2910325 Phoenix Contact Electrical Measuring & Monitoring Instruments

Phoenix Contact 2910325 Set consisting of a 1 A measuring transducer and a Rogowski coil with signal line. Length of Rogowski coil: 300 mm, diameter: 95 mm. Length of signal line: 5 m. The Rogowski coil measures the AC current of busbars and power lines.
Phoenix Contact

Part#:2910325

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

Set consisting of a 1 A measuring transducer and a Rogowski coil with signal line. Length of Rogowski coil: 300 mm, diameter: 95 mm. Length of signal line: 5 m. The Rogowski coil measures the AC current of busbars and power lines.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2910325 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Depth
    70.4 mm
  • Measuring coil degree of protection
    IP67 (not assessed by UL)
  • Max. current consumption
    190 mA
  • Frequency measuring range
    40 Hz ... 20000 Hz
  • Output signal (at 50 Hz)
    100 mV (no load, at 1,000 A)
  • Load
    0 Ω ... 1.5 Ω
  • Housing material
    Polyamide
  • Insulation
    double insulation
  • Ambient temperature (operation)
    -30 °C ... 80 °C (Measuring coil)
  • Permissible humidity (operation)
    5 % ... 95 % (non-condensing)
  • Power consumption
    4 W
  • Phase angle
    < 1 °
  • Configurable/programmable
    Via DIP switches
  • Output voltage (sinusoidal, in no-load operation)
    100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A))
  • Output voltage (in no-load operation)
    VOUT = M * dI/dt
  • Rated insulation voltage
    1000 V AC (rms CAT III)
  • Current consumption
    < 190 mA (at 19.2 V)
  • Stripping length
    7 mm
  • Torque
    0.5 Nm ... 0.6 Nm
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 11.0
    27210902
  • ECLASS 6.0
    27210900
  • ETIM 6.0
    EC002048
  • Width
    22.5 mm
  • Measuring transducer degree of protection
    IP20
  • Position error
    <± 1 % (typical)
  • Rated power
    1.5 VA
  • Current output signal
    0 A AC ... 1 A
  • Conductor structure signal line
    2x 0.22 mm (Signal (tinned))
  • Basic accuracy
    <± 0.2 %
  • Maximum transmission error
    ≤ 0.5 % (From the range end value)
  • Connection name
    Measuring transducer side
  • Connection method
    Screw connection
  • Conductor cross section AWG
    24 ... 14
  • ECLASS 4.1
    27210900
  • ECLASS 9.0
    27210902
  • Ambient temperature (storage/transport)
    -40 °C ... 80 °C (Measuring coil)
  • Nominal supply voltage
    24 V DC -20 % ... +25 %
  • Linearity error
    < 0.5 % (From the range end value)
  • Max. distances for copper cables at PN max
    32 m (0.75 mm² (AWG 20))
  • Length of signal cable
    5000 mm
  • Coil material
    Elastollan
  • Test voltage
    1.5 kV AC (Supply/input and output: 50 Hz, 1 min)
  • Max. detectable harmonics
    < 2 kHz
  • Standards/regulations
    IEC 61010-1
  • Conductor cross section solid
    0.2 mm² ... 2.5 mm²
  • ECLASS 10.0.1
    27210902
  • ECLASS 5.0
    27210900
  • ECLASS 7.0
    27210902
  • Height
    85 mm
  • Maximum altitude
    < 2000 m
  • Nominal supply voltage range
    19.2 V DC ... 30 V DC
  • Measuring ranges (current)
    100 A 250 A 400 A 630 A 1000 A 1500 A 2000 A 4000 A
  • Input signal (at 50 Hz)
    100 mV (1000 A)
  • Input impedance
    27 kΩ (smallest measuring range)
  • Length of measuring coil
    300 mm
  • Diameter of measuring coil
    8.3 mm ±0.2 mm
  • UL, USA/Canada
    UL 508 Listed
  • Typical measuring error
    < 1 %
  • Screw thread
    M3
  • Overvoltage category
    III (1000 V, to neutral conductor)
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 5.1
    27210900
  • ETIM 7.0
    EC002048
  • Frequency range
    45 Hz ... 65 Hz
  • Temperature coefficients
    0.005 %/K (+10 °C ... +70 °C, both components have the same ambient temperature)
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Pollution degree
    2
  • ECLASS 4.0
    27210900

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo