2910128 Phoenix Contact DC/DC Converters
Part#:2910128
Manufacturer:Phoenix Contact
Product Lifecycle:Active
Get a quick Quote!
Primary-switched DC/DC converter, QUINT POWER, DIN rail mounting, SFB Technology (Selective Fuse Breaking), Push-in connection, input: 48 V DC , output: 48 V DC / 5 A
About the manufacturer: Phoenix Contact is one of the manufacturers that offers DC/DC Converters that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2910128 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Weight0.8 kg
- Comments Criterion A
- Electrostatic discharge EN 61000-4-2
- Electric strength, max. 35 V DC (60 s)
- Inrush current limitation typical 2.3 A
- Input fuse 20 A (slow-blow, internal)
- Type test (IEC/EN 60950-1) D 0.5 kV DC
- Production test D 0.5 kV DC
- Mains buffering typ. 17 ms (48 V DC)
- Inrush current integral (I2t) < 0.1 A2s
- Type test (IEC/EN 60950-1) B 4 kV DC
- Production test C 0.5 kV DC
- Conductor cross section solid 0.2 mm² ... 1 mm²
- Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) 0.2 mm² ... 1.5 mm²
- Nominal output voltage (UN) 48 V DC
- Dynamic Boost (IDyn.Boost) 10 A (5 s)
- System deviation, static < 3 % (change in load, static 10 % ... 90 %)
- Connection in parallel Yes, for redundancy and increased capacity
- Types of signaling LED
- Analog 4 mA ... 20 mA ±5 % (Load ≤400 Ω)
- Output current 5 A
- Auxiliary converter stage 190 kHz ... 220 kHz (Auxiliary converter stage)
- Hood version Stainless steel X6Cr17
- Height with alternative assembly 130 mm
- Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
- Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
- Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
- Identification CB scheme (IEC 61010-1, IEC 61010-2-201)
- Noise emission EN 55016
- Discharge in air 15 kV (Test Level 4)
- Power frequency magnetic field EN 61000-4-8
- Pulse-shape magnetic field EN 61000-4-9
- Test level 2 150 Hz 1.5 kHz (Test Level 3)
- Alternating component of DC voltage EN 61000-4-17
- Criterion A Normal operating behavior within the specified limits.
- ECLASS 9.0 27210901
- Switch-on time < 1 s
- Static Boost (IStat.Boost) 6.25 A
- System deviation, input voltage change < 0.3 % (change in input voltage ±10 %)
- Connection in series yes
- UIn > 0.8 x UInNom (LED off)
- Digital 0 V DC
- Function Signal ground
- Voltage 1 kV
- Degree of protection IP20
- Depth 125 mm
- Efficiency typ. 95.2 % (48 V DC)
- Power dissipation SLEEP MODE < 2 W
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- EMC requirements for noise immunity EN 61000-6-1
- Designation SIQ
- DNV GL conducted interference Class B
- Electromagnetic HF field EN 61000-4-3
- Fast transients (burst) EN 61000-4-4
- Signal 2 kV (Test Level 3 - asymmetrical)
- Test level 1 15 Hz 150 Hz (Test Level 3)
- Asymmetrical conducted disturbance variables EN 61000-4-16
- Attenuated oscillating wave EN 61000-4-18
- Input, output (test level 1) 100 kHz 1 MHz (Test Level 2 - symmetrical)
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- Typical current consumption 6.8 A (48 V DC)
- Insulation voltage input/output 4 kV DC (type test)
- Production test A 2 kV DC
- Stripping length 8 mm
- Flexible conductor cross section (ferrule with plastic sleeve) 0.2 mm² ... 0.75 mm²
- Conductor cross section AWG 24 ... 16
- Magnetic circuit breaker tripping A1 ... A6 / B2 / C1 ... C2 / Z1 ... Z6
- Short-circuit-proof yes
- Protection against overvoltage at the output (OVP) ≤ 60 V DC
- Connection labeling 3.4 +
- Maximum contact load 24 V DC
- MTBF (IEC 61709, SN 29500) > 1476000 h (25 °C)
- Main converter stage 67 kHz ... 135 kHz (Main converter stage)
- Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
- Ambient temperature (start-up type tested) -40 °C
- Degree of pollution 2
- Overvoltage category EN 61010-1 II
- Standards/regulations EN 61000-4-29
- Conducted noise emission EN 55016
- Additional text Test Level 2
- Test field strength 100 A/m
- Output 1 kV (Test Level 3 - symmetrical)
- I/O/S asymmetrical
- Voltage dips EN 61000-4-29
- Test level 3 1.5 kHz 15 kHz (Test Level 3)
- Test level 4 15 kHz 150 kHz (Test Level 3)
- Signals (test level 1) 100 kHz 1 MHz (Test Level 2 - symmetrical)
- ECLASS 11.0 27210901
- Input voltage range 29 V DC ... 57.6 V DC
- Typical response time 300 ms (from SLEEP MODE)
- Type test (IEC/EN 60950-1) A 2 kV DC
- Type test (IEC/EN 60950-1) C 0.5 kV DC
- Production test B 2 kV DC
- Conductor cross section flexible 0.2 mm² ... 1.5 mm²
- Nominal output current (IN) 5 A
- Selective Fuse Breaking (ISFB) 30 A (15 ms)
- No-load proof yes
- Feedback voltage resistance ≤ 60 V DC
- POut > 100 % (LED lights up yellow, output power > 240 W)
- Signal option Output current
- Switch contact floating
- Time 428200 h
- Side element version Aluminum
- Width 50 mm
- Width with alternative assembly 122 mm
- Maximum power dissipation in no-load condition < 3 W
- Vibration (operation) 5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)
- Climatic class 3K3 (EN 60721)
- Standard designation Mains variation/undervoltage
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- DNV GL noise radiation Class B
- Frequency range 50 Hz ... 60 Hz
- Surge voltage load (surge) EN 61000-4-5
- Frequency 0 Hz
- Damped oscillating magnetic field EN 61000-4-10
- Test level 5 16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
- Input, output (test level 2) 100 kHz 1 MHz (Test Level 2 - asymmetrical)
- Signals (test level 2) 100 kHz 1 MHz (Test Level 2 - asymmetrical)
- ECLASS 10.0.1 27210901
- Connection method Push-in connection
- Setting range of the output voltage (USet) 48 V DC ... 56 V DC (> 48 V constant capacity)
- System deviation, dynamic < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
- Residual ripple < 50 mVPP
- Rise time < 1 s (UOUT (10 % ... 90 %))
- UOut > 0.9 x USet (LED lights up green)
- Default Output power ON (>40 kΩ/24 V DC/open bridge between REM and SGnd)
- Reference potential to OUT1, OUT2, REM
- Temperature 30 °C
- Protection class Special with SELV input and output
- Height 130 mm
- Depth with alternative assembly 53 mm
- Power loss nominal load max. < 13 W
- Maximum altitude ≤ 5000 m (> 2000 m, observe derating)
- Overvoltage category EN 62477-1 III
- EMC requirements, power plant IEC 61850-3
- Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
- Contact discharge 8 kV (Test Level 4)
- Input 1 kV (Test Level 3 - symmetrical)
- Conducted interference EN 61000-4-6
- Voltage dip 0 %
- Test level 6 0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 3)
- Input, output (test level 3) 10 MHz (Test Level 2 - asymmetrical)
- Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨