2908196 Phoenix Contact Electrical Measuring & Monitoring Instruments

Phoenix Contact 2908196 Surge protection, consisting of protective plug and base element, with integrated status indicator for a 2-wire floating signal circuit. Indirect grounding via gas-filled surge arrester.
Phoenix Contact

Part#:2908196

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Checking verified in-stock parts...

About the product: Surge protection, consisting of protective plug and base element, with integrated status indicator for a 2-wire floating signal circuit. Indirect grounding via gas-filled surge arrester.

About the manufacturer: Phoenix Contact develops and manufactures industrial electrical and electronic technology products that power, protect, connect and automate systems and equipment.

Check out the 2908196 Phoenix Contact price in the box on the right side or send a quick quote.

2908196 Product Details

  • Height
    105.8 mm
  • Housing material
    PBT
  • Type
    DIN rail module, two-section, divisible
  • Rated current
    600 mA (56 °C)
  • Total discharge current Itotal (8/20) µs
    10 kA
  • Voltage protection level Up (line-earth)
    ≤ 900 V (C1 - 1 kV/500 A)
  • Response time tA (line-signalground)
    ≤ 100 ns
  • Cut-off frequency fg (3 dB), sym. in 150 Ω system
    typ. 420 kHz
  • Connection method
    Screw connection
  • Screw thread
    M3
  • Stripping length
    8 mm
  • ECLASS 5.0
    27130801
  • ECLASS 6.0
    27130800
  • ETIM 6.0
    EC000943
  • UNSPSC 11
    39121610
  • UNSPSC 13.2
    39121620
  • Depth
    100 mm (incl. DIN rail 7.5 mm)
  • Permissible humidity (operation)
    5 % ... 95 %
  • Flammability rating according to UL 94
    V-0
  • Nominal discharge current In (8/20) µs (line-line)
    5 kA
  • Nominal discharge current In (8/20) µs (line-signal ground)
    5 kA
  • Voltage protection level Up (line-line)
    ≤ 220 V (C1 - 1 kV/500 A)
  • Response time tA (line-line)
    ≤ 1 ns
  • Capacity (line-line)
    typ. 5.2 nF
  • Impulse durability (line-earth)
    C1 - 1 kV / 500 A
  • Impulse durability (line-signalground)
    C1 - 1 kV / 500 A
  • Conductor cross section AWG
    24 ... 12
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 4.1
    27130801
  • ECLASS 9.0
    27130807
  • UNSPSC 12.01
    39121610
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Degree of protection
    IP20
  • Direction of action
    Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
  • Maximum continuous voltage UC
    15 V DC
  • Pulse discharge current Iimp (10/350) µs (line-earth)
    0.5 kA
  • Voltage protection level Up (line-signalground)
    ≤ 750 V (C1 - 1 kV/500 A)
  • Voltage protection level Up static (line-signalground)
    ≤ 750 V (C1 - 1 kV/500 A)
  • Resistance per path
    1.65 Ω ±20 %
  • Max. total discharge current I total max (8/20) µs
    20 kA (1x)
  • Pulse reset time (line-signalground)
    ≤ 1500 ms
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 11.0
    27130807
  • ECLASS 5.1
    27130801
  • UNSPSC 7.0901
    39121610
  • UNSPSC 20.0
    39121620
  • UNSPSC 6.01
    30212010
  • Ambient temperature (operation)
    -40 °C ... 85 °C
  • Altitude
    ≤ 4000 m (amsl (above mean sea level))
  • Mounting type
    DIN rail: TH 35 - 7.5 mm
  • IEC test classification
    C1
  • Residual current IPE
    ≤ 1 µA
  • Operating effective current IC at UC
    ≤ 100 µA
  • Pulse discharge current Iimp (10/350) µs (line-signalground)
    0.5 kA
  • Voltage protection level Up static (line-line)
    ≤ 30 V (C1 - 1 kV/500 A)
  • Input attenuation aE, sym.
    typ. 0.3 dB (≤ 130 kHz/150 Ω)
  • Max. required back-up fuse
    630 mA (FF)
  • Pulse reset time (line-line)
    ≤ 700 ms
  • Conductor cross section flexible
    0.2 mm² ... 2.5 mm²
  • Conductor cross section solid
    0.2 mm² ... 4 mm²
  • ECLASS 10.0.1
    27130807
  • ETIM 3.0
    EC000943
  • UNSPSC 19.0
    39121620
  • Width
    6.2 mm +0.1 mm
  • Color
    traffic grey A RAL 7042
  • Nominal voltage UN
    12 V DC
  • Nominal discharge current In (8/20) µs (line-earth)
    5 kA
  • Pulse discharge current Iimp (10/350) µs (line-line)
    0.5 kA
  • Voltage protection level Up static (line-earth)
    ≤ 900 V (C1 - 1 kV/500 A)
  • Response time tA (line-earth)
    ≤ 100 ns
  • Impulse durability (line-line)
    C1 - 1 kV / 500 A
  • Pulse reset time (line-earth)
    ≤ 30 ms
  • Tightening torque
    0.5 Nm ... 0.6 Nm
  • Standards/specifications
    IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
  • ECLASS 4.0
    27140201
  • ECLASS 7.0
    27130807
  • ETIM 7.0
    EC000943
  • ETIM 4.0
    EC000943
  • UNSPSC 18.0
    39121620
  • UNSPSC 21.0
    39121620

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

Shipping and Delivery Worldwide

calculate cost and time at Checkout


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo