2908062 Phoenix Contact Electrical Measuring & Monitoring Instruments

Phoenix Contact 2908062 Ex i output signal conditioner, HART. Isolates and transmits 0/4…20 mA signals with intrinsic safety to a load in the Ex area. Galvanic 3-way electrical isolation, line fault detection (can be switched off via DIP switch), SIL 2 (SC3), Push-in connection.
Phoenix Contact

Part#:2908062

Manufacturer:Phoenix Contact

Product Lifecycle:Active

Get a quick Quote!

About the product: Ex i output signal conditioner, HART. Isolates and transmits 0/4…20 mA signals with intrinsic safety to a load in the Ex area. Galvanic 3-way electrical isolation, line fault detection (can be switched off via DIP switch), SIL 2 (SC3), Push-in connection.

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Measuring & Monitoring Instruments that you can order at Quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2908062 Phoenix Contact price in the box on the right side or send a quick quote.

2908062 Product Details

  • Height
    116 mm
  • Degree of protection
    IP20
  • Line fault detection
    Response threshold of input current >0.2 mA
  • Output ripple
    < 20 mVrms
  • Max. current consumption
    < 45 mA (at 24 V DC / 20 mA)
  • Conductor cross section flexible
    0.2 mm² ... 1.5 mm²
  • Connection name
    COMBICON connection
  • Degree of pollution
    2
  • Overvoltage category
    II
  • Ambient temperature (operation)
    -40 °C ... 45 °C
  • Description
    Non-Ex applications (EN 61010-1)
  • Rated insulation voltage
    300 Vrms
  • Signal output
    Current output intrinsically safe
  • Transmission Behavior
    1:1 to input signal
  • Stripping length
    8 mm
  • Connection method
    Push-in connection
  • Transmission error, typical
    ≤ 0.05 % (of final value)
  • Step response (10-90%)
    < 140 µs (for 4 mA ... 20 mA step)
  • Insulation
    Safe isolation in accordance with IEC/EN 61010-1
  • Max. output voltage Uo
    25.2 V
  • Max. external inductivity Lo
    100 µH
  • Max. external capacitance Co
    817 nF
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Max. voltage Um
    60 V AC (non-intrinsically-safe circuit)
  • Input impedance
    > 1 MΩ (If there is a line fault)
  • Non-load voltage
    ≤ 27 V
  • Power consumption
    ≤ 1.1 W (at 24 V DC / 20 mA)
  • Maximum transmission error
    0.1 % (of final value)
  • Temperature coefficient, typical
    ≤ 0.005 %/K
  • Interference emission
    EN 61000-6-4
  • Color
    gray
  • Protocols supported
    HART
  • Group
    IIC
  • Conformance
    CE-compliant, additionally EN 61326
  • Temperature
    B
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 5.1
    27210100
  • ETIM 6.0
    EC002653
  • Depth
    114.5 mm
  • Noise immunity
    EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
  • Current input signal
    0 mA ... 20 mA (Function (short-circuit detection off))
  • Voltage drop
    < 2.4 V (at 20 mA)
  • Supply voltage range
    19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
  • Conductor cross section solid
    0.2 mm² ... 1.5 mm²
  • Max. diameter
    2 mm
  • Status display
    Green LED (supply voltage)
  • Designation
    Systematic Capability
  • Electrical isolation
    375 V (Peak value in accordance with IEC/EN 60079-11)
  • Max. internal capacitance Ci
    negligible
  • Additional text
    and EN 61326
  • Width
    12.5 mm
  • Permissible humidity (operation)
    5 % ... 95 % (non-condensing)
  • Altitude
    ≤ 2000 m
  • Current output signal
    0 mA ... 20 mA (Function (short-circuit detection off))
  • Nominal supply voltage
    24 V DC
  • Power dissipation
    < 0.8 W (at 24 V DC / 20 mA)
  • Conductor cross section AWG
    24 ... 16
  • Maximum temperature coefficient
    0.01 %/K
  • Housing material
    PA 6.6-FR
  • HART function
    Yes
  • Max. output power Po
    586 mW
  • Noise emission
    EN 61000-6-4
  • Certificate
    DNV GL TAA00000AG
  • China RoHS
    Environmentally Friendly Use Period = 50 years
  • ECLASS 4.1
    27210100
  • ETIM 7.0
    EC002653
  • Max. output current Io
    93 mA
  • Standards/regulations
    GB 3836.1
  • Identification
    3
  • ECLASS 4.0
    27210100
  • ECLASS 9.0
    27210120
  • Max. internal inductance Li
    negligible
  • Safety-related maximum voltage Um
    253 V AC (125 V DC)
  • EMC
    B
  • Enclosure
    Required protection according to the Rules shall be provided upon installation on board
  • ECLASS 5.0
    27210100
  • ETIM 4.0
    EC002653
  • Test voltage
    2.5 kV AC (50 Hz, 1 min.)
  • Humidity
    B
  • Vibration
    A
  • ECLASS 10.0.1
    27210120
  • ECLASS 11.0
    27210120
  • ECLASS 6.0
    27210100
  • ECLASS 7.0
    27210120

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used surplus in original packaging with original factory seal.

1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

2908062

Select Qty:

Average response time: 11 minutes

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo