2910119 Phoenix Contact DC/DC Converters

Phoenix Contact 2910119 Primary-switched DC/DC converter, QUINT POWER, DIN rail mounting, SFB Technology (Selective Fuse Breaking), Push-in connection, input: 24 V DC , output: 24 V DC / 5 A
Phoenix Contact

Part#:2910119

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 30

04/15/2024

About the product: Primary-switched DC/DC converter, QUINT POWER, DIN rail mounting, SFB Technology (Selective Fuse Breaking), Push-in connection, input: 24 V DC , output: 24 V DC / 5 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers DC/DC Converters that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2910119 Phoenix Contact price in the box on the right side or send a quick quote.

2910119 Product Details

  • Output current
    5 A
  • Main converter stage
    50 kHz ... 420 kHz (Main converter stage)
  • Hood version
    Stainless steel X6Cr17
  • Height with alternative assembly
    130 mm
  • Power dissipation SLEEP MODE
    < 1 W
  • Ambient temperature (start-up type tested)
    -40 °C
  • Maximum altitude
    ≤ 5000 m (> 2000 m, observe derating)
  • Climatic class
    3K3 (EN 60721)
  • Overvoltage category EN 61010-1
    II
  • Identification
    ABS
  • Noise emission
    EN 55016
  • Electromagnetic HF field
    EN 61000-4-3
  • Fast transients (burst)
    EN 61000-4-4
  • Surge voltage load (surge)
    EN 61000-4-5
  • Frequency
    0 Hz
  • Electric strength, max.
    35 V DC (60 s)
  • Mains buffering
    typ. 14 ms (24 V DC)
  • Typical response time
    300 ms (from SLEEP MODE)
  • Input fuse
    15 A (slow-blow, internal)
  • Insulation voltage input/output
    4 kV DC (type test)
  • Type test (IEC/EN 60950-1) C
    0.5 kV DC
  • Production test A
    2 kV DC
  • Production test D
    0.5 kV DC
  • Conductor cross section flexible
    0.2 mm² ... 1.5 mm²
  • Flexible conductor cross section (ferrule with plastic sleeve)
    0.2 mm² ... 0.75 mm²
  • Static Boost (IStat.Boost)
    6.25 A
  • Selective Fuse Breaking (ISFB)
    30 A (15 ms)
  • No-load proof
    yes
  • Protection against overvoltage at the output (OVP)
    ≤ 32 V DC
  • Types of signaling
    LED
  • Connection labeling
    3.4 +
  • Analog
    4 mA ... 20 mA ±5 % (Load ≤400 Ω)
  • Function
    Signal ground
  • Auxiliary converter stage
    190 kHz ... 220 kHz (Auxiliary converter stage)
  • Degree of protection
    IP20
  • Depth
    125 mm
  • Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
  • Power loss nominal load max.
    < 10 W
  • Shock
    18 ms, 30g, in each space direction (according to IEC 60068-2-27)
  • EMC requirements, power plant
    IEC 61850-3
  • Designation
    Shipbuilding
  • DNV GL noise radiation
    Class B
  • Additional text
    Test Level 2
  • Discharge in air
    15 kV (Test Level 4)
  • Output
    1 kV (Test Level 3 - symmetrical)
  • Power frequency magnetic field
    EN 61000-4-8
  • Test level 2
    150 Hz 1.5 kHz (Test Level 3)
  • Alternating component of DC voltage
    EN 61000-4-17
  • Signals (test level 1)
    100 kHz 1 MHz (Test Level 2 - symmetrical)
  • ECLASS 11.0
    27210901
  • Magnetic circuit breaker tripping
    A1 ... A4 / B2 / C1 ... C2 / Z1 ... Z4
  • Short-circuit-proof
    yes
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • Rise time
    < 1 s (UOUT (10 % ... 90 %))
  • UOut
    > 0.9 x USet (LED lights up green)
  • Default
    Output power ON (>40 kΩ/24 V DC/open bridge between REM and SGnd)
  • Digital
    0 V DC
  • Maximum contact load
    24 V DC
  • Temperature
    30 °C
  • Time
    520000 h
  • Width
    36 mm
  • Depth with alternative assembly
    39 mm
  • Maximum power dissipation in no-load condition
    < 2 W
  • Vibration (operation)
    5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)
  • EMC requirements for noise immunity
    EN 61000-6-1
  • EMC requirements for noise emission
    EN 61000-6-3
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • DNV GL conducted interference
    Class B
  • Frequency range
    50 Hz ... 60 Hz
  • Comments
    Criterion A
  • I/O/S
    asymmetrical
  • Voltage dip
    0 %
  • Input, output (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • Criterion C
    Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
  • ETIM 7.0
    EC002046
  • Input voltage range
    18 V DC ... 32 V DC
  • Typical current consumption
    6.9 A (24 V DC)
  • Switch-on time
    < 1 s
  • Inrush current limitation typical
    1 A
  • Inrush current integral (I2t)
    < 0.05 A2s
  • Type test (IEC/EN 60950-1) D
    0.5 kV DC
  • Production test C
    0.5 kV DC
  • Connection method
    Push-in connection
  • Conductor cross section solid
    0.2 mm² ... 1 mm²
  • Conductor cross section AWG
    24 ... 16
  • Nominal output current (IN)
    5 A
  • Dynamic Boost (IDyn.Boost)
    10 A (5 s)
  • System deviation, dynamic
    < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
  • Residual ripple
    < 10 mVPP
  • UIn
    > 0.8 x UInNom (LED off)
  • Switch contact
    floating
  • Reference potential
    to OUT1, OUT2, REM
  • Side element version
    Aluminum
  • Width with alternative assembly
    122 mm
  • Efficiency
    typ. 92.2 % (24 V DC)
  • Max. permissible relative humidity (operation)
    ≤ 95 % (at 25 °C, non-condensing)
  • Overvoltage category EN 62477-1
    III
  • Standard designation
    Mains variation/undervoltage
  • Conducted noise emission
    EN 55016
  • Electrostatic discharge
    EN 61000-4-2
  • Input
    1 kV (Test Level 3 - symmetrical)
  • Conducted interference
    EN 61000-4-6
  • Pulse-shape magnetic field
    EN 61000-4-9
  • Asymmetrical conducted disturbance variables
    EN 61000-4-16
  • Test level 6
    0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 3)
  • Attenuated oscillating wave
    EN 61000-4-18
  • ECLASS 10.0.1
    27210901
  • ETIM 6.0
    EC002046
  • Type test (IEC/EN 60950-1) A
    2 kV DC
  • Type test (IEC/EN 60950-1) B
    4 kV DC
  • Production test B
    2 kV DC
  • Stripping length
    8 mm
  • Flexible conductor cross section flexible (ferrule, w/o plastic sleeve)
    0.2 mm² ... 1.5 mm²
  • Nominal output voltage (UN)
    24 V DC
  • Setting range of the output voltage (USet)
    24 V DC ... 29.5 V DC (> 24 V DC, constant capacity)
  • System deviation, static
    < 1 % (change in load, static 10 % ... 90 %)
  • System deviation, input voltage change
    < 0.1 % (change in input voltage ±10 %)
  • Connection in series
    yes
  • Feedback voltage resistance
    ≤ 35 V DC
  • POut
    > 100 % (LED lights up yellow, output power > 120 W)
  • Signal option
    Output current
  • MTBF (IEC 61709, SN 29500)
    > 1600000 h (25 °C)
  • Voltage
    1 kV
  • Protection class
    Special with SELV input and output
  • Height
    130 mm
  • Weight
    0.6 kg
  • Ambient temperature (operation)
    -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Degree of pollution
    2
  • Standards/regulations
    EN 61000-4-29
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • Contact discharge
    8 kV (Test Level 4)
  • Test field strength
    100 A/m
  • Signal
    2 kV (Test Level 3 - asymmetrical)
  • Voltage dips
    EN 61000-4-29
  • Test level 1
    15 Hz 150 Hz (Test Level 3)
  • Test level 4
    15 kHz 150 kHz (Test Level 3)
  • Input, output (test level 3)
    10 MHz (Test Level 2 - asymmetrical)
  • Criterion A
    Normal operating behavior within the specified limits.
  • ECLASS 9.0
    27210901
  • Damped oscillating magnetic field
    EN 61000-4-10
  • Test level 3
    1.5 kHz 15 kHz (Test Level 3)
  • Test level 5
    16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
  • Input, output (test level 2)
    100 kHz 1 MHz (Test Level 2 - asymmetrical)
  • Signals (test level 2)
    100 kHz 1 MHz (Test Level 2 - asymmetrical)
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

This item can ship within 24h!

1-year warranty

$252.00

2910119

Stock:

30

Select Qty:

$252.00

$252.00 each

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo