2908199 Phoenix Contact Electrical Measuring & Monitoring Instruments

Phoenix Contact 2908199 Surge protection, consisting of protective plug and base element, with integrated status indicator for a 2-wire floating signal circuit. Indirect grounding via gas-filled surge arrester.
Phoenix Contact

Part#:2908199

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

About the product: Surge protection, consisting of protective plug and base element, with integrated status indicator for a 2-wire floating signal circuit. Indirect grounding via gas-filled surge arrester.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2908199 Phoenix Contact price in the box on the right side or send a quick quote.

2908199 Product Details

  • Depth
    100 mm (incl. DIN rail 7.5 mm)
  • Permissible humidity (operation)
    5 % ... 95 %
  • Flammability rating according to UL 94
    V-0
  • Type
    DIN rail module, two-section, divisible
  • Maximum continuous voltage UC
    55.2 V DC
  • Pulse discharge current Iimp (10/350) µs (line-line)
    0.5 kA
  • Voltage protection level Up (line-line)
    ≤ 180 V (C1 - 1 kV/500 A)
  • Response time tA (line-line)
    ≤ 1 ns
  • Cut-off frequency fg (3 dB), sym. in 150 Ω system
    typ. 1.8 MHz
  • Max. required back-up fuse
    160 mA DC (FF)
  • Impulse durability (line-signalground)
    C1 - 1 kV / 500 A
  • Conductor cross section solid
    0.2 mm² ... 4 mm²
  • Standards/specifications
    IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
  • ECLASS 10.0.1
    27130807
  • ETIM 3.0
    EC000943
  • UNSPSC 12.01
    39121610
  • UNSPSC 20.0
    39121620
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Housing material
    PBT
  • IEC test classification
    C1
  • Operating effective current IC at UC
    ≤ 5 µA
  • Pulse discharge current Iimp (10/350) µs (line-earth)
    0.5 kA
  • Voltage protection level Up static (line-earth)
    ≤ 900 V (C1 - 1 kV/500 A)
  • Response time tA (line-signalground)
    ≤ 100 ns
  • Impulse durability (line-line)
    C1 - 1 kV / 500 A
  • Pulse reset time (line-earth)
    ≤ 30 ms
  • Tightening torque
    0.5 Nm ... 0.6 Nm
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 4.1
    27130801
  • ECLASS 7.0
    27130807
  • UNSPSC 7.0901
    39121610
  • UNSPSC 21.0
    39121620
  • Ambient temperature (operation)
    -40 °C ... 85 °C
  • Color
    traffic grey A RAL 7042
  • Direction of action
    Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
  • Rated current
    160 mA DC (75 °C)
  • Residual current IPE
    ≤ 1 µA
  • Total discharge current Itotal (8/20) µs
    10 kA
  • Voltage protection level Up static (line-line)
    ≤ 45 V (C1 - 1 kV/500 A)
  • Response time tA (line-earth)
    ≤ 100 ns
  • Impulse durability (line-earth)
    C1 - 1 kV / 500 A
  • Screw thread
    M3
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 5.0
    27130801
  • ETIM 4.0
    EC000943
  • ETIM 6.0
    EC000943
  • UNSPSC 18.0
    39121620
  • Width
    6.2 mm +0.1 mm
  • Altitude
    ≤ 4000 m (amsl (above mean sea level))
  • Nominal voltage UN
    48 V DC
  • Nominal discharge current In (8/20) µs (line-earth)
    5 kA
  • Pulse discharge current Iimp (10/350) µs (line-signalground)
    0.5 kA
  • Voltage protection level Up (line-signalground)
    ≤ 750 V (C1 - 1 kV/500 A)
  • Capacity (line-line)
    typ. 1.1 nF
  • Resistance per path
    1.65 Ω ±20 %
  • Pulse reset time (line-signalground)
    ≤ 1500 ms
  • Connection method
    Screw connection
  • Conductor cross section AWG
    24 ... 12
  • ECLASS 11.0
    27130807
  • ECLASS 6.0
    27130800
  • ETIM 7.0
    EC000943
  • UNSPSC 13.2
    39121620
  • Height
    105.8 mm
  • Degree of protection
    IP20
  • Mounting type
    DIN rail: TH 35 - 7.5 mm
  • Nominal discharge current In (8/20) µs (line-line)
    5 kA
  • Nominal discharge current In (8/20) µs (line-signal ground)
    5 kA
  • Voltage protection level Up (line-earth)
    ≤ 900 V (C1 - 1 kV/500 A)
  • Voltage protection level Up static (line-signalground)
    ≤ 750 V (C1 - 1 kV/500 A)
  • Input attenuation aE, sym.
    typ. 0.3 dB (≤ 470 kHz / 150 Ω)
  • Pulse reset time (line-line)
    ≤ 700 ms
  • Max. total discharge current I total max (8/20) µs
    20 kA (1x)
  • Stripping length
    8 mm
  • ECLASS 4.0
    27140201
  • ECLASS 5.1
    27130801
  • ECLASS 9.0
    27130807
  • UNSPSC 6.01
    30212010
  • UNSPSC 11
    39121610
  • UNSPSC 19.0
    39121620

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

2908199

Select Qty:

Average response time: 11 minutes

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo