X20AT6402 B&R Electronic Components
Part#:X20AT6402
Manufacturer:B&R
Product Lifecycle:Active
In-stock parts: 8
May 2, 2024
About the product: X20 temperature input module, 6 thermocouple inputs, type J, K, N, S, B, R, resolution 0.1°C
Check out the X20AT6402 B&R price in the box on the right side or send a quick quote.
X20AT6402 Product Details
- Max. error at 25°C Offset Type R: PtRh13-Pt 0.09%
- Temperature Operation Vertical mounting orientation 0 to 50°C
- Temperature Operation Horizontal mounting orientation 0 to 55°C
- Max. error at 25°C Offset Type B: PtRh30-PtRh6 0.13%
- Max. error at 25°C Offset Type S: PtRh10-Pt 0.11%
- Max. error at 25°C Offset Type N (Rev. ≥D0) 0.05%
- Max. error at 25°C Offset Type K: NiCr-Ni 0.05%
- Measurement range Sensor temperature Type R: PtRh13-Pt -50 to 1664°C
- Measurement range Sensor temperature Type S: PtRh10-Pt -50 to 1768°C
- Measurement range Sensor temperature Type B: PtRh30-PtRh6 0 to 1820°C
- Max. error at 25°C Offset Type T: Cu-CuNi 0.04%
- Measurement range Sensor temperature Type N: NiCrSi-NiSi -270 to 1300°C (Rev. ≥D0)
- Measurement range Sensor temperature Type K: NiCr-Ni -270 to 1372°C
- Measurement range Sensor temperature Type J: Fe-CuNi -210 to 1200°C
- Relative humidity Transport 5 to 95%, non-condensing
- Relative humidity Storage 5 to 95%, non-condensing
- Relative humidity Operation 5 to 95%, non-condensing
- Temperature Transport -40 to 85°C
- Temperature Storage -40 to 85°C
- Installation elevation above sea level 0 to 2000 m No limitation
- Temperature Derating -
- Installation elevation above sea level >2000 m Reduction of ambient temperature by 0.5°C per 100 m
- Mounting orientation Vertical Yes
- Terminal temperature compensation precision With natural convection ±2°C after 10 min
- Mounting orientation Horizontal Yes
- Terminal temperature compensation precision With artificial convection ±4°C after 10 min
- Insulation voltage Between channel and bus 500 Veff
- Common-mode rejection 50 Hz >70 dB
- Common-mode rejection DC >70 dB
- Max. offset drift Type R: PtRh13-Pt 0.0074 %/°C
- Max. offset drift Type B: PtRh30-PtRh6 0.0114 %/°C
- Max. offset drift Type N (Rev. ≥D0) 0.0029 %/°C
- Max. offset drift Type S: PtRh10-Pt 0.0079 %/°C
- Max. offset drift Type K: NiCr-Ni 0.0024% / °C
- Monitoring General fault 0x8000
- Max. offset drift Type J: Fe-CuNi 0.0019 %/°C
- Max. error at 25°C Gain 0.06%
- Monitoring Open inputs 0x7FFF
- Monitoring Range overshoot 0x7FFF
- Monitoring Open circuit 0x7FFF
- Monitoring Range undershoot 0x8001
- Normalization Type B: PtRh30-PtRh6 0 to 1820.0°C
- Normalization Type R: PtRh13-Pt -50.0 to 1664.0°C
- Normalization Type S: PtRh10-Pt -50.0 to 1768.0°C
- Normalization Terminal temperature -25.0 to 85.0°C
- Normalization Type K: NiCr-Ni -270.0 to 1372.0°C
- Normalization Type N (Rev. ≥D0) -270.0 to 1300.0°C
- Normalization Type J: Fe-CuNi -210.0 to 1200.0°C
- Conversion time 1 channel 80.4 ms with 50 Hz filter
- Resolution Raw value output with respect to gain 1 LSB = 1 µV or 2 µV
- Resolution Sensor temperature 1 LSB = 0.1°C
- Measurement range Raw value ±65.534 mV
- Resolution Terminal temperature 1 LSB = 0.1°C
- Conversion time N channels (n + 1) x 40.2 ms with 50 Hz filter
- Measurement range Terminal temperature -25 to 85°C
- Certifications EAC Yes
- Certifications KC Yes
- Certifications ABS Yes
- Certifications KR Yes
- Certifications LR ENV1
- Certifications DNV Temperature: B (0 - 55°C); Humidity: B (up to 100%); Vibration: B (4 g); EMC: B (bridge and open deck)
- Certifications ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X
- Certifications UL cULus E115267; Industrial control equipment
- Certifications HazLoc cCSAus 244665; Process control equipment; for hazardous locations; Class I, Division 2, Groups ABCD, T5
- Certifications UKCA Yes
- Certifications CE Yes
- Power consumption Internal I/O 0.91 W
- Power consumption Bus 0.01 W
- Diagnostics Inputs Yes, using LED status indicator and software
- Pitch 12.5+0.2 mm
- Diagnostics Module run/error Yes, using LED status indicator and software
- Note Order 1x terminal block X20TB12 separately.; Order 1x bus module X20BM11 separately.
- Degree of protection per EN 60529 IP20
- Electrical isolation Channel isolated from bus; Channel not isolated from channel
- Nonlinearity ±0.001%
- Common-mode range ±15 V
- Max. gain drift 0.01%/°C
- Permissible input signal Max. ±5 V
- Crosstalk between channels <-70 dB
- Input filter First-order low-pass filter / cutoff frequency 500 Hz
- Linearization method Internal
- Conversion procedure Sigma-delta
- Terminal temperature compensation Internal
- Sensor standard EN 60584
- Output format INT
- Input Thermocouple
- Filter time Configurable between 1 ms and 66.7 ms
- Status indicators I/O function per channel, operating state, module status
- Digital converter resolution 16-bit
- B&R ID code 0x1BA9
- I/O module 6 inputs for thermocouples
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.
Related documents X20AT6402 Specs
This item can ship within 3 days!
1-year warranty
$1,344.42
X20AT6402
Stock:
8
Select Qty:
$1,344.42
$1,344.42 each
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Relevant products
Do you have questions?
We’re here for you ✨