3049013 Phoenix Contact Terminal Blocks

Phoenix Contact 3049013 Bolt connection terminal block, Note: the BE-RT... path extension is to be used for non-insulated cable lugs (see accessories)., nom. voltage: 1000 V, nominal current: 24 A, connection method: Bolt connection, number of connections: 2, width: 12.3 mm, col
Phoenix Contact

Part#:3049013

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 26387

May 4, 2024

About the product: Bolt connection terminal block, Note: the BE-RT... path extension is to be used for non-insulated cable lugs (see accessories)., nom. voltage: 1000 V, nominal current: 24 A, connection method: Bolt connection, number of connections: 2, width: 12.3 mm, col

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 3049013 Phoenix Contact price in the box on the right side or send a quick quote.

3049013 Product Details

  • Tightening torque max
    0.8 Nm
  • ECLASS 4.1
    27141100
  • ETIM 3.0
    EC000897
  • ETIM 7.0
    EC000897
  • ECLASS 6.0
    27141100
  • UNSPSC 19.0
    39121410
  • UNSPSC 18.0
    39121410
  • UNSPSC 11
    39121410
  • UNSPSC 21.0
    39121410
  • ECLASS 4.0
    27141100
  • China RoHS
    Environmentally friendly use period: unlimited = EFUP-e
  • Bolt diameter
    3 mm
  • ECLASS 5.1
    27141100
  • Nominal voltage UN
    1000 V (Rated voltage for open disconnect point 500 V)
  • Back of the hand protection
    guaranteed
  • Result of the test for mechanical stability of terminal points (5 x conductor connection)
    Test passed
  • Setpoint
    1 N
  • Potentials
    1
  • Flammability rating according to UL 94
    V0
  • Maximum power dissipation for nominal condition
    0.77 W
  • Smoke gas toxicity NFPA 130 (SMP 800C)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R26
    HL 1 - HL 3
  • Length
    66 mm
  • Note
    Note: the BE-RT... path extension is to be used for non-insulated cable lugs (see accessories).
  • Insulating material
    PA
  • Insulating material group
    I
  • Shock protection test specification
    DIN EN 50274 (VDE 0660-514):2002-11
  • Note regarding shock protection
    Electric shock protection only with insulated cable lug and closed wing flap guaranteed.
  • Result of voltage-drop test
    Test passed
  • Tight fit on carrier
    NS 35
  • Short-time current
    0.3 kA
  • Test frequency
    f1 = 5 Hz to f2 = 150 Hz
  • Test directions
    X-, Y- and Z-axis (pos. and neg.)
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
    130 °C
  • End cover width
    2.2 mm
  • Number of connections
    2
  • Color
    gray
  • Rated surge voltage
    8 kV
  • Maximum load current
    24 A (with a 2.5 mm² conductor cross section)
  • Finger protection
    guaranteed
  • Power frequency withstand voltage setpoint
    2.2 kV
  • Short circuit stability result
    Test passed
  • Test specification, oscillation, broadband noise
    DIN EN 50155 (VDE 0115-200):2008-03
  • Result of thermal test
    Test passed
  • Shock test result
    Test passed
  • Test duration per axis
    5 h
  • Number of levels
    1
  • Area of application
    Railway industry
  • Overvoltage category
    III
  • Nominal current IN
    24 A
  • Result of surge voltage test
    Test passed
  • Result of tight fit on support
    Test passed
  • Conductor cross section short circuit testing
    2.5 mm²
  • Test spectrum
    Service life test category 1, class B, body mounted
  • Proof of thermal characteristics (needle flame) effective duration
    30 s
  • Acceleration
    5g
  • Shock duration
    30 ms
  • Surface flammability NFPA 130 (ASTM E 162)
    passed
  • Nominal cross section
    2.5 mm²
  • Degree of pollution
    3
  • Open side panel
    Yes
  • Result of power-frequency withstand voltage test
    Test passed
  • Result of temperature-rise test
    Test passed
  • Shock form
    Half-sine
  • UNSPSC 13.2
    39121410
  • Number of shocks per direction
    3
  • Test specification, shock test
    DIN EN 50155 (VDE 0115-200):2008-03
  • Calorimetric heat release NFPA 130 (ASTM E 1354)
    28 MJ/kg
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 3
  • Stripping length
    The stripping length depends on the specification provided by the cable lug manufacturer.
  • Height NS 35/15
    58.5 mm
  • AWG min
    18
  • Oscillation, broadband noise test result
    Test passed
  • Height NS 35/7,5
    51 mm
  • Connection method
    Bolt connection
  • Max. cross section for cable lug connection
    2.5 mm²
  • Hole diameter, min.
    3.2 mm
  • ECLASS 7.0
    27141120
  • ASD level
    1.857 (m/s2)2/Hz
  • Relative insulation material temperature index (Elec., UL 746 B)
    130 °C
  • Specific optical density of smoke NFPA 130 (ASTM E 662)
    passed
  • Screw thread
    M3
  • Ambient temperature (actuation)
    -5 °C ... 70 °C
  • Ambient temperature (storage/transport)
    -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
  • ECLASS 10.0.1
    27141120
  • ETIM 2.0
    EC000897
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 11.0
    27141120
  • ECLASS 9.0
    27141120
  • ETIM 6.0
    EC000897
  • UNSPSC 7.0901
    39121410
  • UNSPSC 20.0
    39121410
  • Requirement temperature-rise test
    Increase in temperature ≤ 45 K
  • Static insulating material application in cold
    -60 °C
  • Width
    12.3 mm
  • Min. cross section for cable lug connection
    1 mm²
  • Connection in acc. with standard
    CUL
  • AWG max
    14
  • Tightening torque, min
    0.6 Nm
  • Ambient temperature (assembly)
    -5 °C ... 70 °C
  • Cable lug width, max.
    6 mm
  • Operating temperature
    -60 °C ... 105 °C (max. short-term operating temperature 130°C)
  • Permissible humidity (storage/transport)
    30 % ... 70 %
  • ECLASS 5.0
    27141100
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 3
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 3
  • Connection
    1 level
  • Cable lug connection according to standard
    DIN 46237:1970-07
  • ETIM 4.0
    EC000897
  • UNSPSC 6.01
    30211811
  • UNSPSC 12.01
    39121410

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

This item can ship within 24h!

1-year warranty

$4.04

3049013

Stock:

26387

Select Qty:

$4.04

$4.04 each

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty