation
    DIN VDE 0100-410

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

This item can ship within 3 days!

1-year warranty

$340.49

2320908

Stock:

27

Select Qty:

$340.49

$340.49 each

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo