Phoenix Contact 1087082 Axioline P EX, Analog output module, Analog outputs: 4 (HART), 0 mA ... 20 mA, 4 mA ... 20 mA, connection method: 2-conductor, transmission speed in the local bus: 100 Mbps, HART functionality, degree of protection: IP20, including bus base module and con
Phoenix Contact

Part#:1087082

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 58

Apr 24, 2024

About the product: Axioline P EX, Analog output module, Analog outputs: 4 (HART), 0 mA ... 20 mA, 4 mA ... 20 mA, connection method: 2-conductor, transmission speed in the local bus: 100 Mbps, HART functionality, degree of protection: IP20, including bus base module and con

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Programmable Logic Controllers that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 1087082 Phoenix Contact price in the box on the right side or send a quick quote.

1087082 Product Details

  • Depth
    77.14 mm
  • Connection method
    Connection for bus base module
  • Conductor cross section flexible min.
    0.2 mm²
  • Note on weight specifications
    with connectors and bus base module
  • Supply voltage
    5 V DC (via bus base module)
  • Utilization restriction
    Use in potentially explosive areas is not permitted in China.
  • Permissible humidity (operation)
    5 % ... 95 % (non-condensing)
  • Conductor cross section solid min.
    0.2 mm²
  • Conductor cross section AWG max.
    16
  • Maximum altitude
    2000 m
  • Immunity to surge
    Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion A, supply lines DC: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), ±1 kV to shielded I/O cables
  • ATEX
    DEMKO 20 ATEX 2370XII 3(1)G Ex ec [ia Ga] IIC T4 GcII (1)D [Ex ia Da] IIIC
  • Protection class
    III (IEC 61140, EN 61140, VDE 0140-1)
  • ECLASS 9.0
    27242601
  • Note on dimensions
    The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).
  • Air pressure (operation)
    70 kPa ... 106 kPa (up to 2000 m above sea level)
  • Designation
    Supply of the Axioline P local bus UBus
  • Conductor cross section flexible max.
    1.5 mm²
  • Mounting type
    DIN rail
  • Supply voltage range
    19.2 V DC ... 30 V DC (via bus base module (UL) at AXL P BK...)
  • Height
    126.1 mm
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Air pressure (storage/transport)
    70 kPa ... 106 kPa (up to 2000 m above sea level)
  • Conductor cross section solid max.
    1.5 mm²
  • Color
    traffic grey A RAL 7042
  • Degree of pollution
    2
  • Current consumption
    max. 135 mA
  • Interference emission
    Noise emission test as per EN 61000-6-4 Class A
  • China RoHS
    Environmentally Friendly Use Period = 25;
  • Width
    53.6 mm
  • Ambient temperature (operation)
    -40 °C ... 70 °C (Standard)
  • Permissible humidity (storage/transport)
    5 % ... 95 % (non-condensing)
  • Degree of protection
    IP20
  • Note on the connection method
    Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
  • Conductor cross section AWG min.
    24
  • Stripping length
    8 mm
  • Net weight
    0 g
  • Transmission speed
    100 Mbps
  • Immunity to EF
    Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
  • Immunity to burst
    Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV
  • UL, USA/Canada
    Ind. Cont. Eq. (E238705) also ListedInd. Cont. Eq. for haz. loc. E196811Install in: Class I, Div. 2, Groups A, B, C, D T4Intrinsically safe outputs for: Class I, Groups A, B, C, D; Class II, Groups E, F, G; Class III; [Ex ia] Haz locClass I, Zone 2, AEx e
  • ECLASS 11.0
    27242601
  • Test section
    5 V supply of the local bus (UBus) / functional ground 500 V AC 62 Hz 1 min.
  • Immunity to conducted interference
    Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
  • IECEx
    IECEx UL 20.0044XEx ec [ia Ga] IIC T4 Gc[Ex ia Da] IIIC
  • Group
    A, B / IIC
  • Overvoltage category
    II
  • ECLASS 10.0.1
    27242601

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

This item can ship within 24h!

1-year warranty

$718.56

1087082

Stock:

58

Select Qty:

$718.56

$718.56 each

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo